Instructions for Replacing
The Packing on 1510, 1531
& Series 80
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER'S USE.
SAFETY
INSTRUCTIONS
This safety alert symbol will be used in this manual and on the
pump safety instruction decals to draw attention to safety
related instructions. When used, the safety alert symbol
means ATTENTION! BECOME ALERT! YOUR SAFETY IS
INVOLVED! FAILURE TO FOLLOW THE INSTRUCTIONS MAY
RESULT IN A SAFETY HAZARD.
SERVICE INSTRUCTIONS
WARNING: Electrical Shock Hazard
Disconnect and lockout the power before making
electrical connections. Failure to follow these instructions
could result in serious personal injury, death and/or property
damage.
1. Close valves on suction and discharge sides of pump. (If
no valves have been installed, it will be necessary to drain
the system).
CAUTION: Extreme Temperature Hazard
Allow the pump temperature to reach an acceptable
level before proceeding. Open the drain valve and do not
proceed until the liquid has completely drained. If the liquid
does not stop flowing from the drain valve, then the isola-
tion valves are not sealing and should be repaired before
continuing. After the liquid has stopped flowing, leave the
drain valve open and continue. Remove the drain plug
located on the bottom of the pump volute. Do not reinstall
this plug or close the drain valve until the reassembly is
complete. Failure to follow these instructions could result
in moderate personal injury and/or property damage.
2. For 1531 and Series 80 pumps:
Remove motor foot capscrews (1531 only). Loosen volute
capscrews, but do not remove them. Use capscrews in
the jackscrew holes provided. Begin to remove the pump
assembly from the volute.
For 1510 pumps:
Remove coupler guard and loosen set screws in both
coupler halves. Slide each half back as far as possible on
its shaft. Remove coupler sleeve. Where a full diameter
impeller is being used, it may be necessary to remove the
-PF Type Pumps
®
INSTRUCTION MANUAL
pump side coupler half and slide the motor back on its
base in order to gain sufficient clearance to remove the
pump assembly from the volute. Remove the pump
assembly from the volute. Remove support foot capscrews.
Loosen volute capscrews, but do not remove them. Use
capscrews in the jackscrew holes provided. Begin to re-
move the pump assembly from the volute.
WARNING: Excessive Pressure Hazard
Make certain internal pressure of the pump is relieved
before continuing. Failure to follow these instructions could
result in serious personal injury, death and/or property
damage.
3. Remove seal flushing tube.
Remove the volute capscrews and remove the pump
assembly from the volute.
4. Remove the impeller capscrew, lock washer and washer.
Remove the impeller.
5. Remove hex nuts from packing gland and remove cover-
plate capscrews. Remove coverplate from bracket.
6. Remove packing rings from the stuffing box.
7. Check condition of shaft sleeve and replace if scored or
otherwise damaged.
8. Insert two packing rings in the stuffing box followed by the
lantern ring and then the remaining two pieces of packing.
Make certain that the packing joints are staggered 90°.
9. Install, but do not tighten the packing gland.
10. Install coverplate over the pump shaft, tighten capscrews
(per torque chart on page 4).
11. Tighten packing gland to compress packing.
12. Install impeller, impeller washer, lock washer and cap-
screw, then tighten (per torque chart on page 4).
13. Install new volute gasket, then install pump assembly into
volute. Tighten volute capscrews (per torque chart). Install
seal flushing tube.
P81747C

Advertisement

loading

Summary of Contents for Xylem Bell & Gossett 80-PF Series

  • Page 1 INSTRUCTION MANUAL P81747C Instructions for Replacing The Packing on 1510, 1531 & Series 80 -PF Type Pumps ® INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE. SAFETY pump side coupler half and slide the motor back on its base in order to gain sufficient clearance to remove the INSTRUCTIONS pump assembly from the volute.
  • Page 2 For 1531 and Series 80 pumps: time before further tightening of the glands. Take up gland Install motor foot capscrews (1531 only) and tighten. Install bolts uniformly, one flat at a time. drain plug and close drain valve. An adequate leakage rate is not one single value for all pumps For 1510 pumps: and installations, but is the amount required to provide ade- Install support foot capscrews and tighten.
  • Page 3 COUPLER ALIGNMENT For Fine Alignment, Orange Hytrel Sleeves, 3500 RPM Operation, or All Other Coupler Types All alignment should be done by moving or shimming the Use a dial indicator when greater alignment accuracy is motor only. Adjustments in one direction may alter alignment required.
  • Page 4 Xylem Inc. 8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. P81747C May 2012...

This manual is also suitable for: