A precision instrument for the measuring and
documentation of water flow in heating, cooling
and drinking water systems.
PFM-2000 is a meter for pressure and flow meas-
urements across, for example, balancing valves.
Valve characteristics for a number of valves from
different manufacturers are stored in the
PFM-2000's memory. The valve database is
updated continuously. Every instrument unit is
delivered with a CD-ROM containing demo
programs, valve data and manuals.
SPECIFICATIONS
Measuring Range
Pressure Difference: up to 150 kPa,
Static Pressure:
Accuracy
Pressure Difference: <10 kPa ± 0.1 kPa
Flow:
Resolution
Pressure Difference: 0.01 kPa,
Static Pressure:
Flow:
Optional features and accessories available for this
Macon product are an extra charge, and not included
in the standard model price.
www.maconbalancing.com
at total pressure <1000 kPa
Max 2000 kPa
up to 1000 kPa
>10 kPa ± 1% of
metered value
As for pressure + the
valve's deviation
at total pressure <100 kPa
0.1 kPa,
at total pressure >100 kPa
10 kPa
0.001 I/s
Model PFM-2000
Environment
Temperature media:
Temperature Storage:
Humidity, not controlled:
Power Supply
Capacity:
R6 Rechargable NiMH batteries (6)
Included in Delivery
Meter x 1
Sensor x 1
Cable x 1
Hoses & Connectors x 2
Battery Charger x 1
Durable Case x 1
Allen Key, 3mm x 1
Allen Key, 5 mm x 1
Manual x 1
Program Disc x 1
Calibration Protocol x 1
Tunstall Corporation
118 Exchange Street · Chicopee, MA 01013
Phone (413) 594-8695 · Fax (413) 598-8109
Section: Components
66
Pressure Flow Meter
Submittal Data
-10º C to 100º C
-20º C to 60º C
Max 90% RH
1500mAh
Bulletin-MB-PFM-2000-0915