15.5. Appendix E : Charge Characteristic
15.5.1. 4-stage charging:
Bulk Entered when charger is started. Constant current is applied until nominal battery voltage is reached, depending on tempera-
ture and input voltage, after which constant power is applied up to the point where excessive gassing is starting (28.8 V resp. 57.6
V, temperature compensated).