Error Messages In The "Send" Coordination Byte - Siemens SIMATIC S5 Series Manual

Second serial interface of the programmable controller
Hide thumbs Also See for SIMATIC S5 Series:
Table of Contents

Advertisement

Computer Link with 3964(R) Transmission Protocol
The error messages are listed and explained in the following tables.

Error messages in the "send" coordination byte

Table 3-1 Error Messages in the "Send" Coordination Byte
Assignment
09
Negative acknowledgement of receiver at
H
connection cleardown
0B
Negative acknowledgement of receiver at
H
connection buildup
0D
Parameterizing error
H
0F
Send procedure aborted by receiver
H
11
No send mailbox available
H
13
Length exceeds output buffer size
H
15
Timeout at connection buildup
H
17
Timeout at connection cleardown
H
19
Initialization conflict, both partners have
H
high priority
1B
Break
H
1D
Initialization conflict, both partners have
H
low priority
3-8
Meaning
S5-95U, Second Serial Interface
Response
Data invalid for receiver
Data not sent
Data not sent
Data invalid for receiver
Data not sent
Data invalid for receiver
Data not sent
Send procedure aborted
Data not sent