Describing the Menu
9. FUNC: In this menu function, the user configures the type of valve characterization curve.
9.1 - LIN: Linear Curve.
9.2 - EP25: Equal Percentage Curve.
9.3 - EP33: Equal Percentage Curve.
9.4 - EP50: Equal Percentage Curve.
9.5 - QO25: Quick Opening Curve. Hyperbolic.
9.6 - QO33: Quick Opening Curve. Hyperbolic.
9.7 - QO50: Quick Opening Curve. Hyperbolic.
10. TRIM: To adjust the input current to the open and close position, correcting small variation on the 4mA
and 20mA.
4: Set the input current as valve closed 0%
20: Set the input current as valve closed 100%
11. LOCK: In this menu function, the user has 2 modes of operation:
YES: In this function, it is not possible to configure neither via local mode or via remote mode.
NO: In this function, it is possible to perform the configuration, either via local mode or via remote mode.
12. TIME: In this menu function, it is possible to view the time in seconds it takes the valve to open or close.
12.1 - 0 100P: Indicates the time the valve takes to go from 0 to 100% of stroke.
12.2 - 100 0P: Indicates the time the valve takes to go from 100 to 0% of stroke.
13. RESET: In this menu function, all default values will be restored, as follows:
YES: Returns to factory settings.
NO: Return to main menu without resetting
14. TIMEOUT: This option allows freely adjustment the time that the positioner waits to perform the calibration. This time can
be configured from 3 to 30 minutes.