Installation - Honeywell F58G Series Product Data

Commercial duct mounted electronic air cleaner
Hide thumbs Also See for F58G Series:
Table of Contents

Advertisement

F58G,H AND F58GUV SERIES COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER
CROSS SUPPORTS
ATTACHED TO DUCT FLANGE
Fig. 5. Array support structure.
Determining Duct Design Requirements
The air cleaner is adaptable to new or existing forced air
heating, cooling and ventilating systems. Transitions,
turning vanes, or offsets may be needed in some
applications.
Use transitions when the duct is a different size than the air
cleaner array in the duct. Gradual transitions reduce air
turbulence and increase efficiency. See Fig. 6. Limit the
duct change to no more than 20 degrees or four inches per
linear foot (one meter per three linear meters).
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
Do not look at the UV lamp when lighting is on. Use
indicator light on the ballast to check status.
In order to prevent exposure to UV light, before
repair of any parts of HVAC system, shut off power
supply to UV system. Do not install in a position
where UV lamp is visible during normal operation of
HVAC equipment.
31-00442—01
AIR HANDLER
DUCT FLANGE
AIR HANDLER DUCT
M13457

INSTALLATION

When Installing This Product...
1. Read these instructions carefully. Failure to follow
2. Check the ratings given in the instructions and on the
3. Installer must be a trained, experienced service tech-
4. After installation is complete, check out product
Unpacking Electronic Air Cleaner
The electronic air cleaner is shipped assembled. Check that
all components are included:
 Galvanized steel cabinet.
 Integral Power Supply (F58G only).
 Two (F58G) or one (F58H) electronic cell(s).
 Pre-filter.
 Two (F58G) or one (F58H) cell handle(s).
 Literature package.
6
20 DEGREE ANGLE PER
SIDE PER FITTING, 4 in.
PER LINEAR FOOT (1M
PER 3 LINEAR METERS).
AIR FLOW
ELECTRONIC AIR CLEANER ARRAY
Fig. 6. Changing duct size gradually
to minimize turbulence.
them could damage the product or cause a hazard-
ous condition.
product to make sure the product is suitable for your
application.
nician.
operation as provided in these instructions.
WARNING
Electric Shock Hazard.
Can cause electrical shock or equipment damage.
Do not connect to power before installation is
complete.
AIR HANDLER DUCT
M13458

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F58h seriesF58guv seriesF58g1016eF58h1006F58g1016euv

Table of Contents