Navigation Flowchart; Disp; Setup; Range/Splt (Split Range) - Sense PD200 Quick Manual

Smart valve positioner
Table of Contents

Advertisement

Run Mode
AUTO
5 sec.
AUTO
Press Enter key to
3 sec
select what the
display will show
to Exit
Quit without changes,
?
press
for 3s
3 sec
Press Enter to
to Exit
select the function
3 sec to
Next Menu
3 sec to
Next Menu
3 sec to
Next Menu
3 sec
Press Enter to
to Exit
select this function
3 sec to
Next Menu
3 sec to
Next Menu
3 sec
Press Enter to
to Exit
select this function
3 sec to
Next Menu
3 sec to
Next Menu
3 sec to
Next Menu
Pd200 Navigation Flowchart

1 - DISP

In this menu function is possible to select 5 modes of exhibition on the LCD display:
1.1 - POS: Indicates on the display the current position of the valve from 0% to 100%.
1.2 – SP: Indicates on the display the current input signal value from 0% to 100%. This parameter represents the desired
position value.
1.3 – F BACK : Allows to indicate on display the current positon of the valve in % or the input current in mA .
1.4 – CYCLE: The display will show alternately Position in %, Setpoint in %
1.5 – MV: Indicates on display the manipulated variable in%.
● Press Enter key
to select what the display will show
● Use up or down arrow keys ↑ ↓ to navigate to the item you want to set
● Press Enter key
to set the option
YES
valve will move
NO
Doing
3 sec
Calibration
YES
NO
valve will move
Doing
3 sec
Calibration
YES
Doing
valve will move
NO
Calibration
3 sec
YES
valve will move
NO
3 sec
NO
3 sec
YES
valve will move
NO
3 sec
YES
valve will move
valve will move
To exit SPLT option use
3 sec
NO
3 sec
YES
valve will move
valve will move
Smart Valve Positioner for
Linear or Rotary Valves

2 - SETUP

In this menu function, it is possible to perform 3 positioner calibration modes:
2.1 - TUNE: Allows to perform PID control tuning automatically (Kp, Tr and Td).
2.2 - AUTO: During this adjustment, the positioner will check the positions of
0% and 100% of valve opening and closing.
2.3 - FULL: Executes AUTO SETUP and AUTOTUNING to find complete valve
tuning, including PID parameters.
● Press Enter key
to select this function.
● Use up or down arrow keys ↑ ↓ to navigate to the item you want to set.
● Press Enter key
on calibration procedure you want to do.
● If you are SURE to proceed with the calibration process selected confirm
with the Enter key
.
● If you want to exit without performing the calibration use the up arrow key ↑
for 3 seconds.
3 - RANGE
In this menu function, it is possible to adjust the minimum and
3 s
maximum operating range of valve opening, as follows:
3.1 – ZERO: Allows to adjust the working range from 0 to 20%.
Selected
3.2 – SPAN: Allows to adjust the working range from 80 to
Value
100%.
● Press Enter key
to select this function.
● Use up or down arrow keys↑ ↓ to navigate to the item you
want to set.
● Press Enter key
to select the option.
● Use up or down arrow keys ↑ ↓ to increase or decrease the
value. Hold it to fast increase or decrease.
3 s
● When the value is ready, store it with the Enter key
return to ZERO / SPAN menu to set the other if you want.
Selected
Value
● If you want to quit the ZERO / SPAN menu press the up
arrow key ↑ for 3 seconds and return to main menu
4 - SPLT (Split Range)
In this menu function, it is possible to adjust the positioner to work in 4 mA
to 12mA or 12 to 20mA.
4.1 – (4 ... 12mA): Split Range enabled from 4 to 12mA.
4.2 – (12 ... 20mA): Split Range enabled from 12 to 20mA.
4.3 – (DESAB): Split Range disabled.
● Press Enter key
to select this function.
● Use up or down arrow keys ↑ ↓ to select one option.
● Press Enter key
to select the option.
● If you are SURE to proceed with the split, confirm with the Enter key
● If you are NOT SURE to proceed press the up arrow key ↑ for 3 seconds.
and
○.
1