Greenheck ODFD Series Installation, Operation And Maintenance Manual page 7

Out of wall fire and combination fire smoke dampers
Table of Contents

Advertisement

Approved Breakaway Connections....
Round and Oval Duct Breakaway Connections
Factory furnished duct collars, type R and O, are also
considered breakaway (see Figure 12).
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19mm) sheet metal
screws as follows:
• Ducts up to 22 in. (558mm) wide (or dia.) and less
shall have three screws.
• Ducts larger than 22 in. (558mm) wide (or dia.) up
to and including 36 in. (914mm) wide (or dia.) shall
have five screws.
Manufactured Flanged System Breakaway Connections
Flanged connection systems manufactured by Ductmate, Durodyne, Ward, Nexus, Radiant T-35m, and MEZ are
approved as breakaway connections when installed as illustrated (see Figure 13).
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF
addendum to the SMACNA Duct Construction Standards. Standard 6 in. (152mm) metal clips may be used with
spacing as shown in diagram (see Figure 14 & 15). 3
together corner pieces (see Figure 16).
Sleeve
Duct
Typical TDC/TDF joint
Figure 14
Sleeve
Duct
Typical TDC/TDF joint
6 in. long metal cleat or 1/16 in.
maximum thickness plastic cleat;
12 in. c-c (minimum 1 per side)
Flanged system angles
(Attach per
manufacturer's
instructions)
Duct
Figure 13
Clip Spacing
Std. Clip
Length
9 in.
6 in.
6 in.
60 in. Duct
4 Req'd.
Clip Spacing
Std. Clip
7 in.
Length
48 in. Duct
3 Req'd.
5 in.
6 in.
6 in.
60 in. Duct
36 in. Duct
3 Req'd.
4 Req'd.
5 in.
7 in.
24 in. Duct
48 in. Duct
2 Req'd.
3 Req'd.
5 in.
18 in. Duct
&
Smaller
36 in. Duct
C L
1 Req'd.
3 Req'd.
Duct
5 in.
24 in. Duct
2 Req'd.
18 in. Duct
&
Smaller
1 Req'd.
Figure 15
Type R and O
factory furnished
duct collars qualify
as breakaway
connections.
Figure 12: Type R and O Transition
Fire Damper Sleeve
3/8 in. bolts in corners
between all angles
Neoprene or Butyl gasket
between all angles
in. (9.5mm) metal bolts and nuts may be used to fasten
3
8
6 in.
7 in.
9 in.
5 in.
6 in.
5 in.
7 in.
5 in.
5 in.
C L
Duct
Out of Wall Fire and Combination Fire Smoke Dampers
Duct
Damper
Type B
Wall or Floo
Duct
Damper
Type R, O
Duct End
Flange
Corner Piece
Figure 16
r
Sleeve
3/8 in. bolt
(optional)
7