Peter electronic VersiStart II 3L Series Assembly And Commissioning Instructions

Advertisement

Quick Links

e l e c t r o n i c
Softstarter
VersiStart II 3 ... 15L..
Assembly- and Commissioning Instructions
Quality is our Drive.

Advertisement

Table of Contents
loading

Summary of Contents for Peter electronic VersiStart II 3L Series

  • Page 1 e l e c t r o n i c Softstarter VersiStart II 3 ... 15L.. Assembly- and Commissioning Instructions Quality is our Drive.
  • Page 2: Table Of Contents

    VersiStart II 3 ... 15L .. as per 08/18 15700.10001 Table of Contents Page Safety notes Conformity General description Usage to the intended purpose EC Declaration of Conformity Block diagram Commissioning Mounting instructions Connection Power section (see also connection diagram)) Connection control section 10.
  • Page 3 VersiStart II 3 ... 15L .. These commissioning instructions were prepared with great care. Nevertheless, PETER electronic GmbH & Co. KG does not assume liability for damage resulting from mistakes possibly contained in this manual. Technical changes that serve to improve the product are subject to change without notice.
  • Page 4: Safety Notes

    VersiStart II 3 ... 15L .. Safety notes The described devices are electrical equipment for use in industrial electrical power installations. An impermissible removal of the covers during operation can cause serious damage to your health, since these devices contain live parts with high voltages.
  • Page 5: General Description

    VersiStart II 3 ... 15L .. General description The devices are suitable for an operation of 3-phase motors in star or delta connection. In the case of the soft starters of the VersiStart II type the motor voltage is changed in two phases (1L1/5L3) by a generalized phase control and power semiconductors.
  • Page 6: Ec Declaration Of Conformity

    (authorized representatives of the manufacturer / companies placing the product on the market that are established within the Community) Name / Address: PETER electronic GmbH & Co. KG Bruckäcker 9 92348 Berg hereby declares that the following product (device, component, unit) in the version as supplied...
  • Page 7: Block Diagram

    VersiStart II 3 ... 15L .. Block diagram Supply voltage t an t aus (t acc) (t dec) Electronics Boost Trigger Ramp Start pulse control generator Stop M an Control (M acc) for bypass Option...
  • Page 8: Commissioning

    VersiStart II 3 ... 15L .. Commissioning The device is to be put into operation in 3 steps: 1. Mounting 2. Connection and 3. Parameter setting Mounting instructions Caution: Danger to life through electric shock! The following conditions are to be complied with in order to ensure a safe and reliable operation of the VersiStart II: 1.
  • Page 9: Connection Power Section (See Also Connection Diagram))

    VersiStart II 3 ... 15L .. Connection Power section (see also connection diagram)) Terminal 1L1: Mains voltage L1 Terminal 3L2: Mains voltage L2 Terminal 5L3: Mains voltage L3 Terminal 2T1: Motor terminal U Terminal 4T2: Motor terminal V Terminal 6T3: Motor terminal W Connection control section Stop...
  • Page 10: Led Indicators

    VersiStart II 3 ... 15L .. 10. LED indicators On the circuit board there are 2 light-emitting diodes indicating the following operational states. Operational status Green Device is connected to mains voltage Yellow Start completed, device bypassed Yellow - flashing Soft start / Soft stop with increasing or decreasing frequency On the control terminal X1 / X2 (R 1) one signaling relays are available which signal the following...
  • Page 11 VersiStart II 3 ... 15L .. Switch on the supply voltage and start acceleration. Watch the starting behavior and adapt the approporiate parameters to your drive. At any rate, the starting voltage should be adjusted with the potentiometer „initial torque“ so that the motor starts immediately. At the same time, unnecessary humming with the motor being at rest is to be avoided.
  • Page 12: Adjusting Soft Stop

    VersiStart II 3 ... 15L .. 12.3 Adjusting soft stop Note: Soft stop is only useful for pump drives or applications in the case of which the drive comes to a stop immediately after switch off. In the case of drives driving high-inertia loads, soft stop is not sensible.
  • Page 13: Technical Data

    VersiStart II 3 ... 15L .. 13. Technical data Type designation VersiStart II ... L .. 400V ±10% 50/60Hz Mains / motor voltage acc. to DIN EN 50160 (IEC 38) max. Motor rating at 380/415V 5,5kW 7,5kW 11kW 15kW (rated power) max.
  • Page 14: Environmental Conditions

    VersiStart II 3 ... 15L .. 13.1 Environmental conditions Storage temperature -25 ... 75°C Power reduction above 40°C - 2% per 1°C up to max. 60°C and altitudes above 1000m -2% per 100m Ambient temperature 0 ... 40°C up to an installation altitude of 1000m, not exposed to moisture condensation Degree of protection IP 00...
  • Page 15 On the basis of the I²t-value of the power semiconductors, the starting time and possibly the max. starting current, the fuse supplier is able to select a suitable type. Due to the great variety of producers, sizes and types, PETER electronic does not recommend any particular fuses Note 2 f the value of the fuse or the cutoff-I²t-value is selected too small, it may happen...
  • Page 16: Installation Guideline

    15. Installation guideline 15.1 Connection The device is to be installed according to the attached connection diagram. For other connections please consult PETER electronic GmbH & Co. KG. Note: Further connection diagrams for special circuit arrangements are available on our homepage at www.peter-electronic.com.
  • Page 17 VersiStart II 3 ... 15L .. General connection diagram I> I> I> I> I> I> Start 6 +24V Stop VersiStartII .. L . VersiStartII .. L . Stop Start Boost I> I> I> VersiStartII .. L . with litz VersiStartII .. L .
  • Page 18: Typical Connections

    VersiStart II 3 ... 15L .. 15.3 Typical connections Standard circuit Reversing circuit Reversing switch VersiStart II 3 ... 15LDS VersiStart II 3 ... 15LDS S - closed = acceleration; S - open = deceleration S - closed = acceleration; S - open = deceleration Standard circuit for pole-changing motors Reversing circuit for pole-changing motors Reversing...
  • Page 19: Zeitablaufdiagramm

    VersiStart II 3 ... 15L .. 15.4 Zeitablaufdiagramm Start time Initial torque Stop time Stop Start/ Stop Start Start Start Stop Boost Boost...
  • Page 20: Dimensions

    VersiStart II 3 ... 15L .. 15.5 Dimensions Mounting dimensions VersiStart II 3 ... 5,5L.. 102,5 108,5 98,5 92,5 82,5 55,0 VersiStart II 7,5 ... 15L.. 102,5 139,0 129,0 92,5 82,5 55,0 All dimensions indicated in mm.
  • Page 21 VersiStart II 3 ... 15L ..