Safety features

The relay meets the following safety requirements:
The circuit is redundant with built-in self-monitoring.
}
The safety function remains effective in the case of a component failure.
}
The correct opening and closing of the safety function relays is tested automatically in
}
each on-off cycle.
The unit has an electronic fuse.
}

Block diagram/terminal configuration

A1 A2
=
=
Power
Centre: Front view with cover, right: Front view without cover

Function description

Single-channel operation: no redundancy in the input circuit, earth faults in the reset
}
and input circuit are detected.
Automatic start: Unit is active once the input circuit has been closed.
}
Manual reset: Unit is active once the input circuit is closed and then the reset circuit is
}
closed.
Increase in the number of available instantaneous safety contacts by connecting con-
}
tact expander modules or external contactors/relays;
A connector can be used to connect 1 PNOZsigma contact expander module.