Samsung MIM-B16N Installation Manual page 11

Pulse input module
Hide thumbs Also See for MIM-B16N:

Advertisement

Connectable Meter with PIM
Meter without Separate External Output
f If the pulse constant(Wh/Pulse or m
f
e . g . Pulses per kWh : 1,000 converted to  1Wh/Pulse, Connection is possible!
e . g . Pulses per kWh : 10,000 converted to  0 . 1 Wh/Pulse, Connection is not possible!
Meter with Separate External Output
f Connect according to the pulse output specification .
f
Meter must have more than 4ms Delay Between the first Pulse Input and the Next Pulse
Waveform of CH1~8
limit of Connectable Meter
• Pulse constant range
CAUTION
- Power : 1Wh/Pulse ~ 10,000Wh/Pulse
- Gas : 0 . 0 01m
/Pulse ~ 10m
3
- Water : 1L/Pulse ~ 10 . 0 00L/Pulse
• Pulse width range: 20~1000ms .
/Pulse or L/Pulse) value is an integer, connection is possible .
3
Over 4ms
20~1000ms
/Pulse
3
English-11
Next Pulse