Outdoor Error Code For Mds-M Pcb - McQuay MDS Series Service Manual

Multi digital scroll system
Table of Contents

Advertisement

6.5 Outdoor Error Code for MDS-M PCB

Error
Description
Code
R22
Wrong combination of
PCB and software
R410
Wrong combination of
PCB and software
ERSE
Wrong dipswitch setting
EC00
00# - 47# indoor unit
-
communication failure
EC47
6
ER48
Digital compressor
overload
ER49
Fixed compressor 1
overload
ER50
Fixed compressor 2
overload
ER51
Fix compressor 3
overload
ER52
Discharge pressure too
high
ER53
Suction pressure is too
low
Outdoor unit's IC error
ER54
70
PCB hardware is designed for R22 but software for R410A unit is installed into it.
PCB hardware is designed for R410A but software for R22 unit is installed into it.
Outdoor dipswitch setting wrong
Outdoor model dipswitch setting wrong
Indoor 00# - 47# and outdoor communication wire broken
Indoor 00# - 47# and outdoor communication wire loose
Indoor 00# - 47# and outdoor communication wire A B reverse
Indoor 00# - 47# and outdoor jump wire not correct, still on update status
Indoor 00# - 47# and outdoor PCB program not compatible
Indoor 00# - 47# and outdoor PCB abnormal
Digital compressor operating current too high, overload protector OL4 on
Fixed compressor 1 operating current too high, overload protector OL1 on
Fixed compressor 2 operating current too high, overload protector OL2 on
Fixed compressor 3 operating current too high, overload protector OL3 on
Outdoor motor broken (cooling)
Outdoor circulating air short-circuit (cooling)
Outdoor heat exchanger too dirty (cooling)
Outdoor ball valve not open
Indoor circulating air short-circuit (heating)
Indoor heat exchanger too dirty (heating)
Indoor unit filter blocked by dirt (heating)
Indoor EXV not on properly (heating)
Refrigerant over charged
Outdoor PCB high pressure output port abnormal
Pressure sensor broken
Pressure switch broken
Outdoor ball valve not open
Outdoor heat exchanger efficiency too low when heating
Outdoor motor run abnormally when heating
Refrigerant leakage or insufficient
Outdoor PCB low pressure output port abnormal
Low pressure sensor broken
Outdoor PCB chip read faultily at the very beginning when power on
Outdoor PCB chip broken
Possible Causes
Page
88
88
89
76
77
78
82
Service Manual SM-MDS_(ii)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents