ABB Relion 670 Series Product Manual page 140

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Line distance protection REL670
Version 2.2
Table 191. IEC Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
k
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1251-SMALL V1 EN-US
I = I
/I
measured
set
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Operate characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
k
(
)
ç
÷
P
è
-
ø
I
C
EQUATION1370-SMALL V1 EN-US
Reset characteristic:
TR
=
×
t
k
(
)
PR
-
I
CR
EQUATION1253-SMALL V1 EN-US
I = I
/I
measured
set
The parameter setting
Reserved (where, n = 1 - 4) shall not be
used, since this parameter setting is
for future use and not implemented
yet.
140
Range or value
0.05 ≤ k ≤ 999.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
k = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001
Characteristn =
© Copyright 2017 Hitachi Power Grids. All rights reserved
1MRK 506 372-BEN M
Accuracy
IEC 60255-151, ±2.0%
or ±40 ms whichever is
greater
Hitachi Power Grids