Fluke VoltAlert 1AC II Instruction Sheet
Hide thumbs Also See for VoltAlert 1AC II:

Advertisement

Quick Links

FOR USE BY COMPETENT
PERSONS
Anyone using this instrument should be
knowledgeable and trained about the risks
involved with measuring voltage, especially
in an industrial setting, and the importance of
taking safety precautions and of testing the
instrument before and after using it to ensure
that it is in good working condition.
Read First: Safety Information
To prevent possible electric shock or personal injury:
• Read all safety information before you use the Product.
• Do not rely on the Tester to detect the presence or absence of voltage on a
conductor for safety purposes. A single pole non-contact voltage detector such as
this Tester is NOT suitable to determine if a circuit is hazardous. A volt meter or
2-pole voltage detector is necessary to confirm the absence of hazardous voltage
prior to commencing work
• Hold the Product behind the tactile barrier.
• Do not use the Product around explosive gas, vapor, or in damp or wet
environments.
• Replace all alkaline batteries with fresh batteries of the same manufacturer and type
to prevent battery leakage.
• Remove the alkaline batteries if the Product is not used for an extended period of
time, or if stored in temperatures above 50 °C. If the batteries are not removed,
battery leakage may result.
• Repair the Product before use if the battery leaks. Battery leakage may create a
shock hazard or damage the Product.
• Alkaline batteries contain hazardous chemicals that can cause burns. If exposure to
chemicals occurs, clean with water and get medical aid.
If the Tester is used in a manner not specified by the manufacturer, protection
provided by the Tester may be affected.
Do not use if VoltBeat is not flashing.
Test on a known live source within the rated ac voltage range of the product, both
before and after use to ensure unit is in good working condition.
When using the Tester, if tip does not glow, voltage could still be present. The Tester
indicates active voltage in the presence of AC electric fields of sufficient strength
emanating from the conductor. If the field strength is low, the Tester may not provide
indication of live voltages. Lack of an indication occurs if the Tester is unable to
sense the presence of the electric field which may be influenced by several factors
including, but not limited to:
• Shielded wire/cables
• Thickness and type of insulation
• Distance from the voltage source
• Fully-isolated users that prevent an effective ground
• Receptacles in recessed sockets/ differences in socket design
• Condition of the Tester and Batteries
Do not use if the Tester appears damaged or if the Tester is not operating properly.
Specifically examine the probe tip for cracks or breakage before use. If in doubt,
have the Tester serviced.
Do not apply more than the rated voltage as marked on the Tester.
Use caution with voltages above 30 V ac as a shock hazard may exist.
Comply with local and national safety codes. Use personal protective equipment
(approved rubber gloves, face protection, and flame-resistant clothes) to prevent
shock and arc blast injury where hazardous live conductors are exposed.
Safety: IEC 61010-1: Pollution Degree 2; IEC 61010-2-030: CAT IV 1000 V
Electromagnetic Environment: IEC 61326-1: Portable Electromagnetic Environment;
CISPR 11: Group 1, Class B
Electromagnetic Compatibility: Applies to use in Korea only. Class A Equipment (Industrial
Broadcasting & Communication Equipment)
[1] This product meets requirements for industrial (Class A) electromagnetic wave equipment
and the seller or user should take notice of it. This equipment is intended for use in business
environments and is not to be used in homes.
Voltage Detection Range:
Model
A1/A2
E1/E2
LAC (low voltage)
C
PN 3497693
July 2009 Rev. 1, 8/20
© 2009-2020 Fluke Corporation. All rights reserved.
Specifications are subject to change without notice.
 Warning
[1]
Region
N. America, S. America, Asia
Europe
N. America
China
1AC II
VoltAlert
Instruction Sheet
Range
90 V ac to 1000 V ac
200 V ac to 1000 V ac
20 V ac to 90 Vac
90 V ac to 1000 V ac

Advertisement

loading

Summary of Contents for Fluke VoltAlert 1AC II

  • Page 1 LAC (low voltage) N. America 20 V ac to 90 Vac China 90 V ac to 1000 V ac PN 3497693 July 2009 Rev. 1, 8/20 © 2009-2020 Fluke Corporation. All rights reserved. Specifications are subject to change without notice.
  • Page 2 LIMITED WARRANTY AND LIMITATION OF LIABILITY This Fluke product will be free from defects in material and workmanship for two years from the date of purchase. This warranty does not cover fuses, disposable batteries, or damage from accident, neglect, misuse, alteration, contamination, or abnormal conditions of operation or handling.