Carbon Monoxide Alarm
Lithium Battery Powered
Wireless Interconnection
Model
Ei208DWRF
Wireless interconnection to RadioLINK Smoke, Heat and Carbon
Monoxide (CO) alarms and accessories
Proven Electrochemical sensor (7 year life)
Lithium battery (sealed in)
Easy to use large Test/Hush button
LCD displays CO level, status messages and icons
Memory feature records if Carbon Monoxide (CO) has been detected
Pre alarm LED and LCD display gives early warning of CO
Loud distinctive alarm sound (85db (A) at 3 metres)
Power, alarm and fault indicator lights
Kitemarked to BS EN50291-1:2010
5 Year Guarantee
Product Description
The Ei208DWRF is a RadioLINK Carbon Monoxide (CO) Alarm
that is powered by a sealed-in Lithium battery.
The alarm has a high performance, proven electrochemical
sensor to sense CO presence. The sensor is individually
calibrated and tested in CO gas on assembly to ensure
accuracy.
The LCD displays CO level, status messages and icons.
The alarm has RadioLINK interconnectivity which enables
wireless transmission of a CO alarm condition to other
RadioLINK alarms and accessories.
The alarm has a twist on mounting base which has multiple
fixing points so it can easily be secured to a ceiling or wall.
The memory feature records the last CO level sensed and can
be useful to check if CO has been present if the home owner
or tenant has been absent from the property.
An easy to use Test/Hush button allows the user to test the
alarm. This checks all aspects of the alarm (sensor, electronics
and sounder).
The alarm has an 'End of life' indicator which will notify the
user when the alarm needs replacing at the end of its seven
year life.
Mile End Business Park, Oswestry, Shropshire SY10 8NN
E & OE Our policy is one of continuous improvement.
We reserve the right to amend designs and specifications without prior notice.
Operation
When dangerous levels of CO are detected, the LCD will
display the CO concentration, the alarm will sound and the
red alarm light will flash as detailed below:
CO Level
Red Light
<43ppm
Off
43-80ppm
1 flash every 2 sec
80-150ppm 1 flash every sec
>150ppm
2 flashes every sec
When lower levels of CO are detected, the alarm will display
a 'VENTILATE' message. When higher levels are detected, the
alarm will display an 'EVACUATE' message
If the alarm is reaching the end of life or a sensor fault is
detected the alarm will display a 'REPLACE UNIT' message
and the amber fault light will flash three times every minute
with three beeps
The 'Test/Hush' button will either silence false alarms (if
briefly pressed) or perform a unit self test (if pressed and
held). Note that the alarm cannot be silenced when sensing
a CO level of 150ppm or above
Tel. 0870 758 4000
Alarm
Off
Sounds after 60-90 mins
Sounds after 10-40 mins
Sounds within 2 mins
Fax. 0870 758 4010