ARP Control v5.x Troubleshooting Guide

2.8 OPn Process Value

2.9 SHt Process Value

2.10 SSH Process Value

On/Off
Display
SetUp

2.11 FAn Setting

04/20/202
0 © 2013-2020 ARPC L.L.C. All rights reserved.
The
OPn
value is a count of how many times the ARP
boiler sensor has had a wiring or sensor open condition.
Please see section
If there is an intermittent problem due to vibration or a
bad crimp connection, OPn will record the total number of
times the circuit opens and closes. Push the SetUp
button to zero the OPn value. Any changes must be
stored, see
2.22 Store
The
SHt
value is a count of how many times the ARP
boiler sensor has had a short circuit. When the ARP
Control is in the ARP mode of operation, and either the
wiring or sensor is measured as a short circuit,
flash on the screen. SHt will record the total number of
times the boiler sensor has an intermittent short circuit
and then returns to normal operation. A short in the
sensor circuit is usually do to either the two sensor wires
touching or a sensor wire shorted to chassis ground.
See
3.5 SHt
and
information.
The
SSH
value measures the boiler steady-state
maximum temperature. This value is only valid if the
control has been set to the PID control mode, see Set-
Point Function Setting section below.
If the control is tripping in the PID control mode, this
variable is very valuable for troubleshooting when
combined with the above
greater than the
AtS
fridge. If the
SSH
control is tripping when in steady-state operation.
FAn
is the temperature setting at which the ARP will turn
On/Off the fan. There are six fan temperature settings to
select from.
For a non-fan type ARP Control, the fan setting is a fixed
number 0 and cannot be changed.
By momentarily pressing the SetUp button the fan control
temperature can be set to a desired value. Any changes
must be stored, see
4 is the default fan setting value.
3.4 OPn for further
Setting.
RTD TROUBLESHOOTING
AbS
value. If the AbS value is
value, the start up is tripping the
value is greater than
2.22 Store
Setting.
4
information.
SHt
will
for further
AtO
value, the