Download Print this page
Autonics ABL Series Quick Start Manual

Autonics ABL Series Quick Start Manual

Relay terminal block
Hide thumbs Also See for ABL Series:

Advertisement

Quick Links

ABL Series
Relay Terminal Block (screwless type)
Features
[Common Feature]
●Selectable between independent and load common output with jumper bar
●High tensile force and easy wiring with one-touch screwless type crimp terminal
●Convenient operating status check with operation indicator (blue LED)
[1-point]
●Rated load voltage: 3A
●Selectable between independent and power ommon input with jumper bar
●DIN Rail mounting
●Relay: [Fujitsu] NYP24W-K / [Panasonic] APAN3124
[4-point]
●Rated load voltage: 5A
● Selectable between NPN (+ COM) and PNP (- COM) input with jumper bar
●Relay protection with the cover
●Easy relay replacement with relay ejector or removal lever
●DIN Rail or screw mounting
●Relay: [Fujitsu] NYP24W-K / [Panasonic] APAN3124, PQ1a-24V /
[Omron] G6B-1174P-FD-US
[16-point]
●Rated load voltage: 3A
●Relay protection with the cover
●Easy relay replacement with relay ejector
●DIN Rail or screw mounting
●Relay: [Omron] G6B-1174P-FD-US
Please read "Safety considerations" in instruction
manual before using.
▣ Ordering Information
AB
L
L
04
No. of relay points
Controller
Terminal block
Item
Crimp Terminal Specifications
End Sleeve (ferrule terminal)
crimp terminal
A-44
PQ
U
N
Varistor installation
Input logic
Relay type
C
A
B
C
10 to 12.0
≤ 2.0
≤ 4.1
N
Not installed
Y
Installed
U
Universal
N
NPN
P
PNP
TN
TAKAMISAWA(Fujitsu) NYP
PA
MATSUSHITA(Panasonic) PA
PQ
MATSUSHITA (Panasonic) PQ
R6
OMRON G6B
01
1
04
4
16
16
L
Screwless
H
Hirose connector
L
Screwless
AB
Relay terminal block
A
B
Applicable wire
AWG22-16 (0.30 to 1.25mm
(60℃ only)
(unit: mm)
2
)

Advertisement

loading
Need help?

Need help?

Do you have a question about the ABL Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Autonics ABL Series

  • Page 1 -|Transparent setting guide|- ABL Series Relay Terminal Block (screwless type) Features [Common Feature] ●Selectable between independent and load common output with jumper bar ●High tensile force and easy wiring with one-touch screwless type crimp terminal ●Convenient operating status check with operation indicator (blue LED) [1-point] ●Rated load voltage: 3A...
  • Page 2: Specifications

    IP20 (IEC standard) Approval ABS Series ※ 6 Weight Approx. 148g (approx. 92g) Approx. 150g (approx. 94g) Approx. 143g (approx. 87g) Approx. 144g (approx. 88g) ABL Series Rated load current 3A ASL Series ABL-L01PA-NN ABL-L01TN-NN ABL-L01PA-NY ※1 ABL-L01TN-NY ※1 ABL-L04PA-UN...
  • Page 3 -|Transparent setting guide|- ABL Series Dimensions (unit: mm) Rated load current 5A ABL-L04PQ/R6- 2-Ø5 ● Jumper bar (model: JB-10.2-04L) ※ For the desired application (power/load common), jumper bar is sold separately. 36.2 10.2 4-3.9 30.6 10.2 Rated load current 3A ABL-L01TN/PA- 38.5...
  • Page 4 Rated load current 5A ABL-L04PQ(R6)-UN(UY) ABS Series ABL Series ※ NPN, PNP, LOAD common are operated by the inserting position of the Jumper bar. Please refer to the ‘2. Using jumper bars’ of ‘▣ Replacing Relay and Using Jumper Bar’.
  • Page 5 -|Transparent setting guide|- ABL Series Connections Rated load current 3A ABL-L01PA(TN)-NN(NY) 24VDC INPUT OUTPUT ● ABL-L01PA(TN)-PN(PY) 24VDC OUTPUT INPUT ABL-L04PA(TN)-UN(UY) ※ NPN, PNP, LOAD common are operated by the inserting position of the Jumper bar. Please refer to the ‘2. Using jumper bars’...
  • Page 6 N . C4 N . C1 GND1 GND2 R10- R11- R12- R13- R14- R15- R16- N . C3 ABS Series ABL-H16R6-PN ABL Series ASL Series Power Relay 3 4 1 2 RY10 RY11 RY12 RY13 RY14 RY15 RY16 JP10 JP11 JP12...
  • Page 7 -|Transparent setting guide|- ABL Series Replacing Relay and Using Jumper Bar Rated load current 5A ABL-L04PQ/R6- 1. Replacing relays ① 1) Remove the protection cover. Relay type 2) Push the operation indicator guide in direction to remove the relay. color ※1...
  • Page 8: Installation

    2) Pull the relay ejector to direction ② for removing the relay. ② ① ABS Series Installation ABL Series ※ Each model appearance is different by no. of relay points. ASL Series Power Relay 1. Mounting and removal at DIN rail 2.
  • Page 9: Cautions During Use

    -|Transparent setting guide|- ABL Series Cautions during Use 1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents. 2. Check the polarity of power or COMMON before connecting PLC or other controllers. 3. Do not touch the unit immediately after the load power is supplied or cut.
  • Page 10 -|Transparent setting guide|- Relay Terminal Blocks I/O Terminal Blocks Interface Terminal Blocks Common Terminal Blocks Sensor Connector Terminal Blocks Relay Terminal Blocks I/O Cables Connector Type Cables Open Type Cables Others ABS Series ABL Series ASL Series Power Relay A-53...