Summary of Contents for Johnson Controls SERIES 40
Page 1
PACKAGED ROOFTOP AIR CONDITIONING UNITS R-410A ONLY, GEN 5 INSTALLATION, OPERATION & MAINTENANCE Supersedes 5276178-JIM-B-0117 5276178-JIM-C-0118 SERIES 40 ROOFTOP 25, 30 AND 40 TON WITH IPU CONTROL LD14136...
Page 2
NOT be installed inside the micro panel. NO external wiring is allowed to be run through the micro panel. All wiring must be in accordance with Johnson Controls published specifications and must be performed ONLY by qualified Johnson Controls personnel. Johnson Controls will not be responsible for damages/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
Johnson Controls whether the equipment has been modified and if current Applied Systems office.
Page 4
5276178-JIM-C-0118 NOMENCLATURE JOHNSON CONTROLS...
FILTERS ............................79 CONDENSATE DRAIN ........................79 Condensate Drain Piping .....................79 Condensate Drain Trap ......................79 COMPRESSORS .........................79 AIR HOODS ..........................79 Air Hoods for Fixed Outside Air ..................79 Air Hoods for Economizer ....................79 Air Hoods for Exhaust Air ....................80 FIELD WIRING ..........................80 JOHNSON CONTROLS...
Page 6
Piping Connections ......................88 STEAM HEAT..........................89 Piping Connections ......................90 SECTION 3 – START-UP .........................91 CRANKCASE HEATERS ......................91 CHECKING THE SYSTEM PRIOR TO INITIAL START (NO POWER) ........91 Unit Checks ...........................91 UNIT CHECKS – POWER APPLIED ...................92 Verifying Compressor Rotation ...................92 JOHNSON CONTROLS...
Page 7
......................102 HOT WATER AND STEAM COILS ....................103 SECTION 4 – MAINTENANCE ......................114 GENERAL ..........................114 PERIODIC MAINTENANCE – MONTHLY .................114 Filters ...........................114 Linkages ..........................114 Compressors ........................114 Condenser Coils .........................114 PERIODIC MAINTENANCE – 3 TO 6 MONTHS ...............114 Motors ..........................114 JOHNSON CONTROLS...
Page 8
COMPRESSOR STAGING SEQUENCE ...................137 CONDENSER FAN OPERATION ....................138 LOW AMBEINT CONDENSER FAN OPERATION ..............138 ECONOMIZER ...........................138 Dry Bulb ..........................138 Single Enthalpy ........................138 Dual Enthalpy ........................139 Best Method ........................139 NonFlexSys Economizer ....................140 FlexSys Economizer ......................140 COMPRESSOR OPERATION....................140 Compressor Data ........................140 JOHNSON CONTROLS...
Page 9
MODULATING GAS HEAT ......................150 HOT WATER/STEAM HEAT ......................150 Programmed Data .......................150 Active SP ..........................150 Sequence of Operation ......................150 Freeze Protection ........................151 Freeze Fault .........................151 MORNING WARM UP ........................151 Sequence of Operation ......................152 ADAPTIVE MORNING WARM UP .....................152 Sequence of Operation ......................152 JOHNSON CONTROLS...
Page 10
PROGRAM ..........................175 OPTIONS ...........................175 DATE / TIME..........................175 SCHEDULE ..........................176 OPERATING HOURS / START COUNTER ................177 PRINTER ............................178 Set Up ..........................178 Report Section ........................178 SERVICE MODE ........................179 HISTORY ............................189 PASSWORD ..........................190 POWER UP BANNER ........................191 COMMUNICATION........................192 Communication Ports ......................192 JOHNSON CONTROLS...
Page 11
SECTION 7 – PARAMETER DEFENITIONS AND OPTIONS ............218 SECTION 8 – SERVICE .........................228 ANALOG INPUT OPERATION ....................228 Temperature Sensors ......................228 Duct Pressure Transducer ....................228 Building Pressure Transducer ...................229 Humidity Sensors .......................229 Sensor ..........................230 Furnace Status Input ......................230 FAULTS ............................231 MULTI MEDIA CARD .........................242 JOHNSON CONTROLS...
Page 12
TABLE 37 ELECTRICAL DATA 40 TON 460 VOLT WITH ERV ...........76 TABLE 38 ELECTRICAL DATA 40 TON 575 VOLT WITHOUT ERV ...........77 TABLE 39 ELECTRICAL DATA 40 TON 575 VOLT WITH ERV ...........78 TABLE 40 - PIPE SIZES ........................86 TABLE 41 - BLOWER SPEED RATE OF CHANGE ..............94 JOHNSON CONTROLS...
Page 14
TABLE 100 - I/O CONTROL BOARD - ANALOG INPUT PIN OUTS .........236 TABLE 101 - WARNING DESCRIPTION ..................237 TABLE 102 - FAULT AUTO - RESET ....................239 TABLE 103 - FAULTS LOCKOUT ....................240 TABLE 104 - DATA LOG ERROR STATE ..................242 TABLE 105 - DATA LOG ERROR LOG DETAIL ................243 JOHNSON CONTROLS...
Page 15
FIGURE 37 - HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 40 GPM ........107 FIGURE 38 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 60 GPM ........108 FIGURE 39 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 80 GPM ........108 JOHNSON CONTROLS...
Page 16
FIGURE 76 - I/O CONTROL BOARD - BINARY OUTPUTS ............234 FIGURE 77 - I/O CONTROL BOARD - BINARY INPUTS ............235 FIGURE 78 - I/O CONTROL BOARD - ANALOG OUTPUTS .............235 FIGURE 79 - I/O CONTROL BOARD - ANALOG INPUTS (SEE TABLE 90 FOR PIN OUTS) 235 JOHNSON CONTROLS...
Compressor Circuiting packaged rooftop air conditioner meet U.S. EPACT 1992 minimum requirements. The Series 40 is designed so that each scroll compressor has its own refrigeration circuit. This means more reliable compressors, and less equipment down time. With multiple circuits, if a compressor should ever fail on one circuit, the other circuit/s will remain operational to work to maintain occupied loads.
Condenser Fan Motors into the occupied zones of office and other commercial The condenser fan motors used on the Series 40 unit are buildings. This underfloor plenum incorporates the air Totally Enclosed Air Over (TEAO) to provide maximum distribution system with the building power, telecom, durability through any season.
If you cannot reach your gas supplier, call the fire department. BACnet The Series 40 can be adapted to operate with any The furnace and its individual shut-off building automation system that is BACnet compatible valve must be disconnected from the...
Follow all safety codes, including ANSI Z223.1-Latest Edition: wear safety glasses and work gloves; use quenching cloth for unbrazing operations; have fire extinguisher available for all brazing operations. JOHNSON CONTROLS...
COMPRESSOR ACCESS REAR RIGHT HEAT SECTION FRONT OPTIONAL POWER LEFT END OUTLET (115V) POWER EXHAUST ACCESS HEAT SECTION EVAPORATOR COIL AND DRAIN PAN ACCESS FILTER DRIERS FILTER ACCESS REAR SUPPLY BLOWER & MOTOR FIGURE 2 - COMPONENT LOCATION JOHNSON CONTROLS...
Page 22
5276178-JIM-C-0118 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
These weights must be referred to when selecting a crane for rigging and figuring roof weight • Filter compartment economizer compartment loads. Contact your Johnson Controls Sales Office if (two doors). you have any questions regarding unit weights. •...
HOT WATER HEAT If a unit is to be installed on a roof curb 1 ROW COIL 2 ROW COIL other than a Johnson Controls roof curb, gasketing must be applied to all STEAM HEAT surfaces that come in contact with the 1 ROW COIL unit underside.
10HP 15HP 15HP EXHAUST Note: If the Series 40 is VAV with ERV, add the weight of an NOTE: If the Millennium is VAV with ERV, add the SEE TABLE 10 exhaust VFD (it will be in the unit) MOTOR VFD weight of an exhaust VFD - it will be in the unit.
Page 30
4 EA. 16 X 25 / 4 EA. 16 X 25 / 4 EA. 16 X 25 / NUMBER / SIZE 6 EA. 20 X 25 6 EA. 20 X 25 6 EA. 20 X 25 FACE AREA (SQ. FT.) 30.4 30.4 30.4 JOHNSON CONTROLS...
Ø 2-1/2” 1 -1 /2 " F P T 1-1/4” NPT DETAIL B DETAIL A DETAIL C (ELECTRICAL CONNECTION) (DRAIN CONNECTION) (GAS CONNECTION FOR COOLING ONLY AND ALL HEATING APPLICATIONS THROUGH CURB) FIGURE 6 - BOTTOM SUPPLY AND RETURN JOHNSON CONTROLS...
BASE RAIL 6.45" 2.31” 11” BASE RAIL 2-1/2" 1-1/2" FPT 1-1/4” NPT DETAIL B DETAIL A DETAIL C (DRAIN CONNECTION) (ELECTRICAL CONNECTION) (GAS CONNECTION THROUGH CURB) FOR COOLING ONLY AND ALL HEATING APPLICATIONS FIGURE 7- END RETURN, BOTTOM SUPPLY JOHNSON CONTROLS...
11” BASE RAIL 2-1/2" 1-1/2" FPT 1-1/4” NPT DETAIL B DETAIL A DETAIL C (DRAIN CONNECTION) (ELECTRICAL CONNECTION) (GAS CONNECTION THROUGH CURB) FOR COOLING ONLY AND ALL HEATING APPLICATIONS FIGURE 8 - BOTTOM RETURN, FRONT & REAR SUPPLY JOHNSON CONTROLS...
11” BASE RAIL 2-1/2" 1-1/2" FPT 1-1/4” NPT DETAIL B DETAIL A DETAIL C (DRAIN CONNECTION) (ELECTRICAL CONNECTION) (GAS CONNECTION THROUGH CURB) FOR COOLING ONLY AND ALL HEATING APPLICATIONS FIGURE 9 - END RETURN, FRONT & REAR SUPPLY JOHNSON CONTROLS...
BE EXTENDED TO MOUNT A TALLER DISCONNECT DOOR WHEN OPEN SWITCH, BUT THESE FOUR POINTS SHOULD BE USED TO MOUNT THE RAILS TO THE UNIT. FIGURE 11 - FIELD INSTALLED DISCONNECT 259.68 35.42 39.31 93.43 15.00 241.22 FIGURE 12 – 25 TON OVERHEAD VIEW JOHNSON CONTROLS...
Doors # 1, 2, 3, 6, 7, 8. wide. Doors # 4, 5, 9 are dependent upon unit Heating Door configurations are the same on all tonnages and Power Exhaust Options. (40 ton shown). FIGURE 16 – CABINET DOOR CONFIGURATION JOHNSON CONTROLS...
Page 43
1. Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation. 2. Refer to Table 17 for component additions and deductions to fan performance tables. 3. BHP includes drive losses. 4. Shaded RPMs require Class II blower. JOHNSON CONTROLS...
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system and cabinet effects at standard air Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system density and 0' elevation. and cabinet effects at standard air density and 0' elevation. FIGURE 19 – FAN PERFORMANCE - 25 TON FORWARD CURVE JOHNSON CONTROLS...
Page 46
1. Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation. 2. Refer to Table 17 for component additions and deductions to fan performance tables. 3. BHP includes drive losses. 4. Shaded RPMs require Class II blower. JOHNSON CONTROLS...
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system and cabinet effects at standard air and cabinet effects at standard air density and 0' elevation. density and 0' elevation. FIGURE 20 – FAN PERFORMANCE - 30 TON FORWARD CURVE JOHNSON CONTROLS...
Page 49
1. Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation. 2. Refer to Table 17 for component additions and deductions to fan performance tables. 3. BHP includes drive losses. 4. Shaded RPMs require Class II blower. JOHNSON CONTROLS...
Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system and cabinet effects at standard air Note: Standard Unit includes wet evaporator coil, clean 2" throwaway filters, system density and 0' elevation. and cabinet effects at standard air density and 0' elevation. FIGURE 21 – FAN PERFORMANCE - 40 TON FORWARD CURVE JOHNSON CONTROLS...
1. Baseline losses based on system/cabinet effects, wet standard coil and 2”throwaway filters at 70°F, 0 feet elevation with standard air. 2. See Tables 52, 53, 54 and 55 for hot water and steam water coil static resistance. JOHNSON CONTROLS...
1077 10.1 1096 10.4 1119 10.8 1143 11.1 1167 11.4 1. Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet of elevation. 2. BHP includes 5% drive losses. JOHNSON CONTROLS...
15.54 1. Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0 feet elevation. 2. BHP includes the sum of both exhaust fan motors. 3. BHP includes 5% drive losses. JOHNSON CONTROLS...
Air Hoods for Fixed Outside Air Condensate Drain Piping (Units with Manual Economizer) The Series 40 cooling coils are located in the units so These hoods are factory installed. The dampers may that the supply air is drawn through them. This results...
No external power source may be used when field wiring any of the above inputs. The 24VAC source on terminal 2 and 16 (R) of the Terminal Block CTB3 must be used as the power source when field wiring these inputs, JOHNSON CONTROLS...
BACNET COMMUNICATION overloading the unit power supply. The Series 40 rooftop unit can communicate to any MS/TP building automation system using BACnet The VAV Heat Relay output can be found at terminals communication protocol.
If the sensor uses 24VAC additional wires will need to be run to terminal 1 (24VAC) and terminal 2 (24VAC COM) of the CTB3 terminal block. If the sensor required a different power source than 24VAC it will need to be field supplied. FIGURE 26 – FIELD CONTROL WIRING - INPUTS JOHNSON CONTROLS...
A removable patch plate covers both the openings. Use care to avoid damage when drill- ing holes for the disconnect mount- Waterproof connections MUST be ing. used to ensure that water cannot pen- etrate the roof or roof curb. JOHNSON CONTROLS...
(next to the mounting location for the static pressure probe) to the atmospheric pressure probe (see Installation Instructions, Form 100.50- N15) ld11072 FIGURE 27 – STATIC PRESSURE PROBE INSTALLATION JOHNSON CONTROLS...
Johnson Controls will not be responsible for the unit fit up, leak integrity, or sound level with field fabricated Installation of elbows, discharge roof curbs.
Before initial start-up, fitting. Line should not be sized smaller be sure that all of the gas lines external to the unit have been purged of air. than the entrance fitting size. JOHNSON CONTROLS...
COMBUSTION AIR INLET HOT WATER HEAT The Johnson Controls Series 40 units (25, 30, and 40 Ton sizes) can be furnished with a Johnson Controls hot water coil as the heat source. One or two row coil units VENT FLUE ASSEMBLY will be factory installed in the heating section.
In one row hot water coil systems DO conditioned. NOT exceed 40 gallons per minute flow rate. In two row hot water coil systems DO NOT exceed 80 gallons per minute flow rate. JOHNSON CONTROLS...
5276178-JIM-C-0118 STEAM HEAT The Johnson Controls Series 40 units (25, 30 and 40 Ton sizes) can be furnished with a Johnson Controls single row steam coil. Johnson Controls steam coils are a factory installed option. LD14190 FIGURE 30 – STEAM PIPING CROSS-SECTION...
The following figure illustrates the location of the compartment and piping connections. Piping access holes should be sealed with a heat resistant mastic to prevent damage to equipment. LD14189 FIGURE 31 – HOT WATER PIPING CROSS-SECTION JOHNSON CONTROLS...
To protect warranty, this equipment CHECKING THE SYSTEM PRIOR TO INITIAL START (NO POWER) must be installed and serviced by an authorized Johnson Controls service Unit Checks mechanic or a qualified service person experienced in air handling and con- 1. Inspect the unit for shipping or installation dam- denser unit installation.
Change the incoming line connection phasing to obtain proper rotation. UNIT CHECKS – POWER APPLIED The Series 40 rooftop unit uses hermetic scroll 1. Apply 3-phase power and verify its value. Voltage compressors, which only pump in one direction.
Figure the pitch diameter (PD) of the motor sheave using the 56 and 57. formula below: (Specified CFM/Measured CFM) x PD of standard sheave = PD of new sheave. JOHNSON CONTROLS...
BHP at original start-up with 11,000 CFM and 856 RPM = (1.119) x 11 BHP = 1.4012 x 11 BHP = 15.41 BHP New motor amps = (speed increase) x measured motor amps at original start-up with 11,000 CFM and 856 RPM. JOHNSON CONTROLS...
103.4 97.0 100.0 (STD.) 116.3 106.8 100.0 105.5 120.4 110.2 103.0 113.7 124.5 113.6 106.0 121.9 116.9 112.0 120.3 120.9 123.7 129.9 1. (STD), STANDARD FACTORY SUPPLIED DRIVE. ALL OTHER DRIVE COMBINATIONS MUST BE PURCHASED AND FIELD INSTALLED. JOHNSON CONTROLS...
93.7 94.2 100.0 (STD.) 5.5 96.8 97.1 103.6 (STD.) 6.3 100.0 (STD.) 6.9 107.3 103.2 102.9 110.9 106.3 108.7 114.5 109.5 117.4 1. (STD), STANDARD FACTORY SUPPLIED DRIVE. ALL OTHER DRIVE COMBINATIONS MUST BE PURCHASED AND FIELD INSTALLED. JOHNSON CONTROLS...
Evaporator Superheat = 15°F Refrigerant Charge The Series 40 unit comes fully charged from the factory When adjusting the expansion valve, the adjusting with Refrigerant R-410A. Table 41 is a Temperature/ screw should be turned not more than one turn at a time, Pressure chart for R-410A.
6 inches. If gas pressure is 4. Remove the heat shield on top of the manifold outside these limits, contact the local gas utility support. Burners are now accessible for service. for corrective action. Reverse the above procedure to replace the assemblies. JOHNSON CONTROLS...
(with allowance being made for the permissible range of the regulator setting), replace the orifice spuds with Thermal Expansion Valves: The Series 40 units have spuds of the proper size. 4 independent refrigeration systems. These TXVs are set to maintain 15°F superheat leaving the evaporator To find the BTU input, multiply the coil.
1. Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil. TABLE 57 - WATER PRESSURE DROP (1 ROW, 25 & 30 TON) WATER PRESSURE DROP 10.0 TABLE 58 - WATER PRESSURE DROP (1 ROW, 40 TONS) WATER PRESSURE DROP 10.0 JOHNSON CONTROLS...
317.4 371.1 8000 249.8 313.3 377.1 441.1 10000 283.3 355.6 428.2 501.0 12000 312.7 392.7 473.0 553.6 15000 351.0 440.9 531.3 622.1 1. Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil. JOHNSON CONTROLS...
NOTE: Water pressure drop numbers are based on 60°F entering air temperature, 2.00” maximum air pressure drop across the hot water coil(s). ARI certified ratings at covering other conditions are available upon request. Hot water coils are approved for use with glycol (rates available upon request). JOHNSON CONTROLS...
The driers may have to be period, Johnson Controls will not be liable for costs changed several times to clean up the system depending incurred to return the unit to satisfactory operation.
All set screws and/or taper lock bolts must to ensure proper equipment operation. Items such as be checked for tightness and alignment before putting loose hardware, component operation, refrigerant leaks, equipment into operation. unusual noises, etc. should be investigated and corrected immediately. JOHNSON CONTROLS...
If necessary, clean to maintain adequate combustion One end of each flue baffle is provided air discharge. with a sharper bend than the other end. This sharper bend must be positioned at the tube and attached with a stain- less steel screw. JOHNSON CONTROLS...
- see Figure 53. This will preserve the balance of the shaft in this area should be thoroughly cleaned before rotating assembly. Proceed with the following steps: the bearing is removed and again before the new bearing is installed. JOHNSON CONTROLS...
Screws Lube There are various degrees of self-alignment in bearings Fitting of the same manufacturer. The force required for the self-alignment of the bearings used in Johnson Controls Lock Seal manufactured units has been specified and is closely Ring monitored at the factory. If it is necessary to purchase...
The wide inner ring is now locked to the shaft. Using a punch or similar tool in the drilled hole of the collar, tap the tool lightly to lock the collar in the direction of normal shaft rotation. LD06358 FIGURE 56 - ECCENTRIC CAM LOCKING COLLAR BEARING INSTALLATION JOHNSON CONTROLS...
1. Torque screw “A” to 1/2 recommended torque. lock washer 2. Torque screw “B” to full min. recommended bearings value. tapered sleeve 3. Torque screw “A” to full recommended value. 00536vip seal FIGURE 57 - SPLIT BEARING JOHNSON CONTROLS...
FIGURE 58 - 25 TON CHARGING CURVE 30 TON CHARGING CURVE 30 TON CHARGING CURVE 30 TON CHARGING CURVE 105 F 95 F 85 F 75 F 65 F SUCTION PRESSURE (PSIG) LD14105 SUCTION PRESSURE (PSIG) FIGURE 59 – 30 TON CHARGING CURVE JOHNSON CONTROLS...
FIGURE 60 – 40 TON CHARGING CURVE PRESSURE DROP ACROSS A DRY EVAPORATOR COIL PRESSURE DROP ACROSS A DRY EVAPORATOR COIL NOMINAL CFM (THOUSANDS) LD14107 FIGURE61 – PRESSURE DROP DRY EVAPORATOR COIL VS SUPPLY AIR CFM - 25 TON JOHNSON CONTROLS...
PRESSURE DROP ACROSS A DRY EVAPORATOR COIL PRESSURE DROP ACROSS A DRY EVAPORATOR COIL 10 11 12 13 14 15 16 17 18 NOMINAL CFM (THOUSANDS) LD14109 FIGURE 63 – PRESSURE DROP DRY EVAPORATOR COIL VS SUPPLY AIR CFM - 40 TON JOHNSON CONTROLS...
COOLING HIGH -2.0 -1.0 -0.5 +0.5 +1.0 +1.5 +2.0 HEATING LOW HEATING HIGH Difference Between "ZONE TEMP" and "OCC ZONE HEATING" or "UNOCC ZONE HEATING" Set Point LD010572 FIGURE 65 - DIFFERENCES (°F) BETWEEN ZONE TEMPERATURE AND SET POINTS JOHNSON CONTROLS...
0.5°F the Unit Controller will place the unit in the OCCUPIED HEATING mode. The unit will remain in the OCCUPIED HEATING mode until the “RETURN AIR TEMP” is equal to or greater than the “RAT HEATING SETPOINT” plus 0.5°F. JOHNSON CONTROLS...
SETPOINTS key / COOLING subsection The “SUPPLY AIR TEMP ACTIVE SP” is always derived from three programmed parameters “SAT HIGH • “FAN SPEED SETP FOR HIGH SAT” – SETPOINT”, “SAT LOW SETPOINT” and the “SAT SETPOINTS key / COOLING subsection JOHNSON CONTROLS...
Active SAT Set Point SAT LOW SETPOINT (Default = 55.0 °F) OAT SETPOINT OAT SETPOINT Outside Air Temp FOR HIGH SAT FOR LOW SAT (OAT) Increasing OAT FIGURE 67 - ACTIVE SAT SET POINT VS. OUTSIDE AIR TEMP LD12588 JOHNSON CONTROLS...
Set Point SAT LOW SETPOINT (Default = 55.0 °F) FAN SPEED FAN SPEED Supply Fan Speed FOR LOW SAT FOR HIGH SAT LD10308A Increasing Supply Fan Speed FIGURE 69 - ACTIVE SAT SET POINT VS. SUPPLY FAN SPEED JOHNSON CONTROLS...
ON or OFF until the timer has timed down. Controller enters an active cooling mode, the Unit The only exception to this would be if the compressor Controller sets the “COOLING CONTROL OFFSET” protection circuit experienced a fault. to 2.0°F. The Unit Controller compares the current JOHNSON CONTROLS...
After a “COOLING CONTROL OFFSET” calculation is made the Unit Controller initiates a 45 minute Cooling Control Offset Timer. If no compressor is turned ON or OFF before the Cooling Control Offset Timer has expired, the “COOLING CONTROL OFFSET” will be reset to 2.0°F. JOHNSON CONTROLS...
As the pressure state for 10 seconds. If the input does not go to a high goes up, the speed goes down. state during this time frame the Unit Controller will set JOHNSON CONTROLS...
DUCT STATIC RESET HIGH SETP Active DSP Set Point DUCT STATIC RESET LOW SETP 5 Volts 0 Volts Duct Static Pres Rst LD10309A Voltage (Volts DC) FIGURE 70 - ACTIVE DSP SET POINT VS. DUCT STATIC PRES RST VOLTAGE JOHNSON CONTROLS...
THE UNIT CONTROL WILL SET NEXT STAGE TO DISABLE TO THE REMAINING COMPRESSOR STAGE 2 TO 1 FROM THE STAGE 4 TO 3 TRANSITION. THE UNIT CONTROL WILL SET NEXT STAGE TO DISABLE TO THE COMPRESSOR REMAINING STAGE 1 TO 0 FROM THE STAGE 3 TO 2 TRANSITION. JOHNSON CONTROLS...
SAT SETPOINT”. The following parameters must be • The “OUTSIDE AIR TEMP” is less than or equal programmed into the Unit Controller through the User to the “SUPPLY AIR TEMP ACTIVE SP” plus Interface to enable economizer operation: 8°F. JOHNSON CONTROLS...
HUMIDITY SENSOR RELIABLE” are all true. • The “OUTSIDE AIR TEMP” is less than or equal With this setting, all of the above logic for Dry Bulb, to the “SUPPLY AIR TEMP ACTIVE SP” plus Single enthalpy, and Dual Enthalpy apply. 8°F. JOHNSON CONTROLS...
The number symbol will vary to match the compressor number the data is being recorded for, 1A (1), 1B (2), 2A (3) etc. This data can be view under the OPERATING HOURS / START COUNTER key of the User Interface. JOHNSON CONTROLS...
1 A and 1B. Likewise for system 2 they are identified as 2A and 2B. Since the Series 40 unit uses If the safety circuit opens three times in a 120-minute...
• Compressor operation must have been OFF for 10 minutes. If the “SUPPLY AIR TEMP” is equal to or greater than • The “HEAT ENTERING TEMP” must be less JOHNSON CONTROLS...
LOCKOUT TEMP” can never be set lower than 0.0°F. LOW AMBIENT FAN CONTROL OPTION The addition of a condenser fan VFD is programmed If the refrigerant system is configured for low ambient through “LOW AMBIENT PKG” which is under the JOHNSON CONTROLS...
The VFD controls the fan speed based on discharge efficiency. pressure. Configuration (Jumpers and Potentiometers) TABLE 73 - POTENTIOMETER SETTINGS The inverter is configured at the factory. The jumpers 350 PSIG 80 PSIG 6 O’CLOCK 6 O’CLOCK LD11300B FIGURE 71 - CONDENSER FAN VFD POTENTIOMETER SETTINGS JOHNSON CONTROLS...
“RETURN AIR BYPASS ACTIVE SP” = x 100 “RETURN AIR TEMP” - “FLEX EVAP TEMP ACTIVE SP” FORMULA 1 MX SUPPLY AIR TEMP”- “FLEX EVAP TEMP” “ “RETURN AIR BYPASS CURRENT” = x 100 “RETURN AIR TEMP” - “FLEX EVAP TEMP” FORMULA 2 JOHNSON CONTROLS...
“SUPPLY AIR TEMP ACTIVE SP” plus programmed for CONSTANT VOLUME units the HEATING CONTROL OFFSET” additional through the SETPOINTS key, HEATING subsec- stages will be turned OFF after an Interstage tion of the User Interface. Delay timer has expired. JOHNSON CONTROLS...
HCO = time. 2.16 x CFM Where: When UNIT MODE is “STANDBY” and “UNDER • HCO = “HEAT CONTROL OFFSET” FLR TEMP OVRD” is active, one stage of heat is turned ON. • CFM = (See Table 67) JOHNSON CONTROLS...
“SUPPLY AIR TEMP ACTIVE SP” plus the of operation for each gas heat sections “HEATING CONTROL OFFSET” additional stages will be turned OFF after an Interstage The following information can be viewed for each Delay timer has expired. JOHNSON CONTROLS...
The faulted heat that heat section as “SAFETY LOCKOUT”. section will then initiate an ignition sequence, provided 13. If the “SUPPLY AIR TEMP” continues to be less the heating demand is still present. Staged Gas Heat Ignition Sequence JOHNSON CONTROLS...
If the “SUPPLY AIR TEMP” is less than the • “HW VALVE ACTION” must be set to “DI- RECT” OR REVERSE” through the PROGRAM key, HEATING subsection of the User Inter- face. • “1ST STAGE HEATING SETPOINT” must be JOHNSON CONTROLS...
100% or 0 % if the valve Action is • “MORNING WARM UP” is set to USER DIS- programmed for “REVERSE” The Primary Control will ABLED. start a 5 minute Freeze Trip Timer. The STATUS screen • The occupancy mode is OCCUPIED. JOHNSON CONTROLS...
The “OCCUPANCY SCHEDULE” must be pro- 4. If the Return Air Temperature is less than or grammed for the Occupied, Unoccupied start and equal to the “RAT HEATING SETPOINT” minus stop times. This is done through the SCHEDULE key of the User Interface. JOHNSON CONTROLS...
TEMP2 = “RETURN AIR TEMP” when the FLOOR TEMP CONTROL SP” for modulating Warm Up stopped. heat. • TEMP1 = “RETURN AIR TEMP” when the 5. Heating operation will continue until: Warm Up started. • Set Point = “RAT HEATING SETPOINT”. JOHNSON CONTROLS...
“ECONO OUPUT FOR FAN START” must be set using using the SETPOINTS key, EXHAUST subsection of the SETPOINTS key, EXHAUST subsection of the the User Interface. User Interface. “EXHAUST OUTPUT FOR FAN START” must be set “ECONO OUPUT FOR FAN STOP” must be set using JOHNSON CONTROLS...
2-Position the User Interface. • Standard “EXHAUST OUTPUT FOR FAN START” must be set Everything except the NONE and 2-POSTION using the SETPOINTS key, EXHAUST subsection of the User Interface. “EXHAUST OUTPUT FOR FAN STOP” must be set JOHNSON CONTROLS...
Terminal 14 (IAQ OD-) of the CTB3 terminal block. damper to lower the indoor CO level between the minimum and maximum settings. Sequence of Operation The indoor C0 level can be either hard wired or communicated. In order to communicate the indoor C0 JOHNSON CONTROLS...
(negatively pressurize) the building or space in order • VFD = Output to supply Fan VFD. to draw air through the walls from adjacent spaces or Air Measuring Stations outside the building envelope. When this sequence is This feature is not available on this product. JOHNSON CONTROLS...
Page 158
Start the Return Fan, if not already ON. • Start the Exhaust Fan, if not already ON. • Set all Outside Air Damper Output(s) to 0%. • Set all Return Air Dampers to100%. • Set the Exhaust Damper Output to 100%. JOHNSON CONTROLS...
Page 159
5276178-JIM-C-0118 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
STATUS SETPOINTS UNIT DATA PROGRAM COOLING OPTIONS COMPRESSOR SYSTEMS DATE/TIME SUPPLY SYSTEM SCHEDULE OPERATING HOURS HEATING START COUNTER ECONOMIZER PRINT VENTILATION SERVICE EXHAUST HISTORY UNIT LD010669 FIGURE 72 - USER INTERFACE CONTROL PANEL JOHNSON CONTROLS...
The tables contain the Displayed Text, Pass Word Level (if applicable), Range of Values (if applicable), Default Value (if applicable), what key (Setpoints, Program, Options) to use to change the value (if applicable), and under what circumstances the item is displayed. JOHNSON CONTROLS...
SEQ 3 EVACUATION UNIT DATA HARD WIRED OPTIONS / DISPLAY LANGUAGE ENGLISH ENGLISH ENGLISH ONLY AVAILABLE UNIT DATA IMPERIAL / METRIC IMPERIAL ALWAYS DISPLAY UNITS * ONLY THE ZONE TEMP SCREEN FOR THE CURRENT ACTIVE MODE WILL BE SHOWN. JOHNSON CONTROLS...
AND DEWPOINT RESET EQUALS DEW POINT 30.0º F TO 100.0º F DERIVED ENABLED SETPOINTS/ 20.0 TO 40.0% UNIT TYPE EQUALS FLEXSYS MAXIMUM BYPASS COOLING * ONLY THE ZONE TEMP SCREEN FOR THE CURRENT ACTIVE MODE WILL BE SHOWN. JOHNSON CONTROLS...
Page 165
PRESS TRANS PKG AND LOW AMBIENT 0.0º F - 65.0º F 50.0º F COOLING PKG OTHER THAN NONE TEMP SETPOINTS/ PRESS TRANS PKG AND LOW AMBIENT MECH CLG LOCKOUT -10.0º F - 0.0º F 0.0º F TMP MINIMUM COOLING PKG OTHER THAN NONE JOHNSON CONTROLS...
400 PSIG COMP SYS ON THIS UNIT. PRESSURE OPTIONAL/ PRESS TRANS PKG NONE / SYS 1 NONE ALWAYS COMP SYS OPTIONAL/ ALWAYS LOW AMBIENT PKG NONE / SYS 1 NONE COMP SYS * MAY BE 1, OR 2 JOHNSON CONTROLS...
USER PROGRAM / UNIT TYPE EQUALS VARIABLE AIR INSTABILITY MONITOR USER DISABLED DISABLED SUPPLY SYSTEM VOLUM OR FLEXSYS RETURN PRESSURE SETPOINTS / THIS FEATURE IS NOT 0.15 TO 0.45 0.15 HIGH SETP SUPPLY SYSTEM AVAILABLE ON THIS UNIT. JOHNSON CONTROLS...
2 TO 6 DERIVED HW / STEAM VALVE POS 0.0 TO 100% DERIVED HEAT TYPE EQUALS HOT WATER HEAT STEAM FRZ STAT OK TRIPPED DERIVED * ONLY THE ZONE TEMP SCREEN FOR THE CURRENT ACTIVE MODE WILL BE SHOWN. JOHNSON CONTROLS...
Page 169
HEAT TYPE DOES NOT EQUAL HEATING SYSTEM PROGRAM / HEATING DISABLED ENABLED NONE HEAT TYPE DOES NOT USER ENABLED USER USER EQUAL NONE AND CONSTANT PROGRAM / HEATING MORNING WARM UP DISABLED DISABLED VOLUME CONTROL METHOD DOES NOT EQUAL STAGED JOHNSON CONTROLS...
Page 170
DERIVED NONE AND MORN WARM UP WARM UP MAX TIME OPT TIME EQUALS ENABLED HEAT TYPE DOES NOT EQUAL MORNING WARM UP 15 - 240 MIN. 120 MIN. SETPOINTS/HEATING NONE AND MORN WARM UP MAX TIME EQUALS ENABLED JOHNSON CONTROLS...
EQUALS DUAL ENTHALPY OUTSIDE AIR ECONOMIZER INSTALLED 22.0 TO 40.0 BTU/LB 28.0 BTU/LB SETPOINTS / ECONOMIZER ENTHALPY DOES NOT EQUAL NONE SETPOINT ECONOMIZER USER ENABLED USER ECONOMIZER INSTALLED DISABLED PROGRAM / ECONOMIZER DISABLED DOES NOT EQUAL NONE SYSTEM JOHNSON CONTROLS...
VENTILATION OR 2 POSITION DAMPER POSITION CONTINUOUS USER ENABLED USER USER PROGRAM / UNIT TYPE EQUALS CONSTANT VOLUME DISABLED ENABLED VENTILATION VENT COMFORT USER ENABLED USER USER PROGRAM / UNIT TYPE EQUALS CONSTANT VOLUME VENTILATION DISABLED DISABLED VENTILATION JOHNSON CONTROLS...
Page 173
SYSTEM DISABLED ENABLED VENTILATION SETPOINTS / THIS FEATURE IS NOT AVAILABLE ON 0.5 - 1.5 AMS FACTOR 1 VENTILATION THIS UNIT. SETPOINTS / THIS FEATURE IS NOT AVAILABLE ON AMS FACTOR 2 0.5 - 1.5 VENTILATION THIS UNIT. JOHNSON CONTROLS...
SETPOINTS / POWER EXHAUST EQUALS FAN START STOP TO 100% EXHAUST MODULATE DAMPER - VFD 0 - TO EXHAUST OUTPUT SETPOINTS / POWER EXHAUST EQUALS EXHAUST OUTPUT FOR FAN STOP FOR FAN START EXHAUST MODULATE DAMPER - VFD JOHNSON CONTROLS...
Tables 69 thru 77. Then use the ▼ key and the ▲ key to navigate to the parameter you want to change. Follow the instructions given in the Data Entry Keys section to change the parameter to the desired value. JOHNSON CONTROLS...
MMDD is displayed when the value is being edited to remind the operator what the format of this number is. Eg. 1225 represents December 25. SCHEDULE TO EDIT START =06:00 AM STOP =10:00 PM SCHEDULE TO EDIT START =06:00 AM STOP =10:00 PM JOHNSON CONTROLS...
SUPPLY FAN OPER HRS DERIVED SUPPLY FAN STARTS RETURN FAN OPER HRS THIS FEATURE IS NOT AVAILABLE ON THIS DERIVED RETURN FAN STARTS UNIT. Shown below is a typical screen example. HOURS / STARTS OPER HRS. XXXXX COMPRESSOR 1A STARTS XXXXX JOHNSON CONTROLS...
As the report is uploading, from the Unit Control to the PC, it is displayed in the Hyper Terminal window. • After the reports finish transferring to the PC, select “Transfer – Capture to Printer” to send the last page to the printer. JOHNSON CONTROLS...
OFF position. To force an output ON terminal location (ID), Value Range, and when item is use the ◄ or ► key to navigate to the SERVICE AO displayed. section. Then use the ▲ or ▼ key to select the output JOHNSON CONTROLS...
STATUS OF ELECTRIC HEAT DIGITAL ELECTRIC HEAT TB3-4 ON / OFF I/O BOARD OUTPUT OUTPUT TO STAGE 3 STG 3 ELECTRIC HEAT DIGITAL STATUS OF ELECTRIC HEAT DIGITAL TB3-5 ON / OFF I/O BOARD OUTPUT OUTPUT TO STAGE 4 STG 4 JOHNSON CONTROLS...
Page 181
RETURN FAN DIGITAL THIS FEATURE IS NOT TB1-4 ON / OFF I/O BOARD OUTPUT OUTPUT AVAILABLE ON THIS UNIT. EXHAUST FAN DIGITAL STATUS OF EXHAUST FAN OR RETURN TB1-4 ON / OFF I/O BOARD OUTPUT OUTPUT FAN DIGITAL OUTPUT JOHNSON CONTROLS...
Page 182
HUMIDITY SENSOR ANALOG TEMPERATURE THIS FEATURE IS NOT J3-1 0-5 VOLTS I/O BOARD SUCTION 1 INPUT AVAILABLE ON THIS UNIT. ANALOG TEMPERATURE THIS FEATURE IS NOT J3-2 0-5 VOLTS I/O BOARD INPUT SUCTION 2 AVAILABLE ON THIS UNIT. JOHNSON CONTROLS...
Page 183
ANALOG INPUT FROM THE UNDER FLOOR J7-2 0-5 VOLTS I/O BOARD INPUT TEMPERATURE SENSOR SLAB TEMP UNDERFLOOR AIR A N A L O G ANALOG INPUT FROM THE UNDERFLOOR J7-3 0-5 VOLTS I/O BOARD HUMIDITY INPUT HUMIDITY SENSOR JOHNSON CONTROLS...
Page 184
SYSTEM 2 SAFETY CIRCUIT D I G I T A L S A F E T Y I N P U T THIS FEATURE IS NOT TB7-4 OKAY / FAULTED I/O BOARD CHAIN 3 INPUT AVAILABLE ON THIS UNIT. JOHNSON CONTROLS...
Page 185
GIVES THE STATUS OF THE MORNING WARM PORT COMMUN ON / OFF IPU BOARD COMMUNICATED MORNING WARM UP UP CMD COMMAND GIVES THE STATUS OF THE PORT OCCUPIED / OCCUPANCY COMMUN IPU BOARD COMMUNICATED OCCUPANCY COMMAND UNOCCUPIED COMMAND JOHNSON CONTROLS...
Page 186
PORT GIVES THE STATUS OF THE COMMUN ON / OFF IPU BOARD UNIT STOP COMMUNICATED UNIT STOP COMMAND GIVES THE STATUS OF THE W1 LOW HEAT PORT COMMUN ON / OFF IPU BOARD COMMUNICATED W1 LOW HEAT COMMAND JOHNSON CONTROLS...
Page 187
ESTABLISHES THE COMMUNICATION BAUD P2 BAUD RATE 9600, 19200, RATE FOR PORT 2 38400, 57600 ALLOWS THE MANUAL ENTRANCE OF P2 MANUAL MAC -1 TO 127 THE MAC ADDRESS FOR PORT 2. SEE ADDRESS SECTION 6 - COMMUNICATION JOHNSON CONTROLS...
Page 188
ERROR PAGE AND FIELD CONNEXSYS ERROR REASON DERIVED NOT FOR FIELD USE AND VALVE REAL TIME DERIVED NOT FOR FIELD USE PROBLEM STRING REAL TIME DERIVED NOT FOR FIELD USE PROBLEM NUMBER REAL TIME DERIVED NOT FOR FIELD USE PROBLEM JOHNSON CONTROLS...
Entering the Level 2 password will also The ► key is pressed to move to the next older fault allow the changing of a Level 1 parameter. (fault # 2). HISTORY 02 31 OCT 2004 10:42:39 AM ◄► AUTO RESET-MSAT SENSOR JOHNSON CONTROLS...
Pressing the X key during password entry will cancel Packaged Rooftop Air Conditioner Control Panel. the password entry process and take the user back to • ZZ = the Product Code. the Login Prompt. • YY = the Version Number. JOHNSON CONTROLS...
4 - Transmit (+) LD10821 FIGURE 69 - MAC ADDRESS SWITCHES 5 - Open PORT 1 (J4) PORT 4 (J3) PORT 2 (J5) NOT USED MAC ADDRESS SWITCH PORT 3 (J2) LD11197B FIGURE 73 - IPU CONTROL BOARD JOHNSON CONTROLS...
DIP switches or a change to the above communication parameters using the SERVICE key of the User Interface the main power to the unit must be cycled OFF and back ON to change the value in memory. JOHNSON CONTROLS...
THE NUMBER OF HOURS COMPRESSOR 4 HAS COMP_2B_OPER AI12 OPER HRS BEEN IN OPERATION (HOUR) THIS FEATURE IS NOT AVAILABLE ON COMP_3A COMPRESSOR 3A BI07 1288 THIS UNIT. THIS FEATURE IS NOT AVAILABLE ON COMPRESSOR 3A COMP_3A_OPER AI13 OPER HRS THIS UNIT. JOHNSON CONTROLS...
Page 195
TO BE TURNED ON AND OFF ON FLEXSYS UNITS (0 = OFF / 1 = ON) DUCT STATIC HIGH DSP_HI_LIMIT AV03 1028 THE DUCT STATIC UPPER SET POINT (“WC) LIMIT DUCT STATIC LOW DSP_LO_LIMIT AV04 1029 THE DUCT STATIC LOWER SET POINT (“WC) LIMIT JOHNSON CONTROLS...
Page 196
TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1) FURNACE 1 HIGH ELECTRIC HEAT INDICATES THE STATUS OF THE BINARY OUTPUT FURN_OUT_3 STAGE 3 STG GAS BI28 1309 TO THE INDICATED HEAT SECTION (OFF - 0, ON - 1) FURNACE 2 LOW JOHNSON CONTROLS...
Page 197
MIXED SAT LIMIT AV14 1039 SETPOINT WHEN OPERATING WITHOUT A BYPASS DAMPER (F) A COMMUNICATED INPUT THAT ALLOWS MORNING MORNING WARM MORN_WARM_UP AV(BV)85 1110 WARM UP TO BE TURNED ON AND OFF (0 = UP ENABLE ENALBED; 1 = DISABLED) JOHNSON CONTROLS...
Page 198
USES WHEN USING OUTDOOR AIR SAT RESET TO SWITCH TO THE SAT LOW LIMIT SET POINT (F) IDENTIFIES THE OCCUPIED / UNOCCUPIED STATUS WITH HARD WIRED, COMMUNICATED OCCUPANCY OCC_MODE BI35 1316 OR INTERNAL CLOCK SCHEDULE INPUT MODE (ENA - ENABLED-OCCUPIED; DIS - DISABLED - UNOCCUPIED) JOHNSON CONTROLS...
Page 199
READY TO RUN IDENTIFIES IF COMPRESSOR 4 IS READY TO RUN RDY_RUN_C2B BI43 1324 COMP 2B IF THE COMPRESSOR IS OFF (YES / NO) THIS FEATURE IS NOT AVAILABLE ON READY TO RUN RDY_RUN_C3A BI44 1325 COMP 3A THIS UNIT. JOHNSON CONTROLS...
Page 200
AI43 (TEMPERATURES 1 THIS UNIT. SUCTION) SATURATED THIS FEATURE IS NOT AVAILABLE ON SUCTION TEMP SAT_SUC_TMP2 AI44 (TEMPERATURES 2 THIS UNIT. SUCTION) SATURATED THIS FEATURE IS NOT AVAILABLE ON SUCTION TEMP SAT_SUC_TMP3 AI45 (TEMPERATURES 3 THIS UNIT. SUCTION) JOHNSON CONTROLS...
Page 201
SUPPLY FAN VFD AI48 THE ACTUAL OUTPUT TO THE SUPPLY FAN VFD (%) THE STATUS OF THE BINARY OUTPUT FROM THE SUPPLY_FAN SUPPLY FAN BI59 1340 CONTROLLER TO THE SUPPLY FAN CIRCUIT (0 = OFF, 1 = ON) JOHNSON CONTROLS...
Page 202
THIS ALLOWS THE BAS SYSTEM TO INPUT A UNDER FLOOR TEMPERATURE VALUE TO THE UNDER FLOOR UND_TEMP_BAS AV37 1062 CONTROL ON A FLEXSYS SYSTEM (F). “UNDER TEMP BAS FLR TEMP BAS” MUST BE ENABLED USING THE SERVICE KEY IN ORDER TO USE THIS FEATURE JOHNSON CONTROLS...
Page 203
1343 WITH EITHER A HARDWIRED OR COMMUNCIATED INPUT (ON / OFF) A COMMUNICATED VALUE THAT ALLOWS THE W2 W2 HIGH HEAT W2_HI_HEAT_B AV(BV)97 1122 HEAT CALL TO BE TURNED ON AND OFF (0 = OFF; 1 = ON) JOHNSON CONTROLS...
METHOD” MUST BE SET TO “COMM ZONE TEMP” Notes: 1. The most up to date listing of the Standard Points Mapping can be found in the Johnson Controls website. 2. In order to do BACnet IP a gateway model FS-B2010-02-01Y must be purchased from fieldserver technologies.
Page 205
DERIVED VALUE SHOWING THE NUMBER OF ELECTRIC OR nvoHEAT_STAGES STAGES GAS HEAT AI-023 STAGGED GAS HEAT STAGES AVAILABLE (1 - 7) STAGES SNVT_switch THE OUPUIT FROM THE CONTROL TO A HOT WATER, STEAM, nvoHEATING_VALV HEATING VALVE AI-024 (95) OR MODULATING GAS HEAT VALVE (%) JOHNSON CONTROLS...
Page 206
OCCUPIED OR UNOCCUPIED MODE (0 = UNOCCUPIED / 1 = MAND (95) OCCUPIED) OCCUPIED ZONE SNVT_count_f nviOCC_ZN_COOL AV-021 THE OCCUPIED ZONE COOLING SET POINT (F) COOLING SETP (51) OCCUPIED ZONE SNVT_count_f nviOCC_ZN_HEAT AV-022 THE OCCUPIED ZONE HEATING SET POINT (F) HEATING SETP (51) JOHNSON CONTROLS...
Page 207
(51) SUCTION) SATURATED SUCTION TEMP SNVT_count_f nvoSAT_SUC_TMP2 AI-044 THIS FEATURE IS NOT AVAILABLE ON THIS UNIT. (TEMPERATURES 2 (51) SUCTION) SATURATED SUCTION TEMP SNVT_count_f nvoSAT_SUC_TMP3 AI-045 THIS FEATURE IS NOT AVAILABLE ON THIS UNIT. (TEMPERATURES 3 (51) SUCTION) JOHNSON CONTROLS...
Page 208
TEM (F). "UNDER FLR TEMP BAS" MUST BE ENABLED USING THE SERVICE KEY IN ORDER TO USE THIS FEATURE UNDER FLOOR SNVT_count_f TEMPERATURE OF THE AIR UNDER THE FLOOR THE CONTROL nvoUND_FLR_TEMP AI-057 TEMP (51) IS CONTROLLING TO IN A FLEXSYS SYSTEM (F) JOHNSON CONTROLS...
Page 209
(51) Notes: 1. The most up to listing of the Standard Points Mapping can be found in the Johnson Controls website 2. In order to do LON protocol a e-link gateway part number YK-ELNK101-0 or YK-ELNKE01-0 must be used JOHNSON CONTROLS...
CUTOUT CIRCUIT (0 - FAULTED / 1 - NO FAULT ) COMPRESSOR STATUS OF COMPRESSOR 3 or 4 LOW PRESSURE COMP_LPCO_2 BI10 0, 1 DI 9 LPCO 2 CUTOUT CIRCUIT (0 - FAULTED / 1 - NO FAULT ) JOHNSON CONTROLS...
Page 211
DEG F AI 13 TEMP 1 EVAPORATOR COIL ON A FLEXSYS UNIT (F) THE STATUS OF THE BINARY OUTPUT FOR THE EXHAUST_FAN EXHAUST FAN BI22 0, 1 DI 15 EXHAUST ( 0 = OFF / 1 = ON) JOHNSON CONTROLS...
Page 212
SETPOINT WHEN OPERATING WITHOUT A BYPASS DAMPER (F) A BAS GENERATED COMMAND TO ALLOW THE MORN_WUP_ MORNING WARM AV 86 0, 1 AO 37 MORNING WARM UP FEATURE TO BE TURNED ON UP CMND AND OFF (0 = OFF / 1 = ON) JOHNSON CONTROLS...
Page 213
THE OCCUPIED ZONE HEATING SET POINT (F) HEATING SETP PRESSURES 1 THIS FEATURE IS NOT AVAILABLE ON PRS_1_DISCH AI31 AI 24 DISCHARGE THIS UNIT. PRS_1_ PRESSURES 1 THIS FEATURE IS NOT AVAILABLE ON AI32 AI 25 SUCTION SUCTION THIS UNIT. JOHNSON CONTROLS...
Page 214
AND 5 VOLTS USES SAT LOW LIMIT (V). “SAT RST BAS” MUST BE ENABLED USING THE SERVICE KEY IN ORDER TO USE THIS FEATURE SATURATED SAT_SUC_ SUCTION TEMP THIS FEATURE IS NOT AVAILABLE ON AI43 DEG F AI 36 TMP1 (TEMPERATURES THIS UNIT. 1 SUCTION) JOHNSON CONTROLS...
Page 215
TURNS OFF COMPRESSOR SYSTEM 3 TEMP_1_ TEMPERATURE 1 THIS FEATURE IS NOT AVAILABLE ON AI49 DEG F AI 42 SUCTION SUCTION THIS UNIT. TEMP_2_ TEMPERATURE 2 THIS FEATURE IS NOT AVAILABLE ON AI51 DEG F AI 43 SUCTION SUCTION THIS UNIT. JOHNSON CONTROLS...
Page 216
19 - MORNING WARM UP 20 - POWER UP STANDBY THIS COMMAND ALLOWS THE UNIT TO BE SHUT UNIT_STOP UNIT STOP AV93 0, 1 AO 40 DOWN THROUGH THE BAS SYSTEM (0 = NORMAL OPERATION/ 1 = STOPPED JOHNSON CONTROLS...
Page 217
Notes: 1 The most up to date listing of the Standard Points Mapping can be found in the Johnson Controls website. 2. In order to do N2 protocol, an e-link gateway part number YK-ELNK 100-0 or YK-ELINK 00-0 must be used.
Normal - Comp A On, Normal - Comp B On, Normal - Both ON, Normal - Both Off, COMP SYS 1 STATUS Safety Trip, Safety Fault, Safety Lockout, Low Amb Inhibit, Low Suct Temp Unl, High DP Unload, or User Disabled. JOHNSON CONTROLS...
Page 219
This is the Morning Warm Up time the Unit Controller recorded during the previous DAILY WARM UP TIME DAY 1 day 1. This value is used to calculate the current Morning Warm initiate time for Adaptive Morning Warm Up. JOHNSON CONTROLS...
Page 220
ON the exhaust fan in an ON/OFF DAMPER CTRL. This parameter is set through the SETPOINTS key and identifies the position of the ECONO OUTPUT FOR FAN STOP economizer damper required to turn OFF the exhaust fan in an ON/OFF DAMPER CTRL option. JOHNSON CONTROLS...
Page 221
FAN SPEED SETP FOR LOW SAT speed is equal to or greater than this value the Active Supply Air Temperature Set Point on a Variable Air Volume Unit will be set to the SAT Set Point Low Limit. JOHNSON CONTROLS...
Page 222
Unit Controller controls the heating option to try and maintain this temperature. This is the current operating mode of the Heating Section. The display will show HEATING SYS STATUS Normal - Active, Normal - Inactive, Safety Trip, Safety Fault, Safety Lockout, User Disabled, or None. JOHNSON CONTROLS...
Page 223
USER ENABLED or USER DISABLED. This parameter is programmed through the SETPOINTS key. This establishes the OA DAMPER MAXIMUM POSITION maximum amount of ventilation air to be used in a Demand Ventilation situation. * May be 1, 2, or 3 JOHNSON CONTROLS...
Page 224
(THIS FEATURE IS NOT AVAILABLE ON THIS UNIT) This is the suction pressure and is shown for each compressor system if pressure PRESSURE SUCTION* transducers are installed and configured for the system. (THIS FEATURE IS NOT AVAILABLE ON THIS UNIT) JOHNSON CONTROLS...
Page 225
RETURN FAN PRESS CURRENT (THIS FEATURE IS NOT AVAILABLE ON THIS UNIT) RETURN FAN PRESSURE ACTIVE This is the current mixed air chamber pressure that the Unit Controller is trying to maintain. (THIS FEATURE IS NOT AVAILABLE ON THIS UNIT) JOHNSON CONTROLS...
Page 226
This is the Binary output from the Unit Controller to the Supply Fan control system. This is a Binary input into the Unit Controller that identifies the Supply Fan is SUPPLY FAN OUTPUT PROOF functioning. SUPPLY FAN VFD SPEED This indicates the output, in percent, to the Supply Fan VFD. JOHNSON CONTROLS...
Page 227
This parameter is programmed using the SETPOINTS key. This is the temperature ZONE TEMP UNOCC ZONE HEATING that the Unit Controller compares the actual space temperature to, to decide when SETPOINT to switch into the Unoccupied Heating Mode. JOHNSON CONTROLS...
0.75 3.25 inputs will now be exposed to the same pressure, the differential pressure will be zero, and the output 2.5VDC 1.00 3.50 according to Table86. 1.25 3.75 1.50 4.00 1.75 4.25 2.00 4.50 2.25 4.75 2.50 5.00 JOHNSON CONTROLS...
TABLE 99 - FURNACE STATUS INPUT STAGED GAS HEAT MIN VDC MAX VDC FURNACE 1 STATUS FURNACE 2 STATUS FURNACE 3 STATUS 0.086 0.166 0.224 0.313 0.361 0.461 0.499 0.609 0.637 0.756 0.774 0.904 0.912 1.051 1.050 1.199 JOHNSON CONTROLS...
2 password must be entered in order to view the data. warnings. A warning is defined as an abnormal condition under which the unit continues to operate. Warnings will not require the unit to shut down; however, they may JOHNSON CONTROLS...
Page 232
60 minutes it will be “COMPRESSOR SYSTEM (1,2,OR 3) CLEAR” shows replaced with a “COMPRESSOR SYSTEM (1,2,OR 3) the time it took for the fault to clear in the HISTORY TIME OUT” message. buffer. JOHNSON CONTROLS...
TB9-12 BYPASS DAMPER COM (411) LD14102 FIGURE 78 - I/O CONTROL BOARD - ANALOG OUTPUTS I/O CONTROL J4, J5, J6, J7 PINOUTS J1, J2, J3 PINOUTS LD10794 FIGURE 79 - I/O CONTROL BOARD - ANALOG INPUTS (SEE TABLE 90 FOR PIN OUTS) JOHNSON CONTROLS...
SHIELD FLEXSYS SLAB SENSOR (367) J2-7 COM OA HUM (319) J7-12 REF FLEXSYS SLAB SENSOR 5VDC (365) J2-4 INPUT RA HUM (320) J7-3 INPUT FLEXSYS UNDER FLOOR HUM (368) J2-8 COM RA HUM (321) J7-8 COM FLEXSYS UNDER FLOOR HUM (369) JOHNSON CONTROLS...
OUTSIDE AIR TEMP MORE THAN OR EQUAL TO ECONO INSTALLED SENSOR/ SENSOR/ OUTSIDE AIR 32 F FOR 10 SECONDS OUTDOOR AIR AUTO RESET SINGLE ENTHALPY MISC STATUS MISC FAULT HUMIDITY < 5% FOR 10 SECONDS OR DUAL ENTHALPY WARNING JOHNSON CONTROLS...
Page 238
FLEXSYS AND DEW SENSOR/ FLOOR RH AUTO RESET MISC STATUS THAN OR EQUAL TO 5 MINUTES POINT RESET IS MISC FAULT SENSOR WARNING USER ENABLED * CAN BE 1, 2, OR 3 # CAN BE A OR B JOHNSON CONTROLS...
- ZONE TEMP OF RANGE FOR MORE THAN OR EQUAL SET TO CV AND MISC RESET SAFETY SENSOR TO 10 SECONDS THE CONTROL FAULT LOCKOUT METHOD IS SET TO ZONE SENSOR HARDWIRED * CAN BE 1, 2, OR 3 JOHNSON CONTROLS...
COMMUNICATED INPUT COMP SYS * STATUS SAFETY OUTSIDE AIR TEMP SENSOR IS OUT SENSOR/ LOCKOUT - OAT UNIT LOCKOUT; OF RANGE FOR MORE THAN OR MISC SENSOR LOCKOUT ECONO SYS EQUAL TO 10 SECONDS FAULT STATUS SAFETY LOCKOUT JOHNSON CONTROLS...
Page 241
SYSTEM * CLEAR” SHOWS THE TIME IT TOOK FOR THE FAULT TO CLEAR IN THE HISTORY BUFFER. “LOCKOUT-COMPRESSOR SYSTEM * TIME OUT” – IF THE “COMPR STATUS CLEAR TIME *” TIMER REACHES 60 MINUTES A “LOCKOUT - COMPRESSOR SYSTEM * TIME OUT” WILL BE INDICATED IN THE HISTORY BUFFER. JOHNSON CONTROLS...
Each line of data will be timed and date stamped. OPEN A FILE Each file will include a header line detailing what data WRITE A FILE is stored in each column. DELETE A FILE CLOSE A FILE JOHNSON CONTROLS...
OUT OF MEMORY RESOURCE BUSY NO SUCH DEVICE NOT A DIRECTORY IS A DIRECTORY INVALID ARGUMENT TOO MANY OPEN FILES IN SYSTEM FILE TOO LARGE NO SPACE LEFT ON DEVICE ILLEGAL SEEK READ-ONLY FILE SYSTEM FILE NAME TOO LONG JOHNSON CONTROLS...
Page 244
Service 5276178-JIM-C-0118 NOTES JOHNSON CONTROLS...
Page 245
EQUIPMENT STARTUP warranty policy and warranty manual found on UPGnet for details. In the event that communication with Johnson Controls/UPG is Use the local LCD or Mobile Access Portal (MAP) Gateway to required regarding technical and/or warranty concerns, all parties complete the start-up.
Page 246
1034349-UCL-E-0817 SAFETY WARNINGS The inspections and recording of data outlined in this procedure are required for start-up of Johnson Controls/UPG's packaged Lethal voltages are present during some start-up products. Industry recognized safety standards and practices checks. Extreme caution must be used at all times.
Page 247
Check economizer setting (Reference Smart Equipment™ Control Board LCD menu location) Prove economizer open/close through Smart Equipment™ Board Setting Reheat Mode Normal or Alternate Not Applicable Humidity Sensor (2SH0401) _____________________________________________ Unitary Products Group JOHNSON CONTROLS...
Page 248
1. VAV units with heat section - simulate heat call to drive VAV boxes and VFD/IGV to maximum design airflow position. 2. VAV units without heat section - VAV boxes must be set to maximum design airflow position. Unitary Products Group JOHNSON CONTROLS...
Page 249
Stage 2 (If Equipped) Stage 3 (If Equipped) Supply gas pressure at full fire Check temperature rise measured at full fire °F 1. Input X Eff. (BTU output) 1.08 X Temp. Rise Unitary Products Group JOHNSON CONTROLS...
Need help?
Do you have a question about the SERIES 40 and is the answer not in the manual?
Questions and answers