SHIPPING, RIGGING, HOISTING AND ASSEMBLY MANUAL ENERGY RECOVERY VENTILATORS LE6X LE8X LE10X RENEWAIRE.COM...
Page 2
(additional charges apply). heater, verify that the air being extracted by the ERV does not See separate unit-specific Installation, Operation and conflict with proper operation of the fuel-burning device. Maintenance manual for further information. RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499...
IMPORTANT USER INFORMATION SAVE THIS MANUAL UNIT INFORMATION In the unlikely event that factory assistance is ever required, information located on the unit label will be needed. Configuration (Option) Code Unit Label (typical) 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM...
If shipping damage is discovered, take digital pictures and note the visible damage on the ship- ping manifest. Notify your RenewAire dealer immediately. Note that whenever possible, accessories such as weather hoods are assembled and then secured for shipping inside the ERV.
Do not lift in high winds. RenewAire will not be responsible for any damage during the rigging, lifting or installing of the unit or modules. Refer to Corner Weight Charts for exact center of gravity.
4.0 MODULE ASSEMBLY 4.1 CONFIGURATION LABEL RenewAire LE series Energy Recovery Ventilators can either be built and shipped factory assembled or be ordered unassembled for applications where modules must be manipulated separately. If the unit was ordered unassembled, then you will need to assemble the modules in the field.
Shipping straps are attached to the modules at the factory. These straps insure proper rigidity when shipping and lifting. Once the straps are removed they may be disposed of along with the screws that held them in place. www.renewaire.com (800) 627- 4499 Shipping Straps Location support@renewaire.com...
THEN 2 MORE BOLTS IN BASE ACCESS BOLT AND NUT SUPPORT. THROUGH HAND HOLES IN EACH MODULE SIDE BASE RAIL TO BE JOINED. 2 BOLTS THROUGH LIFTING LUGS (EACH SIDE OF UNIT) LE Rooftop Unit Base Bolt Locations 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM...
USE A PIPE CLAMP TO ADJUST THE ROOF BEAMS LATERALLY AND THEN BOLT TOGETHER THE TWO ROOF BEAMS. Roof Beam Assembly Graphic 2 Roof Beam Assembly Bolt Locations www.renewaire.com (800) 627- 4499 support@renewaire.com RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499...
Roof Beam Caulking www.renewaire.com (800) 627- 4499 support@renewaire.com 4.5.4 Install Joining Roof Cap A galvanized cap roof flange is provided to seal the roof seam and to maintain a water and airtight seal.
For best results, use a lower torque setting on the power drill. Be careful not to over tighten the screw. Assembly Strap Locations Assembly Strap Installation www.renewaire.com (800) 627- 4499 support@renewaire.com NOTE: Failure to install the assembly straps will compromise the structural integrity of the unit and cause damage during lifting.
Inside the access panel are low voltage and high voltage wiring connection compartments. The low voltage compartment is the lower compartment and the high voltage compartment is the upper compartment. Both compartments are open on the left side to access the wiring harness plugs that are www.renewaire.com (800) 627- 4499 support@renewaire.com www.renewaire.com...
4.7 INSTALL WEATHERHOODS Rooftop units (RT models) have weatherhoods that are shipped loose and must be field-installed. Installation of the hoods is normally performed after all rigging and hoisting is completed because of www.renewaire.com (800) 627- 4499 support@renewaire.com the chance of damage to the hoods by the rigging equipment.
LE units ship with 20” X 25” X 2” (nominal) MERV-8 air filters. Filters are shipped loose in LE-RT units or may be installed prior to shipment in LE-IN units. In addition, RenewAire provides a set of filter spacers and a filter extractor hook, all shipped loose.
Swing 60 1/2" I.D. TOP VIEW Model: LE6X RTV/RTR AIRFLOW CONFIGURATION Drawing Type: Unit Dimension Available as shown: Version: MAY18 111" Minimum Service Area 13 3/8" X 15 1/2" RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499 Electrical TOP VIEW Connection...
HERT except 6x 8x, LERT Flange LEFT VIEW FRONT VIEW 165 3/8" Overall AIRFLOW CONFIGURATION Model: LE10X RTV/RTR 162 5/8" Case Available as shown: Drawing Type: Unit Dimension Version: MAY18 LE-SERIES OA Inlets, OA Damper 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM Locations (Optional)
HERTexcept 6x 8x, LERT FRONT VIEW Model: LE6X RTH/RTF AIRFLOW CONFIGURATION UNIT MOUNTING & APPLICATION Drawing Type: Unit Dimension Available as shown: Must be mounted as shown. Airstreams can not RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499 be switched. Version: MAY18...
HERTexcept 6x 8x, LERT Flange Model: LE8X RTH/RTF AIRFLOW CONFIGURATION UNIT MOUNTING & APPLICATION Drawing Type: Unit Dimension Available as shown: Must be mounted as shown. Airstreams can not be switched. Version: MAY18 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM...
Knockouts FRONT VIEW RIGHT VIEW AIRFLOW CONFIGURATION UNIT MOUNTING & APPLICATION Model: LE10X RTH/RTF Available as shown: Must be mounted as shown. Airstreams can not Drawing Type: Unit Dimension be switched. RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499 Version: MAY18...
AIRFLOW CONFIGURATION UNIT MOUNTING & APPLICATION Model: LE6XINV 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM Available as shown in dimension drawing. Must be mounted as shown. RA/EA airstream can Drawing Type: Unit Dimension be switched with OA/FA airstream unless certain Version: MAY18 options are selected.
Model: LE8XINV Available as shown in dimension drawing. Must be mounted as shown. RA/EA airstream can Drawing Type: Unit Dimension be switched with OA/FA airstream unless certain Version: MAY18 options are selected. RENEWAIRE.COM INSTALLATION, OPERATION AND MAINTENANCE MANUAL 1.800.627.4499 LE-SERIES...
UNIT MOUNTING & APPLICATION Drawing Type: Unit Dimension Available as shown in dimension drawing. Must be mounted as shown. RA/EA airstream can be switched with OA/FA airstream unless certain Version: MAY18 options are selected. 1.800.627.4499 INSTALLATION, OPERATION AND MAINTENANCE MANUAL RENEWAIRE.COM LE-SERIES...
Do not scale drawing Sheet 1 of 4 "B" 5 HP 1024 LE-6X-RT Corner Weights 1/30/2014 MF SPECIFICATIONS SUBJECT RenewAire LLC LE-6X-RT_CORNER_WEIGHTS_MAY18.dwg 3 HP 1017 TO CHANGE WITHOUT NOTICE. Do not scale drawing Sheet 1 of 4 7.5 HP 1083 "A"...
Sheet 1 of 4 Do not scale drawing TO CHANGE WITHOUT NOTICE. Sheet 1 of 4 7.5 HP 1009 7.5 HP "A" RenewAire LLC LE-6X-INH_CORNER_WEIGHTS_MAY18.dwg RenewAire LLC LE-6X-INV_CORNER_WEIGHTS_MAY18.dwg ADDITIONAL WEIGHTS FOR OPTIONS (lbs.) ADDITIONAL WEIGHTS FOR OPTIONS (lbs.) Options UNIT...
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE. Do not scale drawing Sheet 1 of 4 BASIC UNIT WEIGHTS (lbs.) 73.5" Lifting Lug BASIC UNIT WEIGHTS (lbs.) 73.5" Lifting Lug RenewAire LLC LE-8XRT_CORNER_WEIGHTS_MAY18.dwg Motors UNIT Door End Door End Motors UNIT LE-8X-RT Corner Weights...
Sheet 1 of 4 Do not scale drawing TO CHANGE WITHOUT NOTICE. Sheet 1 of 4 "B" 7.5 HP 1280 7.5 HP RenewAire LLC LE-8X-INH_CORNER_WEIGHTS_MAY18.dwg RenewAire LLC LE-8X-INV_CORNER_WEIGHTS_MAY18.dwg ADDITIONAL WEIGHTS FOR OPTIONS (lbs.) ADDITIONAL WEIGHTS FOR OPTIONS (lbs.) "A" Options...
SPECIFICATIONS SUBJECT BASIC UNIT WEIGHTS (lbs.) 73.5" Lifting Lug TO CHANGE WITHOUT NOTICE. Do not scale drawing Sheet 1 of 4 73.5" Lifting Lug BASIC UNIT WEIGHTS (lbs.) RenewAire LLC LE10X-RT_CORNER_WEIGHTS_MAY18.dwg Motors UNIT Door End Door End Motors UNIT LE10X-RT Corner Weights...
TO CHANGE WITHOUT NOTICE. Sheet 1 of 4 Do not scale drawing "B" Sheet 1 of 4 7.5 HP 1489 7.5 HP 1127 RenewAire LLC LE10X-INH_CORNER_WEIGHTS_MAY18.dwg RenewAire LLC LE10X-INV_CORNER_WEIGHTS_MAY18.dwg 10 HP 1508 10 HP 1127 "A" ADDITIONAL WEIGHTS FOR OPTIONS (lbs.) ADDITIONAL WEIGHTS FOR OPTIONS (lbs.)
Page 32
A B OUT REN EWAI RE For over 30 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size. This is achieved while maximizing sustainability through our fifth-generation, static-plate, enthalpic-core...