S+S Regeltechnik Hygrasgard KFF Operating Instructions, Mounting & Installation page 21

Duct humidity/outdoor humidity/temperature sensors
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 10
Schéma de raccordement
5 6
Passive
Plug
sensor
display
°C
1 2 3 4
Schéma de raccordement
Plug
display
UB- GND
Output temperature 0-10V in °C
Output humidity 0-10V in % r.H.
UB+ 24V AC/DC
Raccordement
3 fils
+UB 24V AC/DC
1
Output humidity in % r.H. 0-10V
2
Free
3
–UB-GND
4
Raccordement
KFTF - U ⁄ AFTF - U
4 fils
+UB 24V AC/DC
1
Output humidity in % r.H. 0-10V
2
Output temperature in °C 0-10V
3
–UB-GND
4
DIP switches
0N
multi-range
switching
1 2
r.H.
Offset
Offset
Temperature: ± 5 K
Humidity: ± 10% r.H.
Offset temperature: ± 5 K
Offset humidity: ± 10 % r.H.
5 6
Passive sensor
°C
r.H.
Offset
0N
1 2
DIP switches
multi-range
switching
KFF - U ⁄ AFF - U
Raccordement
2 ou 3 fils*
1
2
3
4
Raccordement
3 ou 4 fils**
1
2
3
4
KFTF - U
Schéma de raccordement**
avec écran
AFTF - U
Schéma de raccordement**
avec écran
Output temperature 4-20mA in °C
Output humidity 4-20mA in % r.H.
KFF - I ⁄ AFF - I
(transmetteur)
+UB 24V DC
Output humidity in % r.H. 4-20mA
Free
–UB-GND (optional for backlighting)
KFTF - I ⁄ AFTF - I
(transmetteur)
+UB 24V DC
Output humidity in % r.H. 4-20mA
Output temperature in °C 4-20mA
–UB-GND (optional for backlighting)
21
5 6
Passive
Plug
sensor
display
0N
1 2
°C
r.H.
Offset
1 2 3 4
Offset temperature: ± 5 K
Offset humidity: ± 10 % r.H.
5 6
Passive sensor
0N
Plug
display
1 2
UB- GND (optional for
LCD background lighting
UB+ 24V DC
Raccordement
4 ou 6 fils
+UB 24V AC/DC
1
Output humidity in % r.H. 0-10V
2
Output temperature in °C 0-10V
3
–UB-GND
4
Passive element
5
e.g. Pt1000, Ni1000,
6
LMZ235Z
Raccordement
4 ou 6 fils
+UB 24V DC
1
Output humidity in % r.H. 4–20mA
2
Output temperature in °C 4–20mA
3
–UB-GND (optional for backlighting)
4
Passive element
5
e.g. Pt1000, Ni1000,
6
LMZ235Z
KFTF - I
avec écran
DIP switches
multi-range
switching
Offset
Temperature: ± 5 K
Humidity: ± 10 % r.H.
AFTF - I
avec écran
°C
r.H.
Offset
DIP switches
multi-range
switching
KFTF - U ⁄ AFTF - U
(capteur de
température passif)
KFTF - I ⁄ AFTF - I
(capteur de
température passif)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents