AXPTC125 POWER TEE SPLICE CONNECTION KIT
OPTIONAL CUSTOMER SUPPLIED POWER CONNECTION WIRING
 Remove stopping plug and locknut.
 Install flex conduit and drain as shown.
 Terminate power and ground wires to terminal
block.
 Install enclosure cover.
STEP 11
TULSA, OK 74146
GA-5052 Rev. 3
Sheet 8 of 10
August 2017
STEP 10
TEL 918-627-5530
 Install thermal insulation and protective lagging.
 Apply sealant around standoff penetration to
prevent moisture entry.
 Leave installation instructions with end user for
future maintenance and/or trouble shooting.
 Fill in the blank fields on the label located on the
cover of the junction box as follows:
CIR. NO. – Electrical circuit heating cable
connected too.
CAT. NO. – Type of heating cable used
VOLTS – Operating voltage of heating cable – Max
277VAC
AMPS – Operating current of heating cable – Max
18A continuous current. 25A for XLT cable.
 Heating cable installations require incoming power
wiring to be rated for 105ºC operation.
 Maximum steady-state current may not exceed 18
amps. 25 amps for XLT cable.
 Verify that all connections are properly installed
and secure.
ELECTRICAL WIRING
FAX 918-641-7336
www.nelsonheaters.com
INSTALLATION
INSTRUCTIONS