12 Specific data IO-Link (pin 6)
12.4.23 Error action
The safety position can be set with the Error action parameter.
The safety position is approached when an error occurs, if the supply voltage is too low within the range of 17.8 V to 21.1 V or
in case of the corresponding signal present at Safe/On (see "Failure counter", page 47).
▶ Except the Temperature Over-Run error device, exceeding the permissible motor temperature.If the permissible temperat-
ure is exceeded, the motor is switched off to prevent damage.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x4F
0
0
R/W
Description of parameter values
Index name
Error action
GEMÜ 639
OPEN / CLOSE (Code AE)
Lengt
Index name
h
Error action
2 bits
Parameter
Values
Error action
0
1
2
NOTICE
Parameter
Type
Error action
uint:8
(Hold) Actuator remains in the current position in case of an
error.
(Open) Actuator moves to the OPEN position in case of an
error.
(Close) Actuator moves to the CLOSED position in case of
an error.
44 / 62
Default
Values
2
0
1
2
Description