Tunstall Macon STV Series Manual page 11

Table of Contents

Advertisement

FEATURES
Accurate and precise flow measurement
Accurate and precise flow balancing
Positive shut-off
"Y" Pattern Globe style design
Multi-turn, 360º handwheel with vernier scale and
digital readout
Built in memory stop
Offsetting Pressure/Temperature ports, self sealing with
optional Drain Kits
Wide variety of accessories available
NOMINAL DIMENSIONS & WEIGHTS
SIZE
A
Length
in
mm
in
23.6
8"
200
mm
600
in
28.7
10"
250
mm
730
in
33.5
12"
300
mm
850
FLOW CALCULATIONS
The Minimum Flow is calculated from the minimum recommended pressure drop,
1 ft WG (=3.0 kPa)
The Nominal Flow is calculated from the maximum setting of the valve and the minimum recommended pressure drop,
2 ft WG (=6.0 kPa)
The Maximum Flow is calculated from the maximum setting of the valve and the maximum pressure drop,
20 ft WG (=60.0 kPa)
Optional features and accessories available for this
Macon product are an extra charge, and not included
in the standard model price.
www.maconbalancing.com
WEIGHT
B
Handwheel
Height
Turns
lbs
kg
13.5
260
118
11
343
16.0
390
177
11
406
19.0
490
223
11
483
SPECIFICATIONS
Pressure Ratings:
Temperature Ratings:
Body:
End Connections:
Gaskets:
Seat Seal:
Valve Selection Guide
Minimum
Flow
GPM
30
LPM
114
GPM
47
LPM
178
GPM
43
LPM
163
Tunstall Corporation
118 Exchange Street · Chicopee, MA 01013
Phone (413) 594-8695 · Fax (413) 598-8109
Section: Components
11
Model STVE
8" to 12"
Submittal Data
250 psi / 16 bar (PN 16)
-14ºF to 250ºF (-10ºC to 120ºC)
Cast Iron
ANSI 125# Flanged
EPDM
PTFE
Nominal
Maximum
Range of Flow
Flow
450 - 750
2415
1703 - 2839
9142
750 - 1300
4050
2839 - 4921
15330
1300 - 1600
5115
4921 - 6057
19360
Bulletin-MB-STVE-1704