Victron energy MultiPlus-II GX Manual page 21

Table of Contents

Advertisement

MultiPlus-II GX
Strong distortion of the input voltage can result in the charger hardly operating or not operating at all. If WeakAC is set, the charg-
er will also accept a strongly distorted voltage, at the cost of greater distortion of the input current.
Recommendation : Turn WeakAC on if the charger is hardly charging or not charging at all (which is quite rare!). Also turn on the
dynamic current limiter simultaneously, and reduce the maximum charging current to prevent overloading the generator if neces-
sary.
Note: when WeakAC is on, the maximum charge current is reduced by approximately 20%.
BoostFactor This value adjusts the PowerAssist behaviour. If you are experiencing issues with PowerAssist (e.g. overload),
please consult with a specialist trained by Victron Energy before attempting to modify.
Programmable (AUX) relay
The relay can be programmed for all kinds of other applications, for example as a starter relay for a generator.
Auxiliary AC output (AC-out-2)
Intended for non-critical loads and directly connected to the AC input. With current measurement circuit to enable PowerAssist.