SW1-1
CLOSED = LATCHING
OPEN = NON-LATCHING
SW1-2
CLOSED = NORMALLY ENERGIZED
OPEN = NORMALLY DE-ENERGIZED
J1
INT = NON-ISOLATED
EXT = ISOLATED
HIGH ALARM
AUXILLIARY ALARM
NORMALLY
OPEN/CLOSED
LOW ALARM
RELAY CONTACTS
FAULT
A1392

INSTALLATION CHECKLIST

The following checklist is provided as a means of
double checking the system to be sure that all phases
of system installation are complete and have been
performed correctly.
1. Sensors are pointing down and junction boxes are
securely mounted.
2. All cable shields are properly grounded.
3. All junction box covers are tightly installed.
4. Explosion-proof conduit seals have been installed
at all junction box entries (if conduit is being
used).
5. Sensor to controller wiring is correct.
6. Power wiring to the controller is installed and
power source is operational.
7. External loads are properly connected to the con-
troller.
8. Controller is programmed as desired. Record this
information for future reference.
9. Controller is properly installed in the mounting
rack.
2.1
Figure 15—Programming Jumper Plugs and Switches
16
10. Proper ventilation is provided to prevent over-
heating of the controller.
Proceed to System Startup, Setpoint Adjustment, and
Calibration.
Section III
System Startup

STARTUP PROCEDURE

1. Output loads that are normally actuated by the
system should be secured (remove power from all
output devices) to prevent undesired activation.
2. Check all external wiring for proper connection.
Be sure that the sensor has been wired properly.
3. Before installing the controller in the mounting
rack, inspect it to verify that it has not been physi-
cally damaged in shipment. Check the jumper
plugs and rocker switches on the controller for
proper programming, then slide the controller fully
into the mounting rack.
4. Apply power to the system.