Technical Specifications; How To Replace The Battery; Operation Modes - Pima DGS Series Installation Instructions Manual

Wireless gas detector
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1

Technical specifications

Frequency
Models
(MHz)
One-Way
433.92
DGS143
868.95
DGS187
 Sensitivity: Meets UL-1484 & EN-
50194, before 25% of the LEL.
Content of the product package
 DGS detector
 Transformer + cable
Mounting guidelines
 Mount the DGS on a flat surface, near the roof or the floor, and where gas leakage is more probable. Make sure to choose a location
that is not too near gas appliances, but yet not too far from such appliances.
 Natural gas is lighter than air; therefore, mount the gas detector approximately 30cm below the ceiling, if the detector will be used
for the purpose of detecting this gas.
 Butane and Propane are heavier than air; therefore, mount the gas detector approximately 30cm above the floor, if the detector will
be used for the purpose of detecting one of these gases.
 Leave proper space between the detector and the wall/ceiling, for the ventilation slots (no. 6 in the figure above) not be blocked.
 Mount the detector near a standard 220V outlet.
 Do not mount the detector directly above cooking appliances, or near fans.

How to replace the battery

The battery compartment is located at the back of the DGS. To replace the battery, follow the next steps.
1.
Remove the detector from the bracket by pressing the projecting part on the bottom, and pulling it upwards.
2.
Open the battery compartment (no. 8 in the figure above); use a slotted screwdriver if required.
3.
Remove the battery and insert a new one; observe polarity! The buzzer will sound a long beep and the green LED will start flashing.
4.
Place the detector on the bracket and push it downwards until clicked into place.
5.
Test the detector - see how below.
How to install the DGS
Mount the detector on a flat surface. Follow the next steps.
1.
Remove the detector from the mounting bracket (no. 7 in the figure above): press the projecting part on the bottom and pull the
bracket downwards.
2.
Use the supplied screws and mount the bracket vertically on the designated surface.
Caution: The detector MUST be mounted in vertical position, or its sensitivity and performance
will be affected.
3.
Open the battery compartment (no. 8 in the figure above. Use a slotted screwdriver if required) and insert the supplied battery -
all three LEDs will flash once and a long beep will be sounded. After that the green LED will start flashing. Note: the detector's
warm-up time is three minutes.
4.
Attach the detector to the mounted bracket and push it downward, until clicked into place.
5.
Connect the supplied transformer's USB cable to the detector and to a 220V AC outlet.
6.
Enroll the detector; see the alarm system's installation guide for details.
The LEDs
When connecting the DGS to power, all three LEDs flash once and a long beep is sounded. After that the green LED continue to flash for
three minutes (warm-up time), before the detector becomes operable and starts the process of continually sampling the air around it.
Color and state
Description
Green, blinking
Warm-up time (three minutes); see
Green, solid
Normal mode
Yellow, blinking
Trouble event; see "Malfunction signals" below.
Red, blinking
Alarm event

Operation Modes

 Warm-up: the first three minutes after the unit is powered up, and before the detector becomes operable.
 Standby: the normal operation mode, during which the surrounding air is sampled every 10 seconds, and the detector is self-tested
every 160 seconds. The green LED will illuminate if no trouble exists.
Silencing modes
 Silence: pressing the Test/Silence button (no. 5 in the figure above) when the detector is alarming, silence it for 9 minutes. If the gas
concentration remains high or is becoming high again during the silence time, the detector will sound the alarm again.
 Hush: pressing the Test/Silence button when the detector is in trouble situation, silence it for one hour.
 End of Life: five Years (Typical Usage).
 Standards: Meets EN-50131-1, CE compliance.
Two-Way
 Power:
DGS243
o Main: 100~240, VAC to 5VDC, USB Adapter
DGS287
o Backup Battery: 1X CR123A, 3V, Lithium.
o Standby Current: 17mA
 Backup battery
 Mounting screws and labels
Operation Modes
below.
-2-
 Weight: 200gr
 Dimensions: 11.9 X 8 X 4.4 cm
 Battery life: Up to 5 Years
(Typical Usage)
 Temperature: -10 to +50 °C
 Humidity (Max.): Up to 93% R.H.,
Non-condensing.
 This guide