TORAGE
Leave the equipment on the shipping base.
Store all equipment indoors in a well-ventilated area.
The storage building should have a well-drained paved floor.
The
temperature should be above 60ºF. The air should be dry (50%
maximum humidity).
The sections ship wrapped in plastic for protection during shipment
only. Remove the plastic wrap after placing into storage. Cover with
heavy wrapping paper or other moisture barrier.
Do not use
materials that would trap moisture inside the unit. Do not cover
louvered or filtered openings.
When storing for a long period of time or in high-humidity, use
heaters to keep the interior dry. Bring the power for the heaters to
the load terminals of the device that controls the heater circuits.
.
The device must remain open when using a separate power source
Store circuit breakers upright in their original shipping carton. Do
not stack. Do not store circuit breakers in the switchgear
6