Download Print this page

GE D20 ME Quick Start Manual page 8

Advertisement

GE Power Systems
Introduction to Downloading Flash Code,
Upgrading
Code files for previous D20M modules are created in a binary format, usually
From D20M or
called PROM.BIN files.
1 MB Flash
If you are upgrading a device running a D20M to use a D20 ME, you must
D20 ME?
convert the binary code file to a down.shx format before you can download it to
Flash memory.
You must also use Config Pro to adjust the device's Device Properties so that
the new processor will run the converted code file.
If you are upgrading from a D20 ME with 1 MB Flash (Part # 526-2003), you
must modify the Device Properties of the new configuration in ConfigPro to
use the existing code file.
For more information on upgrading from earlier versions, refer to the D20
ME Processor Module Installation and Operations Guide.
Procedure:
To set up the equipment for downloading code files to the D20 ME:
Setup
Step
Configure and Connect PC to D20 ME
1
2
Identify the D20 ME Type
3
4
8
Connect a WESMAINT cable from the PC's COM port to the D20
ME's front panel WESMAINT serial port.
Start Windows' HyperTerminal communication software on the
PC, and configure it as follows:
9600 Bps
8 bit
no parity
VT100 emulation
Xon/Xoff flow control enabled
If you already know the D20 ME BootROM "type", proceed to:
Code Download – D20 ME - D20 Base or
Code Download – D20 ME - CCU.
Restart the D20 ME (power off-on cycle) and watch the monitor.
If the first line of output text is:
P149-0, D20 ME BootROM
P130-0, GE Energy Services CCUME
BootROM
994-0025-1.00-8
Continued
Action
The D20 ME type is:
D20 Base
CCU
D20 ME
Quick Start Guide