In-Line Filter Replacement
Instructions
Step 1. Close the isolation ball valve.
Step 2. Depressurize the housing by
pressing the SCHRADER valve on the
bottom of the in-line filter housing, as
shown in Figure 5.
Step 3. Remove the lower section of
the in-line filter housing by turning the
filter housing counterclockwise.
Note: A rubber o-ring/seal is located
between the upper and lower sections
of the filter housing.
Step 4. Remove the old filter by turning
the filter counterclockwise.
Step 5. Replace with new filter, TYCO
Model TFLT Replacement Filter Kit.
The filter is secured to the housing by
turning the filter clockwise.
Note: Ensure the filter housing is
secured only finger/hand tight.
Step 6. Install the rubber o-ring/seal on
the lower section of the filter housing.
Step 7. Re-install the filter housing by
turning the filter housing clockwise.
Step 8. Open the isolation ball valve.
Note: Ensure the filter housing is
secured only finger/hand tight.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Page 5 of 6
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
SMART Air Vent, Dry
Specify: Model TVS-D SMART Air Vent,
Dry, Specify P/N
120 VAC/60 Hz
TSV-D . . . . . . . . . . . . . . . . . . . . . . . . . . . TSVD01
230 VAC/ 50 Hz
TSV-D . . . . . . . . . . . . . . . . . . . . . . . . . . TSVD01E
Replacement Filter Kit
Specify: Model TFLT Replacement filter
Kit, Specify P/N TVDFLT
TFP1263