DALI gateway Plus
DALI gateway Plus
Order no.: 2180 00
Operating instructions
1
Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device or load. In
so doing, take all the circuit breakers into account, which support dangerous voltages to the
device and or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
The DALI control voltage is a functional extra-low voltage (FELV). On installing, ensure safe
isolation between KNX and DALI.
These instructions are an integral part of the product, and must remain with the end customer.
2
Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed tech-
nical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
The function of this device depends upon the software. Detailed information on loadable soft-
ware and attainable functionality as well as the software itself can be obtained from the manu-
facturer´s product database.
Planning, installation and commissioning of the device are carried out with the aid of KNX-certi-
fied software. Full functionality with KNX commissioning software version ETS3.0f onwards.
Intended use
Controlling of luminaires and other applications with DALI operating device in KNX install-
ations e.g. electronic ballast
Installation on DIN rail according to EN 60715 in distribution boxes
Product characteristics
Control of up to 64 DALI devices in up to 32 groups
Individual, group or central addressing
Suitable for operation in emergency lighting systems
16 light scenes
Effect control for dynamic lighting effects or colour games
Read out DALI device state via KNX, e.g. brightness or luminaire error
Manual operation of the DALI groups
Restraint
Feedback of switching state and brightness value in bus and manual mode
Collective feedback
Central switching function
Disabling function for each DALI group
Separate ON and OFF delay
Staircase lighting timer with run-on time
Corridor function: when combined with motion detectors, reduced continuous lighting, if
no motion is detected
Online or offline project design of the DALI devices with ETS plug-in
32587022
10867792
15.06.2020
1 / 7

Advertisement

loading

Summary of Contents for Gira Plus

  • Page 1 DALI gateway Plus DALI gateway Plus Order no.: 2180 00 Operating instructions Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, fire or property damage possible. Please read and follow manual fully. Danger of electric shock. Always disconnect before carrying out work on the device or load. In so doing, take all the circuit breakers into account, which support dangerous voltages to the device and or load.
  • Page 2: Operation

    DALI gateway Plus – Short circuit protection – Surge protection – Overload protection – Operating hours counter – Signal of the global switching status of the DALI devices, e.g. to switch off the mains voltage of the DALI devices to avoid standby losses –...
  • Page 3 DALI gateway Plus After 5 seconds without a button-press, the device returns automatically to bus mode. Switching on/off the permanent manual mode Operation using the button field is programmed and not disabled. ■ Press the c (1) button for at least 5 seconds.
  • Page 4 DALI gateway Plus Connecting the device Control cable: appropriate type, cross-section and routing for the specifications for 250 V cables. DALI and mains voltage wires can be run together in a cable, e.g. NYM 5x1.5 mm². ■ The DALI control voltage is a functional extra-low voltage (FELV). When performing in- stallation, perform the installation in such a way that when an area is disconnected the lines carrying both the DALI and also the mains voltage are disconnected.
  • Page 5 DALI gateway Plus Figure 3: Emergency luminaires supplied through a central safety supply Figure 4: Emergency luminaires, KNX system and DALI gateway supplied through a central safety supply 4.2 Commissioning Load physical address and application program ■ Switch on mains voltage. ■...
  • Page 6: Troubleshooting

    DALI gateway Plus Number of DALI subscribers max. 64 DALI transmission rate 1.2 kBit/s DALI protocol EN 62386 Cable type Sheathed cable 230 V, e,g. NYM DALI cable length with Ø 1.5 mm² max. 300 m with Ø 1.0 mm²...
  • Page 7: Warranty

    The warranty is provided in accordance with statutory requirements via the specialist trade. Please submit or send faulty devices postage paid together with an error description to your re- sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center. Gira Giersiepen GmbH & Co. KG...

This manual is also suitable for:

2180 00