Huawei PDU8000 User Manual page 80

Modular precision power distribution cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision Power Distribution Cabinet
User Manual
No.
2
3
4
5
6
7
Issue 01 (2016-02-27)
Alarm
Alarm
Name
Severity
Configurin
Warning
g board ...
Failed to
Critical
configure
board
Board
Critical
quantity
inconsisten
cy
Loading
Warning
board ...
Failed to
Critical
load board
Abnormal
Major
board
power
supply
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Possible
Impact
Cause
The MDU is
The MDU is
configuring
configuring
the power
the power
distribution
distribution
detection
detection
board.
board.
Failed to
The MDU
configure the
version does
power
not match the
distribution
power
detection
distribution
board.
detection
board.
The actual
Detection
number of
board
power
fault
distribution
The cable
detection
has
boards is
become
different from
loose.
the configured
number.
The
N/A
application is
being loaded
to the power
distribution
detection
board.
Failed to load
N/A
the
application to
the power
distribution
detection
board.
The voltage of
N/A
a power input
to the
detection
board is less
than 9.5 V.
9 Operation and Maintenance
Solutions
N/A
Use the latest
upgrade package to
activate the board.
Check whether
the run indicator
of the detection
board is steady
on. If no, replace
the detection
board.
Check whether
the CAN cable is
securely
connected.
Load again. If the
fault persists, contact
Huawei technical
support.
Reload the
application.
Replace the detection
board.
74

Advertisement

Table of Contents
loading

Table of Contents