Page 1
The Signature Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician. Please read this manual carefully before installation and keep it for future reference. Owner & Installation Manual Signature Series MGM*95SE*XA Gas Furnace The Signature Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician.
Warm Air Gas Furnace This manual must be left with the homeowner for future reference. Table of Contents Gas Piping Gas Furnace WARNING CAUTION *F507276-C* MRCOOL, LLC (P) 507276-05C Save these instructions for future reference 507276-05C mrcool.com Page 1 of 57...
Page 3
Unit Dimensions NOTE - C*5 Air B FRONT VIEW SIDE VIEW Model 070-3 110-5 135-5 Page 2 of 57 mrcool.com 507276-05C...
Page 4
Parts Arrangement Figure 1. 507276-05C mrcool.com Page 3 of 57...
Gas Furnace Shipping and Packing List MG*95SE*XA MG*95SE*XA NOTE: In Direct Vent installations, combustion air is taken Non-Direct Vent installations, combustion air is taken from NOTE: Safety Information DANGER DANGER OF EXPLOSION! Figure 2. MG*95SE*XA Building Codes Figure 3. mrcool.com 507276-05C...
Page 6
Figure 4. Heating Unit Installed Parallel to Air Handler Unit NOTE: NOTE: Use of Furnace as a Construction Heater Installed in Combination with a Cooling Coil DO NOT USE THE UNIT FOR CONSTRUCTION HEAT UNLESS ALL OF THE FOLLOWING CRITERIA ARE MET: 507276-05C mrcool.com Page 5 of 57...
Page 7
• • NOTE: • • • CAUTION COMPONENT FAILURE AS A RESULT OF FAILURE TO Combustion, Dilution & Ventilation Air NOTE: In Non-Direct Vent Installations, combustion air is General • • • Page 6 of 57 mrcool.com 507276-05C...
WARNING • • • • • • • • • • • • • CAUTION Air from Inside 507276-05C mrcool.com Page 7 of 57...
Page 9
1 square inch per 4,000 Btu (645mm per 1.17kW) per Figure 6. hour of the total input rating of all other equipment in the enclosure. Outside (Inlet Air from Crawl Space and Outlet Air to Figure 8. Ventilated Attic) Outside Page 8 of 57 mrcool.com 507276-05C...
Page 10
Coupling or *Intake Debris Screen Provided 3 in. to 2 in. Transition (Field Provided) * See Maximum Vent Lengths table NOTE Figure 10. (Inlet Air from Ventilated Crawl Space and Outlet Air to Outside) 507276-05C mrcool.com Page 9 of 57...
Page 11
†Allow proper clearances to accommodate condensate trap. ‡For installations on a combustible oor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood ooring. Figure 13. Installation Clearances Page 10 of 57 mrcool.com 507276-05C...
Page 12
Return Air Guidelines Figure 14. Side Return Air (with Transition and Filter) Figure 15. Optional Return Air Base 507276-05C mrcool.com Page 11 of 57...
Page 13
‡For installations on a combustible oor, do not install the furnace directly on carpeting, tile or other combustible materials other than wood ooring. Figure 18. Installation Clearances Horizontal Applications Suspended Installation of Horizontal Unit Figure 17. Figure 19. Typical Horizontal Application Page 12 of 57 mrcool.com 507276-05C...
Page 14
NOTE: Filter Size Furnace Cabinet Width Side Return Bottom Return Platform Installation of Horizontal Unit Table 1. Duct System NOTE: Supply Air Plenum Return Air Plenum NOTE: Figure 20. Return Air - Horizontal Applications 507276-05C mrcool.com Page 13 of 57...
Page 15
F891 CAUTION F628 (Pipe) ASTM PRIMER & SOLVENT CEMENT IMPORTANT SPECIFICATION MGM95*E F656 CANADA PIPE & FITTING & SOLVENT MARKING CEMENT ULCS636 POLYPROPYLENE VENTING SYSTEM ULC-S636 ULC-S636 Canadian Applications Only ULC-S636 Table 2. mrcool.com 507276-05C...
Page 17
NOTE: WARNING CARBON MONOXIDE POISONING HAZARD Venting Practices Figure 21. Removal of the Furnace from Common Vent Page 16 of 57 mrcool.com 507276-05C...
Without the heat of the original furnace flue products, the existing vent pipe MRCOOL, LLC is probably oversized for the single water heater or other appliance. The vent should be checked for proper draw with the remaining appliance.
Page 19
135 ** Which needs most Intake or Table 4. elbows? Exhaust? How many? 2”, 2-1/2” Desired pipe size? or 3” What is the altitude? Use Table 5 to find max pipe length. Figure 24. Page 18 of 57 mrcool.com 507276-05C...
Page 20
MG*M95SE*XA Maximum Allowable Intake or Exhaust Vent Length in Feet Number Capacity Capacity Capacity Capacity of 90° Elbows Used Number Capacity Capacity Capacity Capacity of 90° Elbows Used Table 5A. 507276-05C mrcool.com Page 19 of 57...
Page 21
Maximum Allowable Intake or Exhaust Vent Length in Feet MG*M95SE*XA Number Capacity Capacity Capacity Capacity of 90° Elbows Used Number Capacity Capacity Capacity Capacity of 90° Elbows Used Table 5B. Page 20 of 57 mrcool.com 507276-05C...
Page 22
Maximum Allowable Exhaust Vent Lengths with Furnace Installed in a Closet or Basement Using Ventilated Attic or Crawl Space for Intake Air in Feet Number Capacity Capacity Capacity Capacity of 90° Elbows Used Number Capacity Capacity Capacity Capacity of 90° Elbows Used Table 5C. 507276-05C mrcool.com Page 21 of 57...
Page 25
Inlet Air Roof Terminated (Minimum 12 in. Exhaust Pipe (305mm) above Attic Floor) *Intake Debris Screen (Provided) Furnace * See Maximum Vent Lengths table NOTE: Figure 30. Figure 31. (Inlet Air from Ventilated Attic and Outlet Air to Outside) mrcool.com 507276-05C...
Page 26
Transition (Field Provided) * See Maximum Vent Lengths table NOTE: IMPORTANT Figure 32. (Inlet Air from Ventilated Crawl Space and Outlet Air to Outside) General Guidelines for Vent Terminations IMPORTANT For Canadian Installations Only: 507276-05C mrcool.com Page 25 of 57...
Page 27
Unit Input Size Vent Pipe Winter Design Temperatures ºF (ºC) Diameter Table 6. Conditioned Space Exhaust Pipe Pipe Insulation Intake Conditioned Pipe Unconditioned Space Space Figure 33. Insulating Exhaust Pipe in an Unconditioned Space Page 26 of 57 mrcool.com 507276-05C...
Page 28
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. HVAC Distributing recommends avoiding this location if possible. Figure 34. 507276-05C mrcool.com Page 27 of 57...
Page 29
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. HVAC Distributing recommends avoiding this location if possible. Figure 35. Vent Termination Clearances for Direct Installations Page 28 of 57 mrcool.com 507276-05C...
Page 30
FOR INTAKE AND EXHAUST LINES Figure 36. Direct Vent Roof Termination Kit (15F75 or 44J41) Figure 37. Termination Capacity Exhaust Pipe Size Pipe Size Figure 38. Table 7. Exhaust Pipe Termination Size Reduction NOTE: 507276-05C mrcool.com Page 29 of 57...
Page 31
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away from adjacent property. The exhaust must never be directed toward the combustion air inlet. Figure 39. Page 30 of 57 mrcool.com 507276-05C...
Page 32
3” - 8” (76MM- 203MM) INSULATE EXTERIOR TO FORM PORTION OF SEAL CHIMNEY * SIZE TERMINATION PIPE PER EXHAUST PIPE TERMINATION SIZE REDUCTION TABLE Figure 44. Direct Vent Application Using Existing Figure 41. Chimney 507276-05C mrcool.com Page 31 of 57...
Page 33
INSULATE TO FORM EXTERIOR PORTION OF SEAL CHIMNEY SIZE TERMINATION * SIZE TERMINATION PIPE PER EXHAUST PIPE PER EXHAUST PIPE TERMINATION TERMINATION SIZE REDUCTION TABLE SIZE REDUCTION TABLE Figure 48. Figure 46. Chimney Termination Page 32 of 57 mrcool.com 507276-05C...
Page 37
Figure 55. Condensate Trap Locations Figure 56. Unit with Cooling Coil Using Separate Figure 57. Evaporator Coil Using a Common Drain Drain Figure 58. Evaporator Coil Using a Common Drain Page 36 of 57 mrcool.com 507276-05C...
Page 38
Figure 59. 507276-05C mrcool.com Page 37 of 57...
Gas Piping IMPORTANT CAUTION Leak Check WARNING IMPORTANT Figure 60. IMPORTANT NOTE: WARNING FIRE OR EXPLOSION HAZARD Page 38 of 57 mrcool.com 507276-05C...
Page 40
Figure 61. Gas Piping Figure 62. Gas Piping Horizontal Applications 507276-05C mrcool.com Page 39 of 57...
Page 45
Terminal Designations LINE CIRC COOL NEUTRALS Figure 68. Integrated Control (Automatic Hot Surface Ignition System) CAUTION FOR YOUR SAFETY READ BEFORE OPERATING WARNING BEFORE LIGHTING WARNING Placing the Furnace into Operation mrcool.com 507276-05C...
Page 46
Priming Condensate Trap Figure 69. NOTE: WARNING Turning Off Gas to Unit Gas Valve Operation See Figure 69 STOP! Failure To Operate STOP! Heating Sequence Of Operation 507276-05C mrcool.com...
Page 47
Dial Dial Dial -110 NOTE: -135 Table 9. Gas Meter Clocking Chart Proper Combustion Capacity % for Nat % for L.P. NOTE: Table 10. Manifold Pressure in. w.g. Supply Line Pressure Capacity in. w.g. Propane NOTE Table 11. mrcool.com 507276-05C...
Page 48
High Altitude Information NOTE: Capacity High Altitude Natural Burner Propane Burner Propane Natural 73W80* 51W01 Pressure Switch Requirements at Varying Altitudes Capacity 10U93 11U70 10U93 10U93 11U70 10U93 Table 12. 507276-05C mrcool.com...
Page 49
WARNING CARBON MONOXIDE POISONING HAZARD Do not operate a summer exhaust fan mrcool.com 507276-05C...
Page 50
Other Unit Adjustments Primary Limit Flame Rollout Switches (Two) Pressure Switch Figure 70. Electrical Temperature Rise Blower Speeds Fan Control NOTE: Constant Torque Motor Electronic Ignition Thermostat Heat Anticipation 507276-05C mrcool.com...
Page 53
Allowable Circulation Speeds Model Yellow Blue Brown Black Table 14. Service Exhaust and Air Intake Pipes WARNING ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD. NOTE: Electrical Winterizing and Condensate Trap Care Blower Cleaning Heat Exchanger WARNING Filters Page 52 of 57 mrcool.com 507276-05C...
Page 55
Cleaning the Burner Assembly mrcool.com 507276-05C...
Page 56
Return air duct Operating performance Fresh air grilles and louvers Combustion gases Burners Vent pipe Unit appearance Instruct the homeowners to pay attention to their furnace. Blower access door Red LED Flash Code NOTE Table 15. 507276-05C mrcool.com Page 55 of 57...
Page 57
Cabinet Parts Heating Parts • • • • • Top Cap • • Control Panel Parts • • Transformer • • • • • Blower Parts • • • • • • • • Page 56 of 57 mrcool.com 507276-05C...
Page 58
A copy of all installation instructions for all Product equipment, all venting instructions, all parts lists instructions shall remain with the appliance or equipment at the completion of the installation. GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS. 507276-05C mrcool.com Page 57 of 57...
Page 59
Signature Series MGM*95SE*XA Gas Furnace ELECTRICIAN and/or HVAC TECHNICIAN: LICENSE #: INSTALLATION DATE: INSTALLATION LOCATION: SERIAL NUMBER: The design and specifications of this product and/or manual are subject to change without prior notice. Consult with the sales agency or manufacturer for details.