5. INSTALLATION

*WARNING*
STATIC ELECTRICITY - Installation, wiring, configuration, or other activity may
require handling or disassembly of the transmitter circuit card assemblies (CCA).
Handling of a CCA without proper precautions can expose the electronic components
to the possible damage from static electricity discharge.
Try to ensure you are grounded when handling a CCA. If continuous grounding is
not practical, touch some metal item, which is known to be grounded.
walking around after this as you can regenerate a static charge. Note that the
smallest static discharge, which is noticeable by humans, is 3,000 Volts.
noticeable, significant discharge may be as high as 30,000 Volts

5.1 Mounting

The QTS-6100 Sensor/Transmitter should be mounted where the gas to be measured is most likely to be
present. This location will be dependent on the source of the target gas and whether that gas is lighter or
heavier than air. Air circulation and mixture should also be taken into account. The following table
provides recommended mounting location based on the molecular weight of the gas:
M
#
G
ODEL
AS
QTS-61110 Hydrogen Sulphide
QTS-61115 Hydrogen Cyanide
QTS-61120 Chlorine
QTS-61123 Chlorine Dioxide
QTS-61125 Hydrogen Chloride
QTS-61140 Sulphur Dioxide
QTS-61150 Nitrogen Dioxide
QTS-61160 Carbon Monoxide
QTS-61190 Nitric Oxide
QTS-61211 Hydrogen
QTS-61220 Ammonia
QTS-61230 Ethylene Oxide
QTS-61240 Ozone
Where possible, the sensor/transmitter should be mounted where it is accessible for the purposes of routine
re-calibration and periodic sensor replacement. Sufficient room should be left to allow the enclosure cover
to be removed. On units with industrial explosion-proof enclosures, sufficient room should be left to allow
the connection of the calibration adapter to the sensor assembly. For sensor element replacement there will
need to be enough room to reach into the sensor assembly.
*CAUTION*
The sensor assemblies on the industrial explosion-proof enclosures are designed for
integral mounting only.
transmitter may be possible, but may require special wiring considerations. If you
must remote mount the sensor from the transmitter please consult the factory for
recommendations.
B71050-021-000-RB.doc
JUL. 18, 2007
QTS-6000 Series
Analog Transmitter/Sensor
S
YMBOL
H2S
HCN
Cl2
ClO2
HCl
SO2
NO2
CO
NO
H2
NH3
C2H4O
O3
Table 1 - Sensor/Transmitter Mounting Location
Remote mounting of the sensor assembly from the
M
L
OUNT
OCATION
Low
9 to 18" (230 to 460 mm) above floor
Mid
48 to 72" (1200 to 1800 mm) above floor
Low
9 to 18" (230 to 460 mm) above floor
Low
9 to 18" (230 to 460 mm) above floor
Mid
48 to 72" (1200 to 1800 mm) above floor
Low
9 to 18" (230 to 460 mm) above floor
Low
9 to 18" (230 to 460 mm) above floor
Mid
48 to 72" (1200 to 1800 mm) above floor
Mid
48 to 72" (1200 to 1800 mm) above floor
High
9 to 18" (230 to 460 mm) below ceiling
High
9 to 18" (230 to 460 mm) below ceiling
Low
9 to 18" (230 to 460 mm) above floor
Mid
48 to 72" (1200 to 1800 mm) above floor
7
ELECTROCHEMICAL TRANSMITTER
PRODUCT MANUAL