INTERFACE SERIES
Installation & Operation Instructions
PXP2.3, PXP2.3FS, PXP2.3LG
GENERAL INFORMATION
The PXP2.3 is an electric to pneumatic transducer which
converts an analog electrical input signal to a
proportional pneumatic output. The PXP2.3 will
automatically modulate its control valve(s) to regulate
the branch line pressure to the selected set point as
determined by the input signal. The PXP2.3 o ers four
selectable input ranges which convert to a 0 to 15 psig
modulating output (See EPC product for 0 to 20 psig
outputs). A 0-5 VDC feedback signal indicating the
resultant branch line pressure is also provided. This
signal varies linearly with branch pressure (0 volts= 0
psig, 5 volts = 15 psig). The PXP2.3 incorporates two
valves and does not use air at set point. It's branch
exhaust ow and response time are not limited by an
internal restrictor and are similar to its load rate. If power
fails to the PXP2.3, branch line pressure remains
constant if the branch line does not leak air. The
PXP2.3FS is equipped with a N.O. branch exhaust valve
which allows exhaust of branch air on power failure. A
manual override (jumper selectable), which controls the
output
pressure,
is
troubleshooting.
MOUNTING INSTRUCTIONS
Circuit board may be mounted in any position. If
circuit board slides out of snap track, a
non-conductive "stop" may be required. Use only
ngers to remove board from snap track. Slide
out of snap track or push against side of snap
track and lift that side of the circuit board to
remove. Do not flex board or use tools.
WIRING INSTRUCTIONS
PRECAUTIONS
Remove power before wiring. Never
connect or disconnect wiring with power
applied.
When using a shielded cable, ground the
shield only at the controller end. Grounding
both ends can cause a ground loop.
• It is recommended you use an isolated
UL-listed class 2 transformer when powering
the unit with 24 VAC. Failure to wire the
devices with the correct polarity when
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
provided
for
setup
FIGURE 1: DIMENSIONS
PXP
2.18"
(55.37mm)
PXP With Gauge
and
Ø1.64"
(41.66mm)
Page 1
Phone: 1-888-967-5224
Website: workaci.com
3.25" (82.55mm)
2.18"
(55.37mm)
2.70"(68.58mm)
2.70" (68.58mm)
3.65" (92.71mm)
2.95" (74.90mm)
Version: 4.0
I0000599
0.70"
(17.78mm)
2.20"
(55.92mm)

Advertisement

loading

Summary of Contents for aci INTERFACE Series

  • Page 1 INTERFACE SERIES Phone: 1-888-967-5224 Installation & Operation Instructions Website: workaci.com PXP2.3, PXP2.3FS, PXP2.3LG FIGURE 1: DIMENSIONS GENERAL INFORMATION The PXP2.3 is an electric to pneumatic transducer which 3.25” (82.55mm) converts an analog electrical input signal to a proportional pneumatic output. The PXP2.3 will...
  • Page 2 MOV, 0-20mA DC/AC Transorb, Transient Voltage Suppressor (ACI Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side of 0-15V the power supply.
  • Page 3 0 psig. WARRANTY The PXP Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com. W.E.E.E. DIRECTIVE At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.
  • Page 4 PRODUCT SPECIFICATIONS NON-SPECIFIC INFORMATION 24 VAC (+/-10%), 50 or 60Hz, 24 VDC (+10%/- 5%) Supply Voltage: 160 mA maximum, 200 mA on fail safe models Supply Current: 0-5 VDC @ 10,000 | 0-10 VDC @ 10,000 | 0-15 VDC @ 10,000 | 0-20 mA @ Input Signal Source (@ Impedance):...