Fan is vibrating excessively
Impeller
Impeller unbalanced due to deposits (dirt or grease)
Impeller unbalanced due to wear
Drive
Unbalanced pulleys
Belts may vibrate excessively
Required air volume not achieved
Impeller
Impeller not centered with inlet collar(s)
Impeller/inlet dirty or clogged
Improper running clearance
Improper inlet cone to wheel fit
Impeller installed or running wrong direction
Incorrect speed of impeller because of:
i)
ii) Belt drive ratio not correct
iii) Too high slip of V-belt
iv) Wrong calibration of inverter
Duct System
Shutters or dampers of the system are closed
Object obstructs fan or duct
Inlet guide vanes are partly close
Dampers closed
Registers closed
Leaks in supply duct
Obstructions near fan outlet or inlet
Sharp elbows near fan outlet or inlet
Improper designed turning vanes
Insulating duct liner loose
Pressure resistance offered by the system higher than
the design value
Fluid density higher than the design value
Improper set inlet vane or damper
Actual system is more restrictive (more resistance to
flow) than expected
Obstructed fan outlet inlets
Elbows, cabinet walls or other obstructions restrict air
flow. Inlet obstructions cause more restrictive
systems but do not cause increased negative
pressure readings near the fan inlet(s)
Fan speed may be increased to counteract the effect
of restricted fan inlet(s). Caution! Do not increase
speed beyond the fan manufacturers
recommendations
No straight duct at fan outlet
(Fans which are normally used in duct system are
tested with a length of straight duct at fan outlet. If
there is no straight duct at the fan outlet, decreased
performance may result.
If it is not practical to install a straight section of duct
at the fan outlet, the fan speed may be increased to
overcome this pressure loss. Caution! Do not increase
fan speed beyond the fan manufacturers
recommendations.)
Projections, dampers or other obstruction in a part of
the system where air velocity is high
Obstructions in high velocity air stream
Possible cause
Possible cause
Wrong motor speed
Remedy
Clean impeller, rebalance the system
Replace impeller
Balance the pulley or the system
Proper sheave alignment and adjust to correct belt
tension
Remedy
Adjust the impeller to the center of inlet collar(s)
Clean the impeller or inlet
Change to correct clearance
Adjust to correct fit
Change to correct rotation by changing poles of
electrical feed line to motor
i)
Change motor or belt drive
ii) Change belt drive
iii) Increase tension of belts
iv) Adjust inverter calibration
Open damper or IVC
Clear obstructed ducts
Open grill/diffuser damper
Open Damper
Open Register
Seal the Leakage
Clear obstruction
Redesign and change elbow
Redesign and change vanes