Blower Testing And Replacement - Bradford White eF Series Troubleshooting Manual And Instructions For Service

Ultra high efficiency water heater
Table of Contents

Advertisement

Blower Testing and Replacement

Does blower energize?
Ensure digital display
shows "Heating." Raise
temperature setpoint if
necessary.
N
Is there 120VAC across
the white and black
wires at the incoming
power harness
connection? (see image
to right).
Call
Y Y
Technical
Support.
Y Y
Refer to ignition control
board illustration below. Is
there 24-28VAC between
blue and yellow wires at
location J8?
Y Y
Is there 120VAC
across white and
N
black wires at the
blower? (see
image above).
Y
Replace blower (see
Blower Replacement
Procedure, pg 36).
36
Service Procedure V
Are collector high limit
Y
switch and pressure
switches in normally
closed position?
N
Check vent.
Correct safety
circuit.
N
Determine power source
problem and correct.
Check amp draw
Is blower wheel
through black wire
Y Y
secured to blower
lead of blower motor.
motor shaft?
Is there approximately
1.5 to 5.5 amps?
N
Replace blower (see
Blower Replacement
Procedure, pg 36).
Are collector high
N
limit switch and
pressure switches in
normally closed.
Y
Correct safety
Replace ignition
circuit problem per
control board.
safety circuit trace
(see Blocked Vent
Pressure Switch
Testing, pg 38).
Repair/replace
wire harness.
J8 Molex Connector
Refer to ignition
Y Y
control board
illustration below. Is
there 24-28VAC
between blue and
yellow wires at
location J8?
Y
N
Black wire
leading to
blower looped
through amp
probe
N
N
Replace ignition
control board.
120 VAC
power
connection
120 VAC check at
blower
120 Control Board Schematic
36