Describing The Menu - Sense PD200 Quick Manual

Smart valve positioner
Table of Contents

Advertisement

Describing the Menu

1. DISP: In this menu function is possible to select 5 modes of exhibition on the LCD display:
1.1 – POS (Position): Indicates on the display the current position of the valve from 0% to 100%
1.2 – SP (Set Point): Indicates on the display the current input signal value of the positioner from 0% to 100%. This
parameter represents the desired position value that is calculated from the
current input level.
1.3 – F BACK (Feedback): Allows to indicate on display the current positon of the valve in % or the input current in mA
1.4 – CYCLE: When this option is selected, the display will remain indicating alternately the current valve position (POS
in %) and the current value of the input signal (SP in %).
1.5 – MV (Manipulated Variable): Indicates on display the manipulated variable in%.
2. SETUP: In this menu function, it is possible to perform 3 positioner calibration modes:
2.1 - TUNE: llows to perform PID control tuning automatically (Kp, Tr and Td).
2.2 - AUTO: During this adjustment, the positioner will check the positions of 0% and 100% of valve opening and
closing.
2.3 - FULL: Executes AUTO SETUP and AUTOTUNING to find complete valve tuning, including PID parameters.
3. RANGE: In this menu function, it is possible to adjust the minimum and maximum operating range of
valve opening, as follows:
3.1 – ZERO: Allows to adjust the working range from 0 to 20%.
3.2 – SPAN: Allows to adjust the working range from 80 to 100%.
4. SPLT (Split Range): In this menu function, it is possible to adjust the positioner to work in 4 to 12mA or 12 to 20mA.
4.1 – (4 ... 12mA): Split Range enabled from 4 to 12mA.
4.2 – (12 ... 20mA): Split Range enabled from 12 to 20mA.
4.3 – (DESAB): Split Range disabled.
5. PID: In this menu function, you can manually set the parameters Proportional Gain
(KP), Integral Time (TR) and Derivative Time (TD).
5.1 – KP: Allows to adjust the proportional gain of the digital PID control from 0 to 50.
5.2 – TR: Allows to adjust the digital PID control integral time from 0.1 to 50 (s).
5.3 – TD: Allows to adjust the digital PID control derivative time from 0 to 10 (s).
6. ALARM: In this menu function, it is possible to enable the alarm setpoint.
6.1 – E ALM: Enables positioner alarm on:
6.1.1 - LOWER: Allows to adjust the alarm range from 0 to 40% of the valve position.
6.1.2 - UPPER: Allows to adjust the alarm range from 60 to 100% of the valve position.
6.2 – DESAB: Disables the alarm.
7. ACTION: In this menu function, it is possible to configure the valve action mode.
7.1 - DIRECT: Direct acting.
7.2 - REVERS: Reverse acting.
8. MODE: In this menu function, it is possible to define the operating mode of the valve.
8.1 - AUTO: The valve operates in automatic mode.
8.2 - MAN: The valve operates in manual mode and can be moved to 0%, 25%, 50%, 75%, 100% and "ADJUST" (User
Adjustable).
Smart Valve Positioner for
Linear or Rotary Valves
4

Advertisement

Table of Contents
loading

Table of Contents