Peter electronic VersiStart p III Series Assembly And Commissioning Instructions

Table of Contents

Advertisement

Quick Links

e l e c t r o n i c
Assembly and Commissioning Instructions
Soft Starters
VS p III
Quality is our Drive.

Advertisement

Table of Contents
loading

Summary of Contents for Peter electronic VersiStart p III Series

  • Page 1 e l e c t r o n i c Assembly and Commissioning Instructions Soft Starters VS p III Quality is our Drive.
  • Page 2: Table Of Contents

    User Manual Quality is our Drive. VersiStart p III Qualität ist unser Antrieb. Contents About This Manual ....................4 Disclaimer ......................... 4 Caution Statements ....................5 Electrical shock risk ....................5 Unexpected Operation ....................6 Avertissements à l'attention des clients canadiens ........... 7 Declaration of conformity ..................
  • Page 3 VersiStart p III Load/Save Settings ....................36 USB Save & Load ....................36 Auto-Start/Stop......................37 Network Address ..................... 38 Digital I/O State ....................... 39 6.10 Analog I/O State ...................... 39 6.11 Serial Number & Rating ..................39 6.12 Software Versions ....................40 6.13 Thermistor Reset .....................
  • Page 4 VersiStart p III 10.11 7 Inputs ........................77 10.12 8 Relay Outputs ...................... 79 10.13 9 Analog Output ...................... 81 10.14 10 Display ....................... 82 10.15 11 Communications Card ..................84 10.16 12 Pump Input Configuration .................. 87 10.17 13 Flow Protection ....................89 10.18 14 Pressure Protection ....................
  • Page 5: About This Manual

    VersiStart p III About This Manual WARNING Indicates a hazard that may cause personal injury or death. CAUTION Indicates a hazard that may damage the equipment or installation. NOTE Provides helpful information. Disclaimer The examples and diagrams in this manual are included solely for illustrative purposes.
  • Page 6: Caution Statements

    VersiStart p III Caution Statements Caution Statements cannot cover every potential cause of equipment damage but can highlight common causes of damage. It is the installer's responsibility to read and understand all instructions in this manual prior to installing, operating or maintaining the equipment, to follow good electrical practice including applying appropriate personal protective equipment and to seek advice before operating this equipment in a manner other than as described in this manual.
  • Page 7: Unexpected Operation

    VersiStart p III Unexpected Operation WARNING – ACCIDENTAL STARTS In some installations, accidental starts may pose an increased risk to safety of personnel or damage to the machines being driven. In such cases, it is recommended that the power supply to the soft starter is fitted with an isolating switch and a circuit-breaking device (eg power contactor) controllable through an external safety system (eg emergency stop, fault detector).
  • Page 8: Avertissements À L'attention Des Clients Canadiens

    VersiStart p III Avertissements à l'attention des clients canadiens AVERTISSEMENT L'icône AVERTISSEMENT ci-contre signale les informations concernant des risques pouvant entraîner des blessures graves, voire mortelles. Pour votre sécurité, veuillez consulter les avertissements sur cette page ou demander une copie du présent manuel en français auprès de votre distributeur local.
  • Page 9 VersiStart p III AVERTISSEMENT – DÉCONNECTER L'ALIMENTATION PRINCIPALE AVANT D'ACCÉDER AU DÉMARREUR OU À LA CHARGE Le démarreur progressif comporte des protections intégrées qui peuvent déclencher des mises en sécurité dans l'éventualité de défauts et ainsi arrêter le moteur. Des fluctuations de tension, des coupures d'alimentation et des blocages du moteur peuvent produire des mises en sécurité...
  • Page 10: Declaration Of Conformity

    2006/42/EC (Machinery directive) and 2014/35/EU (Low voltage directive) is not proved. The devices of the VersiStart p III series are electrical equipment that is used in industrial electrical power installations. They are designed for application in machines, in order to reduce the starting torque and starting current peaks as well as the tripping torque of drives with three-phase induction motors.
  • Page 11: System Design

    VersiStart p III System Design Feature List Streamlined setup process Customisable protection · Configuration profiles for common · Motor overload · Excess Start Time applications · Built-in metering and inputs/outputs · Undercurrent · Overcurrent · Current imbalance Easy to understand interface ·...
  • Page 12: Model Code

    VersiStart p III Model Code VS p III – – Control voltage C1 = 110~120 VAC or 220~240 VAC C2 = 24 VAC/VDC Bypass B = internally bypassed Nominal current rating Mains voltage 525 = 200 ~ 525 VAC 690 = 380 ~ 690 VAC Model Selection Starter sizing The soft starter must be the correct size for the motor and the application.
  • Page 13 VersiStart p III · In-line installation 3.0-10:350 3.5-15:345 4.0-10:350 4.0-20:340 5.0-5:355 VS p III 24 VS p III 42 VS p III 52 3.0-10:590 3.5-15:585 4.0-10:590 4.0-20:580 5.0-5:595 VS p III 64 VS p III 69 VS p III 105 VS p III 115 VS p III 135 VS p III 184...
  • Page 14 VersiStart p III · Inside delta installation 3.0-10:350 3.5-15:345 4.0-10:350 4.0-20:340 5.0-5:355 VS p III 24 VS p III 42 VS p III 52 3.0-10:590 3.5-15:585 4.0-10:590 4.0-20:580 5.0-5:595 VS p III 64 VS p III 69 VS p III 105 VS p III 115 VS p III 135 VS p III 184...
  • Page 15: Dimensions And Weights

    VersiStart p III Dimensions and Weights Width Height Depth Weight mm (inch) mm (inch) mm (inch) kg (lb) VS p III 24 VS p III 42 (10.7) VS p III 52 VS p III 64 (10.9) VS p III 69 (6.0) (3.6) (13.2)
  • Page 16: Physical Installation

    VersiStart p III Physical Installation 2/T1 4/T2 6/T3 B4 B5 10 1 1 12 13 14 15 21 22 33 34 41 42 44 53 54 B4 B5 10 1 1 12 13 14 15 21 22 33 34 41 42 44 53 54 B4 B5 10 1 1 12 13 14 15 21 22 33 34 41 42 44 53 54 B4 B5 10 11 12 13 14 15 21 22...
  • Page 17: Main Contactor

    VersiStart p III Finger Guard Kit Finger guards may be specified for personnel safety. Finger guards fit over the soft starter terminals to prevent accidental contact with live terminals. Finger guards provide IP20 protection when used with cable of diameter 22 mm or greater. Finger guards are compatible with models VS p III 184 ~ VS p III 580.
  • Page 18: Short Circuit Protection Devices (Scpd)

    VersiStart p III 4.11 Short Circuit Protection Devices (SCPD) Fuses may be installed to protect the soft starter or the installation. Type 1 Coordination Type 1 coordination requires that, in the event of a short circuit on the output side of a soft starter, the fault must be cleared without risk of injury to personnel.
  • Page 19: Iec Coordination With Short Circuit Protection Devices

    VersiStart p III 4.12 IEC Coordination with Short Circuit Protection Devices These fuses were selected based on start current of 300% FLC for 10 seconds. Type 1 Type 2 coordination coordination Nominal SCR I t (A 480 VAC, 65 kA 690 VAC, 65 kA Rating (A) Bussmann NH...
  • Page 20: Ul Coordination With Short Circuit Protection Devices

    VersiStart p III 4.13 UL Coordination with Short Circuit Protection Devices Standard Fault Short Circuit Current Ratings Suitable for use on a circuit capable of delivering not more than the stated level of amperes (symmetrical rms, refer ##1 in table), 600 VAC maximum. ·...
  • Page 21 VersiStart p III High Fault Short Circuit Current Ratings · Maximum fuse rating (A) – High fault short circuit current Suitable for use on a circuit capable of delivering not more than 65,000 rms symmetrical amperes, 480 VAC maximum, when protected by fuses of the stated class and rating (refer ##2 and ##3 in table).
  • Page 22 VersiStart p III · Circuit breakers – High fault short circuit current Suitable for use on a circuit capable of delivering not more than 65,000 rms symmetrical amperes, 480 VAC maximum, when protected by circuit breaker models noted in ##4, ##5 or ##6. Model Breaker 1: Eaton Breaker 2: GE...
  • Page 23: Fuse Selection For Type 2 Coordination

    VersiStart p III 4.14 Fuse Selection for Type 2 Coordination Type 2 coordination is achieved by using semiconductor fuses. These fuses must be able to carry motor start current and have a total clearing I t less than the I t of the soft starter SCRs.
  • Page 24: Specifications

    VersiStart p III 4.15 Specifications Supply Mains voltage (L1, L2, L3) VS p III 525 xxxxB ............ 200 ~ 525 VAC (± 10%) VS p III 690 xxxxB ............ 380 ~ 690 VAC (± 10%) Control voltage (A1, A2, A3) VS p III xxx xxxxB-C1 (A1, A2) .....
  • Page 25: Disposal Instructions

    VersiStart p III Heat dissipation During Start ................. 4.5 watts per ampere During Run VS p III 24 ~ VS p III 52 ............≤ 35 watts approx VS p III 64 ~ VS p III 135 ............ ≤ 50 watts approx VS p III 184 ~ VS p III 250 ..........
  • Page 26: Installation

    VersiStart p III Installation WARNING Do not apply mains voltage to the starter until all wiring is complete. WARNING Always apply control voltage before (or with) mains voltage. Command Source The VersiStart p III can be started and stopped via the digital inputs, remote keypad, communication network, smart card or scheduled auto-start/stop.
  • Page 27: Inputs

    VersiStart p III Inputs CAUTION The control inputs are powered by the soft starter. Do not apply external voltage to the control input terminals. NOTE Cables to the control inputs must be segregated from mains voltage and motor cabling. Input Terminals B4 B5 10 11 12 13 14 15 21 22 B4 B5 10 11 12 13 14 15 21 22...
  • Page 28 VersiStart p III Motor Thermistor Motor thermistors can be connected directly to the VersiStart P III. The soft starter will trip when the resistance of the thermistor circuit exceeds approximately 3.6 kW or falls below 20 W. The thermistors must be wired in series. The thermistor circuit should be run in screened cable and must be electrically isolated from earth and all other power and control circuits.
  • Page 29: Outputs

    VersiStart p III Outputs Output Terminals B4 B5 10 11 12 13 14 15 21 22 B4 B5 10 11 12 13 14 15 21 22 33 34 41 42 44 53 54 33 34 41 42 44 53 54 A3 A1 A2 1/L1 3/L2...
  • Page 30: Control Voltage

    VersiStart p III Control Voltage Control Voltage Terminals B4 B5 10 11 12 13 14 15 21 22 33 34 41 42 44 53 54 A3 A1 A2 A3 A1 A2 1/L1 3/L2 5/L3 2/T1 4/T2 6/T3 Connect the control supply according to the supply voltage being used. ·...
  • Page 31: Power Terminations

    VersiStart p III Power Terminations The power input and output terminals for VersiStart P are at the bottom of the unit. · Models VS p III 24~VS p III 135 use cage clamps. · Models VS p III 184~VS p III 580 use busbars. NOTE Some units use aluminium busbars.
  • Page 32 VersiStart p III Motor Connection VersiStart p III soft starters can be connected to the motor in-line or inside delta (also called three-wire and six-wire connection). When connecting in inside delta, enter the motor full load current (FLC) for parameter 1B. The VersiStart p III will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
  • Page 33: Typical Installation

    VersiStart p III Typical Installation The VersiStart p III is installed with a main contactor (AC3 rated). Control voltage must be supplied from the input side of the contactor. The main contactor is controlled by the main contactor output (33, 34). 1/L1 2/T1 3/L2...
  • Page 34: Quick Setup

    VersiStart p III Quick Setup The Quick Setup Menu makes it easy to configure the VersiStart p III for common applications. The VersiStart p III guides you through the most common installation parameters, and suggests a typical setting for the application. You can adjust each parameter to suit your exact requirements.
  • Page 35: Setup Tools

    VersiStart p III Setup Tools Setup Tools includes options to load or save parameters to a backup file, set the starter's network address, check the status of the inputs and outputs, reset the thermal models or test operation using the Run Simulation. To access the Setup Tools, press MENU to open the Menu then select Setup Tools.
  • Page 36: Run Simulation

    VersiStart p III Run simulation The run simulation simulates a motor starting, running and stopping to confirm that the soft starter and associated equipment have been installed correctly. NOTE The soft starter must be disconnected from mains voltage. The simulation is only available when the soft starter is in Ready state. To use the run simulation: 1.
  • Page 37: Load/Save Settings

    VersiStart p III Load/Save Settings Load/Save Settings allows users to: · Reset the VersiStart P III's parameters to default values · Load parameter settings from an internal file · Save the current parameter settings to an internal file The internal file contains default values until a user file is saved. To load or save parameter settings: Press MENU to open the menu then select Setup Tools.
  • Page 38: Auto-Start/Stop

    VersiStart p III File Locations and Formats Save Parameters and Logs: The VersiStart p III will create a directory at the top level of the USB drive, named with the soft starter's serial number. The event log and parameter settings are saved as individual CSV files, and the soft starter's software and system information are saved to a text file.
  • Page 39: Network Address

    VersiStart p III 4. Adjust the settings as required: Start/Stop Sunday Start/Stop Disable Press the ENTER/MENU and EXIT buttons to Start Time: 00:00 select which information to edit. Stop Time: Use the buttons to change the value. 00:00 5. To save changes, press the ENTER/MENU button. The VersiStart p III will confirm the changes.
  • Page 40: Digital I/O State

    VersiStart p III Digital I/O State The top line of the screen shows the start/stop, reset Digital I/O State Inputs: 00000000 and programmable inputs. Outputs: 00000000 The bottom line of the screen shows the fixed Main Contactor output, then programmable outputs A and B. 10 11 12 13 14 15 21 22 33 34 41 42 44 53 54 10, 11: Reset input...
  • Page 41: Software Versions

    VersiStart p III 6.12 Software Versions The software versions screen reports the version of each software component in the starter: · user interface · motor control · remote keypad (if connected) · parameter list · bootloader · expansion card (if fitted) NOTE Updated software, including alternative languages, can be loaded into the starter via the USB port if required.
  • Page 42: Logs

    VersiStart p III Logs The Logs Menu provides information on events, trips and starter performance. To access the Logs Menu on the local keypad, press MENU to open the Menu then select Logs. On the remote keypad, press LOGS. Event Log The Event Log stores details of the starter's most recent trips, warnings, and operations (including starts, stops and configuration changes).
  • Page 43: Keypad And Feedback

    VersiStart p III Keypad and Feedback The Keypad Local keypad Remote keypad (if installed) versi start p Ready Trip Local 1 Four-line display for status and programming details. 2 Status LEDs. 3 Menu navigation buttons: EXIT: Exit the menu or parameter, or cancel a parameter change. On the local keypad, this button also resets a trip.
  • Page 44: Remote Keypad

    VersiStart p III Remote Keypad The remote keypad can be used to control the soft starter if parameter 1A Command Source is set to 'Remote Keypad'. · If the remote keypad is not selected as the command source, the START, STOP and RESET buttons will have no effect.
  • Page 45: Displays

    VersiStart p III Displays The keypad displays a wide range of performance information about the soft starter. To scroll through the feedback screens, press the buttons. Starter information At power-up, the starter information screen shows details of the starter's rating, software versions and serial number.
  • Page 46 VersiStart p III If a remote keypad is connected, press GRAPH to change the graph data. The graph can show: · motor current · motor temperature · motor pf · analog input data from the smart card (if installed)
  • Page 47: Operation

    VersiStart p III Operation Start, Stop and Reset Commands The VersiStart p III can be started and stopped via the digital inputs, remote keypad, communication network, smart card or scheduled auto-start/stop. The command source can be set via the Setup Tools, or using parameter 1A Command Source.
  • Page 48: Emergency Mode

    Emergency mode can be used in conjunction with any command source. NOTE Although emergency mode operation satisfies the functionality requirements of Fire Mode, Peter Electronic does not recommend its use in situations that require testing and/or compliance with specific standards as it is not certified.
  • Page 49: Auxiliary Trip

    VersiStart p III Auxiliary Trip An external trip circuit (such as a low pressure alarm switch for a pumping system) can be used to trip the soft starter and stop the motor. The external circuit is connected to a programmable input (input A 13, 14 or input B 13, 15). To control the behaviour of the trip, set the following parameters: ·...
  • Page 50: Soft Start Methods

    VersiStart p III Application Start Mode Stop Mode Fan - axial (undamped) Constant Current Coast To Stop Fan - centrifugal Constant Current Coast To Stop (damped) Fan - centrifugal Constant Current Coast To Stop (undamped) Fan - high pressure Constant Current Coast To Stop Mill - ball Constant Current...
  • Page 51 VersiStart p III Constant Current with Current Ramp Current ramp soft starting raises the current from a specified starting level (1) to a maximum limit (3), over an extended period of time (2). Current ramp starting can be useful for applications where: ·...
  • Page 52 VersiStart p III · Fine-tuning Adaptive Control If the motor does not start or stop smoothly, adjust the adaptive control gain (parameter 2L). The gain setting determines how much the VersiStart p III will adjust future adaptive control starts and stops, based on information from the previous start.
  • Page 53: Stop Methods

    VersiStart p III Stop Methods Coast to Stop Coast to stop lets the motor slow at its natural rate, with no control from the soft starter. The time required to stop will depend on the type of load. TVR Soft Stop Timed voltage ramp reduces the voltage to the motor gradually over a defined time.
  • Page 54 VersiStart p III Adaptive Control is ideal for pumping applications, where it can minimise the damaging effects of fluid hammer. We recommend testing the three profiles to identify the best profile for the application. Adaptive Stop Profile Application Late Deceleration High head systems where even a small decrease in motor/pump speed results in a rapid transition between forward flow and reverse flow.
  • Page 55 VersiStart p III Parameter settings: · Parameter 2I Stop Mode: set to 'DC Brake'. · Parameter 2J Stop Time: This is the total braking time (1) and must be set sufficiently longer than the brake time (parameter 2P) to allow the pre- braking stage to reduce motor speed to approximately 70%.
  • Page 56 VersiStart p III Soft Brake For applications with high inertia and/or a variable load requiring the maximum possible braking torque, the VersiStart p III can be configured for soft braking. The VersiStart p III uses a changeover relay to control forward run and braking contactors.
  • Page 57: Jog Operation

    VersiStart p III 9.10 Jog Operation Jog runs the motor at reduced speed, to allow alignment of the load or to assist servicing. The motor can be jogged in either forward or reverse direction. Jog operation is controlled by the start/stop input (11, 12) and parameter 1A Command Source must be set to 'Digital Input'.
  • Page 58: Inside Delta Operation

    VersiStart p III 9.11 Inside Delta Operation When connecting in inside delta, enter the motor full load current (FLC) for parameter 1B. The VersiStart p III will automatically detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
  • Page 59: Programmable Parameters

    VersiStart p III Programmable Parameters 10.1 Programming Menu The Programming Menu lets you view and change programmable parameters that control how the VersiStart p III operates. To open the Programming Menu, press the MENU/ENTER button while viewing the monitoring screens. 10.2 Altering Parameter Values To change a parameter value: ·...
  • Page 60 VersiStart p III Parameter Group Default Setting Kickstart Level 500% Jog Torque Stop Mode TVR Soft Stop Stop Time 00:01 (mm:ss) Adaptive Stop Profile Constant Deceleration Adaptive Control Gain Multi Pump Single Pump Start Delay 00:00 (mm:ss) DC Brake Torque DC Brake Time 00:01 (mm:ss) Brake Current Limit...
  • Page 61 VersiStart p III Parameter Group Default Setting Monday Stop Time 00:00 (hh:mm) Tuesday Mode Start/Stop Disable Tuesday Start Time 00:00 (hh:mm) Tuesday Stop Time 00:00 (hh:mm) Wednesday Mode Start/Stop Disable Wednesday Start Time 00:00 (hh:mm) Wednesday Stop Time 00:00 (hh:mm) Thursday Mode Start/Stop Disable Thursday Start Time...
  • Page 62 VersiStart p III Parameter Group Default Setting Pressure Sensor Soft Trip and Log Flow Sensor Soft Trip and Log Depth Sensor Soft Trip and Log High Pressure Soft Trip and Log Low Pressure Soft Trip and Log High Flow Soft Trip and Log Low Flow Soft Trip and Log Flow Switch...
  • Page 63 VersiStart p III Parameter Group Default Setting Display Language English Temperature Scale Celsius Graph Timebase 30 seconds Graph Maximum Adjustment 400% Graph Minimum Adjustment Current Calibration 100% Adjustment Lock Read & Write User Parameter 1 Blank User Parameter 2 Blank Communications Card Modbus Address Modbus Baud Rate...
  • Page 64 VersiStart p III Parameter Group Default Setting Flow Sensor Type None Flow Units litres/second Flow at 4 mA Flow at 20 mA Units per Minute at Max Flow Pulses per Minute at Max Flow Units per Pulse Depth Sensor Type None Depth Units metres...
  • Page 65: Motor Details

    VersiStart p III Parameter Group Default Setting Advanced Tracking Gain Pedestal Detect Bypass Contactor Delay 150 ms Model Rating 0020 Screen Timeout 1 minute 10.5 1 Motor Details 1A – Command Source Digital Input The VersiStart p III will accept start and stop Options: (default) commands from the digital inputs.
  • Page 66: Motor Start/Stop

    VersiStart p III 1E – Motor Service Factor Range: 100% - 130% Default: 105% Description: Sets the motor service factor used by the thermal model. If the motor runs at full load current, it will reach 100%. Set according to the motor datasheet.
  • Page 67 VersiStart p III NOTE The VersiStart p III will apply the current limit on all soft starts, including adaptive control. lf the current limit is too low or the start ramp time (parameter 2B) is too short, the motor may not start successfully. 2F –...
  • Page 68: Motor Start/Stop-2

    VersiStart p III 2L – Adaptive Control Gain Range: 1% - 200% Default: Description: Adjusts the performance of Adaptive Control. This setting affects both starting and stopping control. 2M – Multi Pump Options: Single Pump (default) Manifold Pump Description: Adjusts the performance of adaptive control to suit installations with multiple pumps connected to a common outlet manifold.
  • Page 69 VersiStart p III NOTE VersiStart p III soft starters are not suitable for controlling two separate motors. The secondary parameter set should only be used for a secondary configuration of the primary motor. 3A – Start Mode-2 Options: Constant Current (default) Adaptive Control Description: Selects the soft start mode.
  • Page 70 VersiStart p III Description: Sets the level of the kickstart current. 3H – Jog Torque-2 Range: 20% - 100% Default: Description: Sets the current limit for jog operation. 3I – Stop Mode-2 Options: Coast To Stop TVR Soft Stop (default) Adaptive Control DC Brake Soft Brake...
  • Page 71: Auto-Start/Stop

    VersiStart p III Description: Sets the amount of brake torque the VersiStart p III will use to slow the motor. 3P – DC Brake Time-2 Range: 0:01 - 0:30 (minutes:seconds) Default: 1 second Description: Sets the duration for DC injection during a braking stop. 3Q –...
  • Page 72 VersiStart p III Description: Sets the auto-start time for Sunday (24 hour format). 4D – Sunday Stop Time Range: 00:00 - 23:59 Default: 00:00 Description: Sets the auto-stop time for Sunday (24 hour format). 4E – Monday Mode Options: Start/Stop Disable (default) Stop Only Enable Start Only Enable Start/Stop Enable...
  • Page 73: Protection Levels

    VersiStart p III 4N – Thursday Mode Options: Start/Stop Disable (default) Stop Only Enable Start Only Enable Start/Stop Enable Description: Enables or disables auto-start/stop for Thursday. 4O – Thursday Start Time Range: 00:00 - 23:59 Default: 00:00 Description: Sets the auto-start time for Thursday (24 hour format). 4P –...
  • Page 74 VersiStart p III 5B – Current Imbalance Delay Range: 0:00 - 4:00 (minutes:seconds) Default: 3 seconds Description: Slows the VersiStart P III's response to current imbalance, avoiding trips due to momentary fluctuations. 5C – Undercurrent Range: 0% - 100% Default: Description: Sets the trip point for undercurrent protection, as a percentage of motor full load current.
  • Page 75: Protection Action

    VersiStart p III 10.10 6 Protection Action 6A – Current Imbalance Options: Soft Trip and Log The soft starter will stop the motor as selected in (default) parameter 2I or 3I Stop Mode, then enter trip state. The trip must be reset before the VersiStart p III can restart.
  • Page 76 VersiStart p III 6G – Network Communications Options: Soft Trip and Log (default) Warn and Log Trip Starter Log Only Stop Description: Selects the soft starter's response to the protection event. If set to Stop, the VersiStart p III will perform a soft stop, then can be restarted without a reset.
  • Page 77 VersiStart p III 6N – Pressure Sensor Options: Soft Trip and Log (default) Warn and Log Trip Starter Log Only Description: Selects the soft starter's response if it detects a fault with the pressure sensor. 6O – Flow Sensor Options: Soft Trip and Log (default) Warn and Log Trip Starter...
  • Page 78: Inputs

    VersiStart p III 6U – Flow Switch Options: Soft Trip and Log (default) Warn and Log Trip Starter Log Only Description: Selects the soft starter's response if the flow sensor closes (switch type sensors only). 6V – Well Depth Options: Soft Trip and Log (default) Warn and Log Trip Starter...
  • Page 79 VersiStart p III 7B – Input A Trip A trip can occur at any time when the soft starter Options: Always Active is receiving power. Operating Only A trip can occur while the soft starter is running, (default) stopping or starting. A trip can only occur while the soft starter is Run Only running.
  • Page 80: Relay Outputs

    VersiStart p III 7I – Reset/Enable Logic Options: Normally Closed (default) Normally Open Description: Selects whether the reset input (10, 11) is normally open or normally closed. NOTE If the reset input is active, the starter will not operate. 7J – Input A Name Options: Input A Trip (default) Custom Message...
  • Page 81 VersiStart p III The relay closes when the soft starter receives a Soft Brake Relay stop signal, and remains closed until the end of soft brake. Description: Selects the function of Relay A. Relay A is a changeover relay. 8B – Relay A On Delay Range: 0:00 - 5:00 (minutes:seconds) Default:...
  • Page 82: Analog Output

    VersiStart p III Description: Sets the level at which the high current flag operates, as a percentage of motor full load current. 8I – Motor Temperature Flag The VersiStart p III has a motor temperature flag to give early warning of abnormal operation.
  • Page 83: Display

    VersiStart p III 10.14 10 Display 10A – Language Options: English (default) Português Chinese Français Español Italiano Deutsch Russian Description: Selects which language the keypad will use to display messages and feedback. 10B – Temperature Scale Options: Celsius (default) Fahrenheit Description: Selects whether the VersiStart p III will display temperatures in degrees Celsius or Fahrenheit.
  • Page 84 VersiStart p III 10G – Adjustment Lock Read & Write Allows users to alter parameter values in the Options: (default) Programming Menu. Read Only Prevents users altering parameter values in the Programming Menu. Parameter values can still be viewed. Description: Selects whether the keypad will allow parameters to be changed via the Programming Menu.
  • Page 85: Communications Card

    VersiStart p III Pump Temperature The pump temperature, as measured by the PT100. This information is only available if the smart card is installed. Description: Selects which information will be displayed on the programmable monitoring screen. 10I – User Parameter 2 Options: Blank (default) Rating Capacity (%)
  • Page 86 VersiStart p III 11E – Devicenet Address Range: 0 - 63 Default: Description: Sets the DeviceNet network address for the soft starter. 11F – Devicenet Baud Rate Options: 125 kB (default) 250 kB 500 kB Description: Selects the baud rate for DeviceNet communications. 11G –...
  • Page 87 VersiStart p III 11N – IP Address 3 Range: 0 - 255 Default: Description: Sets the third component of the soft starter's IP address, for Ethernet communications. 11O – IP Address 4 Range: 0 - 255 Default: Description: Sets the fourth component of the soft starter's IP address, for Ethernet communications.
  • Page 88: Pump Input Configuration

    VersiStart p III NOTE DHCP addressing is available with Modbus TCP and Ethernet/IP. DHCP addressing is not supported with Profinet. 11U – Location ID Range: 0 - 65535 Default: Description: Sets the soft starter's unique location ID. 10.16 12 Pump Input Configuration NOTE The parameters in this group are only active if a smart card is installed.
  • Page 89 VersiStart p III 12F – Pressure at 20 mA Range: 0 – 5000 Default: Description: Calibrates the soft starter to the 20 mA (100%) level of the pressure sensor input. 12G – Flow Sensor Type Options: None (default) Pulses per minute Switch Pulses per unit Analog...
  • Page 90: Flow Protection

    VersiStart p III 12N – Depth Sensor Type Options: None (default) Switch Analog Description: Selects which type of sensor is associated with the depth sensor input on the smart card. 12O – Depth Units Options: metres (default) feet Description: Selects which units the sensor will use to report the measured depth. 12P –...
  • Page 91: Pressure Protection

    VersiStart p III 10.18 14 Pressure Protection NOTE The parameters in this group are only active if a smart card is installed. Pressure protection uses terminals B23, B24 or C33, C34, C43, C44 on the smart card. 14A – High Pressure Trip Level Range: 0 –...
  • Page 92: Pressure Control

    VersiStart p III 10.19 15 Pressure Control Pressure control use terminals B23, B24 on the smart card. NOTE The parameters in this group are only active if a smart card is installed. 15A – Pressure Control Mode Options: Off (default) The VersiStart p III will not use the pressure sensor to control soft starting.
  • Page 93: Depth Protection

    VersiStart p III 10.20 16 Depth Protection NOTE The parameters in this group are only active if a smart card is installed. Depth protection uses terminals B13, B14 or C13, C14 on the smart card. 16A – Depth Trip Level Range: 0 –...
  • Page 94: Advanced

    VersiStart p III 10.22 20 Advanced 20A – Tracking Gain Range: 1% - 200% Default: Description: Fine-tunes the behaviour of the adaptive control algorithm. 20B – Pedestal Detect Range: 0% - 200% Default: Description: Adjusts the behaviour of the adaptive control algorithm for soft stop. 20C –...
  • Page 95: Application Examples

    VersiStart p III Application Examples 11.1 Smart Card - Pump Control and Protection The VersiStart p III smart card is ideal for applications with extensive external inputs, such as pumping situations where external sensors provide additional protection to the pump and motor. In this example, the VersiStart p III controls a bore pump via scheduled start/stop operation.
  • Page 96 VersiStart p III Digital inputs Main contactor Manual start 10, 11 Reset input Manual stop 11, 12 Start/stop input Automatic operation 13, 14 Programmable input A (scheduled start/stop) (set = Command Override: Digital) Control voltage 33, 34 Main contactor output Three-phase supply R1, R2, R3 Motor temperature protection Smart card...
  • Page 97: Smart Card - Level Controlled Pump Activation

    VersiStart p III 11.2 Smart Card - Level Controlled Pump Activation The VersiStart p III smart card can be used to control start/stop activation of the starter, based on information from external inputs. In this example, the VersiStart p III controls a pump which fills a tank, with maximum and minimum water levels.
  • Page 98: Troubleshooting

    VersiStart p III Troubleshooting 12.1 Protection Responses When a protection condition is detected, the VersiStart p III will write this to the event log and may also trip or issue a warning. The soft starter's response depends on the Protection Action setting (parameter group 6). Some protection responses cannot be adjusted by the user.
  • Page 99 VersiStart p III Display Possible cause/Suggested solution Current Current imbalance can be caused by problems with the motor, imbalance the environment or the installation, such as: · An imbalance in the incoming mains voltage · A problem with the motor windings ·...
  • Page 100 VersiStart p III Display Possible cause/Suggested solution Flow Switch The flow switch sensor (smart card terminals C23, C24) has closed. Related parameters: 6U, 12G Frequency This trip is not adjustable. The mains frequency has gone beyond the specified range. Check for other equipment in the area that could be affecting the mains supply, particularly variable speed drives and switch mode power supplies (SMPS).
  • Page 101 VersiStart p III Display Possible cause/Suggested solution Keypad Parameter 1A Command Source is set to Remote Keypad but the disconnected VersiStart p III cannot detect a remote keypad. If a remote keypad is installed, check the cable is firmly connected to the soft starter. If no remote keypad is installed, change the setting of parameter Related parameters: 1A L1 phase loss...
  • Page 102 VersiStart p III Display Possible cause/Suggested solution Motor overload The motor has reached its maximum thermal capacity. Overload can be caused by: · The soft starter protection settings not matching the motor thermal capacity · Excessive starts per hour or start duration ·...
  • Page 103 VersiStart p III Display Possible cause/Suggested solution · The reset input may be active. If the reset input is active, the Not ready starter will not operate. · The soft starter may be waiting for the restart delay to elapse. The length of the restart delay is controlled by parameter 5H Restart Delay.
  • Page 104 VersiStart p III Display Possible cause/Suggested solution RTD Circuit The smart card has detected a fault with the RTD sensor, or the RTD has activated temperature protection. Related parameters: 6W, 17B SCR Itsm The SCR current surge rating has been exceeded. Related parameters: None The temperature of the SCRs, calculated by the thermal model, is overtemperatur...
  • Page 105: General Faults

    VersiStart p III 12.3 General Faults This table describes situations where the soft starter does not operate as expected but does not trip or give a warning. Symptom Probable Cause · The reset input may be active. If the reset input is Starter "Not Ready"...
  • Page 106 VersiStart p III Symptom Probable Cause · Start performance may be unstable when using a low The soft starter does not control the motor correctly Motor Full Load Current setting (parameter 1B). · Power factor correction (PFC) capacitors must be during starting.
  • Page 107 VersiStart p III Symptom Probable Cause · Make sure you are saving the new value by pressing Parameter settings cannot be stored. the STORE button after adjusting a parameter setting. If you press EXIT, the change will not be saved. The VersiStart p III does not display a confirmation.

Table of Contents