Model PDP DPU Installation, Preparation and Adjustment
Using Interaction Page 9 Display with an Operator Station
7-2
Digital Input Filter Time Field
Digital Input Filter time is in milliseconds; the default is 10 milliseconds.
This digital filter can be used in place of, or with, the jumper enabled
hardware lag filter on the Model IOP DI modules.
Serial Ports Field
You may connect asynchronous serial devices to serial ports 1 and 2. The
protocols and parameters for these devices are configured here. For
additional information about serial links, refer to Publication 277574, DPU
Embedded Serial Links User's Guide.
Lockout and Log Options Field
In the Lock position, you may disallow certain data DPU Bus operations
from MIS, HOST, REloads, or Screen Edits.
DPU Configuration Page
MODE Run
Active
Backup N
SERIAL I/O PORTS
Port
Baud
Link Type
No
Rate
(0-255)
J6
9600
25 MODB
J7
9600
214 Umax
LOCK OUT ACTIONS
LOG EDIT ACTIONS
Figure 7-1. Interaction Page 9 Display with Sample Configuration.
Use Interaction Page 9 to configure the DPU if a Model 585 Operator
Station is being used instead of a maxSTATION. Refer to Figure 7-2.
Metso Automation MAX Controls • • • • 277573 • • • •
Revision
Date 14/OC/96
Level
Time 09:32:12
DHW 5.0
Model 530 Configuration
CP 5.0
IOM 5.0
DIGITAL
FILTER TIME
10 MSEC
Bits/Char
Stop
Parity
(5,6,7,8)
(1,2)
(O,E,N)
8
1
O
8
2
N
MIS
N HOST?
RELOAD?
MIS
N HOST?
RELOAD?
Stat Page
XON/OFF
RTS/CTS
IN OUT
IN OUT
N N
N N
N N
N N
SCREENS? N
SCREENS? N