Wiring - Honeywell F58G Series Product Data

Commercial duct mounted electronic air cleaner
Hide thumbs Also See for F58G Series:
Table of Contents

Advertisement

Fastening Cabinet to Air Handler
Duct Flange
 Remove and set aside the pre-filter and electronic cells.
 Assemble the array of air cleaner units in the required
size according to the Constructing F58 Array section.
 Install a transition to the air handler duct if the opening
is different than the opening of the air cleaner array (see
Fig. 6).
 Move the completed array into place against the air
handler duct flange.
 Attach the air cleaner cabinets securely using no. 8
sheet metal screws or rivets.
Attaching Cell Handles
The cell handle can be installed on either side of the cell:
1. Hold the handle while inserting the solid tab on the
back of the handle into the slot in the cell. Turn the
handle 90 degrees clockwise to align the divided tab
with the square hole. See Fig. 7.
INSTALL HANDLE ON END OF CELL
CLOSEST TO ACCESS DOOR
Fig. 7. Installing cell handle.
2. Insert the divided tab into the square hole.
3. Fold up the wedge and insert it into the divided tab to
lock the handle in place. If necessary, press with a
blunt instrument like the end of a pliers.
Reassembling Air Cleaner
 Insert the electronic cell with the contact board up and
the air flow arrow pointing downstream.
 Tilt the cell toward you and insert the bottom of the cell
first.
 Rotate the top of the cell back into position under the
spring contacts.
 If the cell does not seat properly, check the orientation of
the airflow arrow on the cell.
 Assemble the pre-filter to the front of the unit by first
inserting the lower portion of the pre-filter into the slot
at the bottom of the cabinet.
 Rotate the pre-filter back into position. When properly
installed, the actuator on the pre-filter is inserted into
the wiring tray of the air cleaner.
 Rotate the latch to secure the pre-filter in place.
F58G,H AND F58GUV SERIES COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER
ROTATE 90
DEGREES
FOLD TAB
TO LOCK
HANDLE
IN PLACE
M6047A

WIRING

WARNING
Electric Shock Hazard.
Can cause personal injury.
Be sure line voltage power source is the same as the
voltage and frequency listed on the air cleaner label.
• Power supply wiring system shall provide a disconnect
switch for all poles.
• Assure all wiring complies with local codes and
ordinances.
• Wire the electronic air cleaner directly to the correct
voltage and frequency electrical source. See Fig. 8 and
Fig. 9.
• Install extension box, with cover, for all external plugs
and wiring connections.
• This appliance incorporates an earth connection for
functional purposes only.
Power Connections:
1. Decide which end of the installed array is most acces-
sible for wiring.
2. Cut off the plastic connector for each row of air
cleaners on the end selected.
3. Install a 2 in. x 4 in. (51 mm x 102 mm) extension box
(for example, Steel City part number 53171) to the
end of each row of air cleaners using the holes pro-
vided.
4. Connect power and ground leads to each row of air
cleaners.
5. Install cover (Steel City part number 52-C-1) on each
box.
6. Install box and cover over power connector on oppo-
site end of each row.
Connection to Building Management System:
1. Decide which end of the installed array is most
accessible for wiring.
2. Cut off the plastic connector for each row of air
cleaners on the end selected.
3. Install a 2 in. x 4 in. (51 mm x 102 mm) extension box
to the end of each row of air cleaners (Steel City part
number 59361).
4. Connect each row in parallel to the building manage-
ment system.
5. Install cover on each box (Steel City part number
58-C-1).
7
31-00442—01