Page 1
80001022 – Issue 1 08/20 Entro-V Controls Part No: 90001308/90001299 BASIC CONTROLLER, DIGITAL CONTROLLER AND OTHER CONTROL OPTIONS User manual...
User Manual Contents PART I – GENERAL DEFINITIONS ......................3 1. General Information ........................3 1.1. Introduction ........................3 1.2. Functions ...........................4 1.3. Accessories ........................5 1.3.1. Temperature Sensor ....................5 1.3.2. Humidity Sensor .....................5 1.3.3. CO Sensor ......................5 1.3.4.
Page 3
User Manual 8.2. Status info (Run out) [RUN]....................2 0 8.3. Fault info (Fault out) [FLT] ....................2 1 9. Modbus Function ........................2 1 9.1. Properties ..........................2 1 9.2. Physical Connection ......................2 1 9.3. Modbus Function .......................2 1 9.4.
User Manual PART I – GENERAL DEFINITIONS 1. General Information 1.1. Introduction Lately, most of the people's life is spent indoors (at home, office, etc) and indoor air quality has become a very important topic. To help reducing the indoor air pollution, heat recovery units have been designed. Mechanical Ventilation with Heat Recovery (MVHR) ensures that the stale air is extracted from the indoor environment, heat is recovered within the plate heat exchanger, and fresh filtered air is supplied indoors being warmed-up within the heat recovery core at a requested temperature.
User Manual 1.2. Functions Function Definition • Manual: 3 steps fan speed control for EC or AC fans o Single fan mode o Individual speed control of the fans Fan Speed Control • Automatic o With sensors (Humdity, CO , etc.) o Constant volume or Constant pressure It is used for increasing fan speed if necessary Boost Function...
User Manual 1.3. Accessories 1.3.1. Temperature Sensor NTC 10kΩ (@25°C) type sensor is used for air temperature measurement. The control card has been calibrated according to this sensor. It is suitable for duct type installation. 1.3.2. Humidity Sensor This sensor is used for air humidity measurement. The control card has been calibrated according to this sensor.
User Manual 3. Controller Options 3.1. Basic Controller The Basic Controller was designed to allow the user to simply control all the basic functions of the unit. There are 3 basic buttons and 4 leds on it. Buttons Fan speed leds (blue) Warning led (red)
User Manual 3.1.2. Leds Description Unit off Fan speed is “high”. Fan speed is “mid”. Fan speed is “low”. Fan speed is “boost”. VOD mode is active. Fire function is active. Failure warning (see Part III). Led is off Led is on Blink Cable connection Cable type: Flat (6x)
User Manual 3.2. Digital Controller The Digital Controller was designed to control all the functions of the unit and to change settings related to the unit. It has 4 buttons and 1 graphic display. Graphic Screen Buttons 3.2.1. Buttons Function Button Activity Unit Start / Stop...
User Manual 3.2.2. Screenshots 1.Screen 4.Screen Main Screen Adjust 5.Screen 2.Screen Company Timer Logo 3.Screen Information “1.Screen” Symbols: Main Screen Info Input “1.Screen” Symbols: Main Screen (for DX Unit) Info Input 13 / 33...
Page 15
User Manual 1.Symbol: Fresh Air Fan 2.Symbol: Exhaust Fan Fan speed “low” Fan speed “low” Fan speed “mid” Fan speed “mid” Fan speed “high Fan speed “high Fan speed “boost” Fan speed “boost” VOD mode is active VOD mode is active 3.Symbol: Heat exchanger (Plate or Rotor) &...
Page 16
User Manual 8.Symbol: Preheater Not available Type: Preheater Status: Closed Type: Preheater Status: Open 9.Symbol: Pymbol for post heater and cooling coil Type: Water coil Not available Status: Closed Type: Heater Type: Water coil Status: Closed Status: Open / Cooling mode Type: Heater Type: Water coil Status: Open...
Page 17
User Manual “2.Screen” Symbols: Timer Info Input Day of the week selection 1.Field Fan mode selection 2.Field Clock selection 3.Field System time information 4.Field “3.Screen” Symbols: Information Info Input Temperature sensor values [°C] 1.Field Sensor values [mV] 2.Field Fan speed values [rpm] (if fan tacho connection is available) 3.Field Fan speed values [%] 4.Field...
Page 18
User Manual “4.Screen” Symbols: Settings Info Input Date setting [YYYY.MM.DD] 1.Field Clock setting [HH:MM] 2.Field day of the week selection. For example, if the 1st day of the week is Monday and today is Wednesday, the entry 3.Field value should be 3, if the 1st day of the week is Sunday and today is Wednesday, the entry value should be 4 Screen contrast value 4.Field...
User Manual PART II – WORKING SCENARIO 1. Fan Speed Control FAN_OA, FAN_RA Fresh air fan “low” speed value Fresh air fan “high” speed value Fresh air fan failure data entry method “tacho” Default values Exhaust air fan “low” speed value Exhaust air fan “high”...
User Manual 4. By-Pass & Rotor Control 4.1. By-Pass Control [BYP] Default values It is better not to use the heat exchanger in terms of energy saving and comfort during the transition seasons such as summer to autumn or spring to summer, when the temperature of the outdoor air changes suddenly and the indoor air can get overheated.
User Manual 5.3. Water Cooling Coil Control [CCW] Default values It is the valve control (on/off) function of the water cooler coil used to reduce the blowing air to the comfort temperature. It can be operated according to room temperature or supply air temperature. 6.
User Manual 8.3. Fault info (Fault out) [FLT] [FLT] Default values It is the information output (dry contact) indicating the device's malfunction. 9. Modbus Function It is the function that controls all the functions and settings of the device through the Building Management System.
Page 23
User Manual Control board supports only two of standard functions of Modbus. These codes are 03 register reading and 06 register writing (below table). In the example below, master wants to know the 16 bit data on 2 register. Corresponding response value of control board is shown on the table below. In the second example, master wants to write the 16 bit data on 2 register and it is reported to control board that the data was written.
User Manual 9.4. Modbus Register List Description Explanation Version of program Versiyon of installed program [MMYY] Unit ON / Off [0,1] 0-Stop / 1-Start Alarm Code Failure code Fresh air fan speed Exhaust air fan speed PWM value of fresh air fan [0,100] PWM value of exhaust air fan [0,100]...
User Manual It is the function that determines the working position of the device in case of fire. When a signal is received from the FRE input (dry contact) of the control board, it will operate depending on one of the following scenarios.
User Manual PART III – ALARM (Failure) 1. Fault Info (Fault out) [FLT] The device displays a warning in case of a malfunction in any of its components. The control card decides whether to continue operating according to the severity of the fault. Fault information is transmitted to the user as a fault code on the controller's display (Digital Controller, Touch Panel, etc.) and warning led in the Basic Controller.
User Manual Annex.A – SERVICE OPERATIONS 1. Basic Controller BUTTONS Function Button Activity Service operation Press for 3 seconds By-Pass function on/off [BYP] Press for 3 seconds Equipments function on/off (Heater, Press for 3 seconds preheater) [HTI] BMS function on/off [BMS] Press for 3 seconds Press for 3 seconds Exit...
Page 28
User Manual “6.Screen” Symbols: Password screen Info Input Password entry 1.Field “7.Screen” Symbols: I/O adjust Info Input Outputs selection (dry contact) (DO) 1.Field Power oputput selection 2.Field Inputs selection (dry contact) (DI) 3.Field Inputs selection (sensor) (AI) 4.Field Inputs Code List (DI) Code Description Code...
User Manual Outputs Code List (DO) Code Description Code Description Not connected Rotor heat exchanger (Part II – 4.2) Unit run out info (Run out) (Part II – 8.2) Water coil (cooling) (Part II – 5.3) Water coil (cooling & heating) Failure info (Fault out) (Part II –...
Page 30
User Manual Description Explanation PWM value (high) of fresh air fan PWM value (low) of exhaust air fan PWM value (mid) of exhaust air fan PWM value (high) of exhaust air fan Countdown for fan failure control Countdown starts when the Countdown for boost panel algorithm is activated, otherwise it is "0"...
Page 31
User Manual Description Explanation Freon system 1.stage info [0,1] 0-Closed / 1-Run [DX1] Freon system 2.stage info [0,1] 0-Closed / 1-Run [DX2] Freon syste four way valve [0,1] 0-Closed / 1-Run info [FWV] Frost protection scenario [0,1] 0-Closed / 1-Run info [FRZ] DO1 Output info [RUN] [0,1]...
Page 32
User Manual Description Explanation Boost Panel status [0,1] 0-Passive / 1-Active PWM value (boost) for Panel [50,100] Boost duration for Panel [1,30] PWM value (boost) for [50,100] Control Board [BST] Boost duration for Control [1,30] Board [BST] VOD Status 0-Passive / 1-Active Sensor lower limit value 0,01 [0,1000]...