ABB ACS880-207 Hardware Manual page 61

Industrial drives, igbt supply units
Hide thumbs Also See for ACS880-207:
Table of Contents

Advertisement

• Cut the shield at the midpoint of the bare part. Be careful not to cut the conductors or
the grounding wire (if present).
• Turn the shield inside out to expose its conductive surface.
• Cover the turned shield and the stripped cable with copper foil to keep the shielding
continuous.
A
2
1
5
Note for top entry of cables: When each cable has its own rubber grommet, sufficient IP
and EMC protection can be achieved. However, if there is more than one cable per grommet,
plan the installation beforehand as follows:
1. Make a list of the cables coming to the cabinet.
2. Sort the cables going to the left into one group and the cables going to the right into
another group to avoid unnecessary crossing of cables inside the cabinet.
3. Sort the cables in each group according to size.
4. Group the cables for each grommet as follows ensuring that each cable has a proper
contact to the cushions on both sides.
Cable diameter in mm
B
C
A
B
C
1
2
3
2
4
3
4
≤ 13
≤ 17
< 25
≥ 25
Electrical installation 61
Stripped cable
Conductive surface of the shield exposed
Stripped part covered with copper foil
Cable shield
Copper foil
Shielded twisted pair
Grounding wire
Max. number of cables per grommet
4
3
2
1
11