Confirm Outdoor Dipswitch Setting; Setting Up Mdom Pcb - McQuay MDS Series Service Manual

Multi digital scroll system
Table of Contents

Advertisement

5.6 Confirm Outdoor Dipswitch Setting

Similar to indoor, there are also some settings need to be done for outdoor unit. The unit capacity and model
type are usually set before ship out from the factory. However, it is advisable to check on the dipswitch again
before power up the outdoor. As for the outdoor address, it is only required when there is a series of outdoors
connected and control by the central control and monitoring software.
For outdoor model, there are two type of outdoor board:
MDOM PCB – For MDS-A series and 5MDS 50/60/70 B/BR
MDS-M PCB – (5)MDS 80-500 B/BR

5.6.1 Setting Up MDOM PCB

Basically, setting up MDOM PCB requires 3 steps:
1. Set up dipswitch 1 (J1)
2. Set up dipswitch 2 (J2)
3. Set up indoor quantity (K2 and K1 button)
5
0
Set up
For outdoor unit which runs on MDOM PCB, there are 2 set of dipswitches (J1 and J2). Besides
Dipswitch 1
this, there is also a setting mode to modify certain important parameters (K2 and K1 button).
(J1)
Please refer to page 14 for further description on their location.
For dipswitch 1 (J1), the main function is to determine the outdoor capacity. Dipswitch J1.1 and
J1.2 (EXV Initial Opening) is only use by R&D for testing purpose. During site commissioning, it
is advisable not to alter the setting unless advice by factory side. Dipswitch J1.3 is reserved for
future used. Dipswitch J1.4 to J1.7 is to determine the outdoor unit capacity.
52
S1
J1
1 2 3 4 5 6 7
EXV Initial
Opening
Reserved
J1.4
J1.5
J1.6
J1.7
0
1
0
1
0
0
0
0
0
0
0
1
0
0
1
0
0
1
1
0
ON
(1)
OFF (0)
MDS A Capacity
Capacity
3HP
4HP
5HP
6HP
7HP
Service Manual SM-MDS_(ii)

Hide quick links:

Advertisement

Table of Contents
loading