To Review Setpoints; Troubleshooting Tips; Override; Typical Wiring Diagrams - Paragon EC4000 Quick Start Manual

Single-channel electronic time control

Advertisement

TO REVIEW SETPOINTS

STEP
KEY
DESCRIPTION
1.
MODE
Advances from RUN mode to SET TIME
mode. (TOD displays.)
2.
MODE
Advances from SET TIME mode to SKIP-A-
DAY PROGRAMMING mode.
3.
MODE
Advances from SKIP-A-DAY PROGRAMMING
mode to EVENT PROGRAMMING mode. The
control will display the first event (1 displays at
bottom.) To modify the event, go to step 2 of
the EVENT PROGRAMMING mode
instructions.
4.
Advance through the remaining setpoints.
5.
RUN
Returns to RUN mode when done reviewing
setpoints.

OVERRIDE:

Manual override reverses the current output state. Loads that are ON
turn immediately OFF; loads that are OFF turn immediately ON. The
timer displays OVR to indicate that the current load state is the result
of an override. The override remains in effect until overridden again or
until the next setpoint is reached. To initiate override, press OVR
(ENTER) key while in the RUN mode.
NOTE: After an override has been initiated, the OVR will display until
the next programmed setpoint is reached, even if the timer is overrid-
den again. Display will show if the load is ON or OFF.
SPDT
N
L
(24, 120 or 277)
L2
L1
(208 or 240)
Maple Chase Company
2820 Thatcher Road
Downers Grove, Illinois 60515
Made in Mexico
Customer Service
800-951-5526
Technical Support
800-732-8400
ISO 9002 registered

Typical Wiring Diagrams

SPST
N
L
(120 or 277V)
L2
L1
(208 or 240V)
Paragon Electric Canada, Ltd.
5785 Kennedy Road
Mississauga, Ontario L4Z 2G3
From outside North America
630-719-5500

TROUBLESHOOTING TIPS

Problem
Nothing happens when a setpoint occurs to turn the load ON or OFF.
Solution
Review programmed setpoints making sure the day has not been
skipped.
Problem
You wish to clear the control's memory and start over.
Solution
Depress the reset switch to the right of the display.
Problem
Manual override does not work.
Solution
Check the load for proper wiring. Remember, the contacts on these
units only switch what is applied to them. (Dry or isolated contacts.)
Problem
Blank display
Solution
Check the input power source, ensure proper connection.
Problem
Control does not operate after programming.
Solution
If programming was not performed (changing clock time or entering a
setpoint), the control will not update itself. Press the ENTER key and
override the load until the next scheduled setpoint.
DPST
See jumpers below
H1
H3
H2
H4
1
2
3
4
120V jumpers
H1
H3
H2
H4
1
2
3
4
L
L1
208 or 240V jumpers
L
N (120v)
L2 (208 or 240V)
N (277V no
jumpers needed)