Field Setting; Setting The Address - Fujitsu AirStage AUUA4TLAV2 Installation Manual

Indoor unit (cassette type)
Hide thumbs Also See for AirStage AUUA4TLAV2:
Table of Contents

Advertisement

● When function setting is "Emergency stop" mode.
Input
Connector
Ch1 of CNA01 or
Edge
CNA02
Ch1
CNA01 or
Pulse
CNA02
Ch2
* All indoor units of same refrigerant system stops when Emergency stop operates.
● When function setting is "Forced stop" mode.
Input
Connector
Ch1 of CNA01 or
Edge
CNA02
Ch1
CNA01 or
Pulse
CNA02
Ch2
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
* When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
• Selection method of functions
"Operation/Stop" mode or "Emergency stop" mode, "Forced stop" mode can be selected
with function setting of indoor unit.
● Forced thermostat off function ("Edge" input only)
*If function setting "60" is set to "00"
Input
Connector
Ch1 of CNA01 or
Edge
CNA02
(2) External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft (25 m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
When indicator etc. are connected directly
Indicator 1
Indicator 2
Indicator 3
Indicator 4
Connected unit
● When connecting with unit equipped with a power supply
Connected
device 1
Connected
device 2
Connected
device 3
Connected
device 4
Connected unit
Relay (locally purchased)
Operation behavior
* If function setting "60" is set to "00"
Connector
Output voltage
External output 1
Pins 1-2
DC 12 V
External output 2
Pins 1-3
DC 12 V
CNB01
External output 3
Pins 1-4
DC 12 V
External output 4
Pins 1-5
DC 12 V
Input signal
Command
OFF → ON
Emergency stop
ON → OFF
Normal
OFF → ON
Emergency stop
OFF → ON
Normal
Input signal
Command
OFF → ON
Forced stop
ON → OFF
Normal
OFF → ON
Forced stop
OFF → ON
Normal
Input signal
Command
OFF → ON
Thermostat off
ON → OFF
Normal
P.C.B
P.C.B
Status
0 V
Stop
Operation
0 V
Normal
Error
0 V
Indoor unit fan stop
Indoor unit fan operation
0 V
External heater OFF
External heater ON
● Indoor unit fan setting for external heater
Fan setting when turning ON output to the connected external heater can be set by
changing Dip switch on PC board.
Dip switch
[SET2 SW3]
OFF
(Factory setting)
ON

7. FIELD SETTING

There are 3 methods for address setting by FIELD SETTING as follows.
Set by either of the methods.
Each setting method is described (1) to (3) below.
(1) IU AD, REF AD SW settings: This section (7.1. Setting the address)
(2) Remote controller settings:
(3) Automatic address settings: Refer to the outdoor unit manual for detailed setting
Be sure to turn OFF the power before performing the field setting.
Do not operate any switches other than prescribed, as it can cause the unit to operate
improperly or malfunction.
Use an insulated screwdriver to set the DIP switches.

7.1. Setting the address

Manual address setting method
The indoor unit address and the refrigerant circuit
address can also be set up through the wireless
remote controller.
CAUTION
Use an insulated screwdriver to set the DIP
switches.
Setting
Indoor unit address
• Rotary switch [IU AD × 1]
CNB
(Factory setting "0")
01
• Rotary switch [IU AD × 10]
(Factory setting "0")
When connecting multiple indoor units to 1
refrigerant system, set the address at IU AD SW
as shown in the Table A.
Refrigerant circuit address
• Rotary switch [REF AD × 1]
(Factory setting "0")
• Rotary switch [REF AD × 10]
(Factory setting "0")
In the case of multiple refrigerant systems, set
REF AD SW as shown in the Table A for each
CNB
refrigerant system.
01
Set to the same refrigerant circuit address as the
outdoor unit.
• If working in an environ-
ment where the wireless
remote controller can be
used, the addresses can
also be set using the
remote controller.
• If setting the addresses
using the wireless
remote controller, set
the indoor unit address
and refrigerant circuit
address to "00".
(For information on set-
ting using the wireless
remote controller.)
* Do not set the indoor
unit address (IU AD
SW) at 64 to 99.
It may result in failure.
Fan setting when
ON is output to the
Explanation
external heater
OFF
For the fan setting details, see the
Design & Technical Manual.
ON
Refer to the wired or wireless remote controller manual
for detailed setting information. (Set IU AD, REF AD
SW to 0)
information. (Set IU AD, REF AD SW to 0)
CAUTION
For indoor
unit address
IU AD
×10
SET3
Setting
range
0 to 63
IU AD × 10
0 to 99
REF AD × 10 REF AD × 1
Table A
Rotary switch
Address
Address
setting
REF AD SW
Refrigerant
Indoor unit
circuit
× 10
× 1
0
0
0
1
0
1
2
0
2
3
0
3
4
0
4
5
0
5
10
1
0
11
1
1
99
9
9
For refrigerant
circuit address
REF AD
RC AD
×1
×10
×1
SET4
Type of switch
Setting example "2"
IU AD × 1
Setting example "63"
Rotary switch
setting
IU AD SW
× 10
× 1
0
0
0
1
0
1
2
0
2
3
0
3
4
0
4
5
0
5
10
1
0
11
1
1
63
6
3
En-10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents