Installation - Riello Multi Switch Installation And User Manual

Table of Contents

Advertisement

Available languages

Available languages

Multi Switch – User's Manual
________________________________________________________________________________________________________
3

INSTALLATION

Remove the machine from its packaging with caution.
Attach the handles to the side of the Multi Switch with the appropriate screws.
Install upstream of the apparatus a 16A magneto-thermal switch with intervention curve B or C.
For greater safety and to avoid making the wrong connections, only use the cables that were supplied with the
machine.
Figure below shows the various possible power supply configurations of the Multi Switch.
Configuration (a) is the best in terms of:
 reliability;
 protection and continuity of the electrical power supply.
In configuration (c), lines "A" and "B" are either two separate lines, or are separated by two different disconnecting
switches above the Multi Switch.
6
Assemblage of the handles
The different possible configurations of the Multi Switch
- ENGLISH -