300 mA current leakage protec- tion (type B or B+). Before connecting unit to the electrical power supply, it is necessary to check whether earthing has been installed properly. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Total power of all external elements with 24 V supply may not exceed 15 W. External control Indication Cooling control 1.3 b Picture. External control elements connection UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Control panel connection and other cable thicknesses are specified in the wiring diagram! Remove protective screen tape, before mounting front cover on the con- trol panel! UAB KOMFOVENT we reserve the right to make changes without prior notice Yellow (A) ( ) White C5.1-20-05...
Holiday operation mode (see chapter Functions) Supply air humidity Energy recovery „Override“ mode operation Extract air humidity Air heater operation Alarm signal Extract (room) Air cooler operation air quality UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
When starting CF type AHU for the first time, it will be needed to perform heat exchanger calibration, which is used for frost prevention function (See 2.5.1.3). Start CF exchanger calibration? Temperature Temperature STARTING UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
1 / 3 Calibrated 2.5.1.4. Detailed information All temperature sensor readings, functioning of sepa- rate air handling unit elements and other detailed in- formation is available in this menu. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
“Air quality function”. Reset settings A room sensor with the analogue output (0...10 V DC) should be de- signed for this function. Factory setting. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Reset settings In ventilation intensity control, this function has top priority over “Out- door compensated ventilation” and “VAV” functions. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Delete holiday 2.5.4. Settings Menu Settings This menu is for air handling unit and the user param- eter setting. Overview Scheduling Air handling unit Functions Settings Personalization UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
/h, and the B6 input value – 7 V, the unit will supply constant air volume of 560 m /h, i. e., 70 % of the set value. The same applies to the exhaust air only by B7 input. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
All you need is to connect the unit to the computer, local area network or the Internet using a network cable. Standard CAT 5 network cable UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
(see 2.5.1.3.). Temporary mode, which can be acti- The service mode is switched off by 127B Service mode vated by the service personnel. simply deleting the alert message. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Page 17
Low pressure on com- Compressor system is leaky or the Indentify the cause and eliminate it. pressor amount of refrigerant is insufficient. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Page 18
/ several of them are broken. 125A, 127A Controller failure Main controller module fault. Replace the main controller. UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Page 19
UAB KOMFOVENT we reserve the right to make changes without prior notice C5.1-20-05...
Page 20
UAB KOMFOVENT PARTNERS TECHNINĖS PRIEŽIŪROS SKYRIUS / J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at SERVICE AND SUPPORT Tel. +370 5 200 8000 Ventilair group www.ventilairgroup.com service@komfovent.com ООО «КОМФОВЕНТ» ACB Airconditioning www.acbairco.be Россия, Москва ул. Выборгская д. 16, REKUVENT s.r.o. www.rekuvent.cz стр.