Troubleshooting
Step 2: Check Power Being Supplied to Damper via Board
© 2015 Goodman Manufacturing Company, L.P.
Set meter to ac voltage, and
test power at board output
to the dampers not
responding.
If no power, the 500mA
breaker could be tripped.
Disconnect power to board,
remove damper wires, and
retest.
If power is restored, the
500mA breaker reset itself.
Check disconnected wiring
back to damper for shorts.