Zr150 (12.5 Ton) Cooling - York PREDATOR R-410A Technical Manual

R-410a zh/zr/xp series 6-1/2 - 12-1/2 ton 60 hertz
Table of Contents

Advertisement

246824-YTG-G-1208

ZR150 (12.5 Ton) Cooling

Air on
Evaporator Coil
Total
1
Capacity
WB
CFM
(MBh)
(°F)
77
190.5
72
180.7
3125
67
171.0
62
158.6
77
199.8
72
189.6
3750
67
179.4
62
166.3
57
154.4
77
209.1
72
198.4
4375
67
187.7
62
174.1
57
161.6
77
218.4
72
207.3
5000
67
196.1
62
181.8
57
168.8
72
211.2
67
199.9
5625
62
185.3
57
172.0
72
215.2
67
203.6
6250
62
188.8
57
175.3
77
180.0
72
165.1
3125
67
150.2
62
137.5
77
188.2
72
172.7
3750
67
157.1
62
143.8
57
139.4
77
196.5
72
180.3
4375
67
164.0
62
150.1
57
145.5
77
204.8
72
187.8
5000
67
170.9
62
156.4
57
151.6
72
193.2
67
175.8
5625
62
160.9
57
156.0
72
198.6
67
180.7
6250
62
165.4
57
160.3
48
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
75°F
9.0
87.6
73.4
59.1
9.2
111.5
97.2
83.0
9.3
135.4
121.1
106.9
9.1
158.6
158.6
158.6
9.2
94.7
78.6
62.4
9.3
119.8
103.7
87.5
9.4
145.0
128.8
112.6
9.2
166.3
166.3
166.3
9.2
154.4
154.4
148.9
9.3
101.9
83.8
65.7
9.4
128.2
110.1
92.0
9.6
154.5
136.4
118.3
9.4
174.1
174.1
174.1
9.3
161.6
161.6
156.6
9.4
109.0
89.0
68.9
9.6
136.6
116.5
96.5
9.7
164.1
144.1
124.1
9.5
181.8
181.8
181.8
9.5
168.8
168.8
164.4
9.6
148.0
126.6
105.3
9.7
179.4
156.7
135.4
9.5
185.3
185.3
185.3
9.5
172.0
172.0
169.8
9.5
159.4
136.7
114.0
9.7
194.6
169.4
146.7
9.5
188.8
188.8
188.8
9.4
175.3
175.3
175.3
95°F
11.9
75.6
61.3
46.9
11.8
99.3
85.0
70.6
11.7
123.0
108.6
94.3
11.5
137.5
133.0
114.6
12.0
83.2
67.2
51.2
11.9
109.0
93.0
77.0
11.7
134.8
118.8
102.8
11.6
143.8
140.8
124.8
11.6
139.4
139.4
125.8
12.0
90.7
73.0
55.4
11.9
118.6
101.0
83.3
11.8
146.6
128.9
111.2
11.6
150.1
148.6
135.1
11.7
145.5
145.5
136.1
12.1
98.3
78.9
59.6
12.0
128.3
109.0
89.6
11.9
158.4
139.0
119.6
11.7
156.4
156.4
145.3
11.7
151.6
151.6
146.4
12.0
138.6
117.4
96.2
11.9
169.6
149.7
128.5
11.7
160.9
160.9
155.4
11.7
156.0
156.0
153.4
12.0
148.9
125.9
102.9
11.9
180.7
160.4
137.4
11.7
165.4
165.4
165.4
11.8
160.3
160.3
160.3
Temperature of Air on Condenser Coil
Total
1
Capacity
(MBh)
75
70
65
-
-
-
185.2
68.8
-
-
172.9
92.7
78.4
-
160.6
150.5
136.2
122.0
148.0
-
-
-
194.0
71.3
-
-
181.1
96.4
80.3
-
168.3
157.9
141.8
125.6
155.1
132.7
116.6
100.4
146.9
-
-
-
202.8
73.9
-
-
189.3
100.2
82.1
-
175.9
165.4
147.3
129.2
162.1
138.5
120.4
102.3
153.5
-
-
-
211.6
76.5
-
-
197.5
104.0
84.0
-
183.5
172.9
152.9
132.8
169.1
144.3
124.3
104.2
160.2
83.9
-
-
202.2
114.0
92.7
-
187.8
169.5
148.2
126.8
173.1
148.5
127.1
105.8
164.0
91.4
-
-
206.9
124.0
101.4
-
192.2
166.2
143.5
120.9
177.1
152.6
130.0
107.3
167.8
-
-
-
168.2
56.3
-
-
153.8
80.0
65.6
-
139.5
100.2
85.9
71.5
127.9
-
-
-
175.5
60.9
-
-
160.6
86.7
70.7
-
145.6
108.8
92.8
76.8
133.5
109.8
93.8
77.7
130.3
-
-
-
182.9
65.6
-
-
167.3
93.5
75.8
-
151.8
117.4
99.7
82.0
139.2
118.4
100.7
83.1
135.7
-
-
-
190.3
70.2
-
-
174.1
100.3
80.9
-
157.9
126.0
106.6
87.2
144.8
127.1
107.7
88.4
141.2
75.1
-
-
178.5
107.3
86.1
-
161.8
134.2
113.0
91.8
148.4
132.2
111.0
89.8
144.7
79.9
-
-
182.8
114.4
91.4
-
165.8
142.4
119.4
96.4
152.0
137.3
114.3
91.3
148.3
Sensible Capacity (MBh)
Total
Input
Return Dry Bulb (°F)
2
(kW)
90
85
80
85°F
10.5
81.6
67.3
53.0
10.5
105.4
91.1
76.8
10.5
129.2
114.9
100.6
10.3
148.0
148.0
139.6
10.6
89.0
72.9
56.8
10.6
114.4
98.3
82.2
10.6
139.9
123.8
107.7
10.4
155.1
155.1
149.5
10.4
146.9
146.9
137.3
10.7
96.3
78.4
60.5
10.7
123.4
105.5
87.6
10.7
150.6
132.7
114.8
10.5
162.1
162.1
159.3
10.5
153.5
153.5
146.4
10.8
103.6
83.9
64.2
10.8
132.4
112.7
93.0
10.8
161.2
141.5
121.8
10.6
169.1
169.1
169.1
10.6
160.2
160.2
155.4
10.8
143.3
122.0
100.8
10.8
174.5
153.2
131.9
10.6
173.1
173.1
173.1
10.6
164.0
164.0
161.6
10.8
154.1
131.3
108.5
10.8
187.7
164.9
142.0
10.6
177.1
177.1
177.1
10.6
167.8
167.8
167.8
105°F
13.3
71.8
58.0
43.9
13.2
95.1
81.0
66.9
13.0
118.4
103.9
89.8
12.9
127.9
125.7
110.1
13.3
79.5
63.7
47.8
13.2
104.5
88.6
72.8
13.1
129.4
113.6
97.7
12.9
133.5
132.1
119.8
13.0
130.3
130.3
117.1
13.4
87.3
69.3
51.7
13.3
113.9
96.3
78.7
13.1
140.5
123.3
105.6
13.0
139.2
138.4
129.5
13.0
135.7
135.7
126.6
13.4
95.1
75.0
55.6
13.3
123.3
104.0
84.6
13.2
151.6
132.9
113.6
13.0
144.8
144.8
139.2
13.1
141.2
141.2
136.1
13.3
133.3
112.3
91.2
13.2
158.7
143.5
122.5
13.0
148.4
148.4
145.6
13.1
144.7
144.7
142.2
13.3
143.3
120.6
97.9
13.2
165.8
154.1
131.4
13.0
152.0
152.0
152.0
13.1
148.3
148.3
148.3
Johnson Controls Unitary Products
75
70
65
-
-
-
62.5
-
-
86.3
72.0
-
125.3
111.1
96.8
-
-
-
66.1
-
-
91.6
75.5
-
133.4
117.3
101.2
121.2
105.2
89.1
-
-
-
69.7
-
-
96.9
79.0
-
141.4
123.5
105.6
128.5
110.6
92.7
-
-
-
73.3
-
-
102.1
82.4
-
149.4
129.7
110.0
135.7
116.0
96.3
79.5
-
-
110.7
89.4
-
151.9
130.6
109.3
140.3
119.1
97.8
85.6
-
-
119.2
96.4
-
154.3
131.5
108.6
145.0
122.1
99.3
-
-
-
52.8
-
-
75.7
61.6
-
96.0
81.9
67.8
-
-
-
56.9
-
-
81.9
66.0
-
104.0
88.1
72.2
101.2
85.4
69.5
-
-
-
61.0
-
-
88.0
70.4
-
111.9
94.3
76.6
109.0
91.3
73.7
-
-
-
65.2
-
-
94.2
74.8
-
119.8
100.4
81.1
116.7
97.3
77.9
70.2
-
-
101.5
80.4
-
124.6
103.5
82.5
121.1
100.1
79.1
75.2
-
-
108.7
86.1
-
129.3
106.6
84.0
125.6
102.9
80.2