Parameter Settings; Setting Grid Parameters - Huawei SUN2000-100KTL-USH0 User Manual

Table of Contents

Advertisement

SUN2000-100KTL-USH0
User Manual

7.1.6.1 Parameter Settings

Ensure that the DC side of the SUN2000 is energized before setting grid
parameters, protection parameters, feature parameters, and grid adjustment
parameters.

7.1.6.1.1 Setting Grid Parameters

Procedure
Step 1 Choose Function Menu > Settings > Grid Parameters to set grid parameters.
Figure 7-19 Grid parameters
Table 7-8 Grid parameters
Parameter
Grid code
Auto start upon
grid recovery
Grid connection
duration after
power grid
recovery (s)
Grid reconnection
voltage upper
limit (V)
Issue 06 (2020-12-18)
Description
Set this parameter based on the grid code
of the country or region where the
SUN2000 is used and the SUN2000
application scenario.
Specifies whether to allow the SUN2000 to
automatically start after the power grid
recovers.
Specifies the waiting time for SUN2000
restart after the power grid recovers.
The standards of certain countries and
regions require that the SUN2000 must not
export power to the power grid again
when the grid voltage exceeds the value of
Grid reconnection voltage upper limit
after the SUN2000 shuts down due to a
fault.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Value Range (Vn represents
the rated voltage.)
-
● Disable
● Enable
[0, 900]
[100%Vn, 136%Vn]
85